T&D Weaver Construction <br /> Plan Check Number: M2303-045, First Building Review <br /> March 21, 2023 <br /> 2. Roof Plan 1/1-1-04 shows a new MUA fan centered on the framing. The following comments <br /> should be addressed: <br /> a. The weight of the unit should be specified in the schedule on Sheet H-07. See IBC Section <br /> 1603.1.8. <br /> b. Calculations should be submitted for review substantiating the capacity of the roof framing <br /> to support the new rooftop equipment, including the underhung hood, in addition existing <br /> dead and roof loads (e.g., snow, etc.). See IBC Section 1604.2. <br /> 3. The hood should comply with the minimum 18-inch required clearance per IMC Section 507.2.6. <br /> The clearance is required on all sides and the top. Alternatively, the drawings should specify <br /> construction complying with the reduced clearances per Table 308.4.2. Note that modifications <br /> to the building structure are required to be performed as part of the Building permit application <br /> per comments above. <br /> 4. Continuing with the previous comment, the exhaust duct for the hood is required to provide the <br /> minimum 18-inch required clearance per IMC Section 506.3.6. Alternatively, construction per <br /> one of the exceptions should be specified. <br /> 5. Details specifying the vertical support and lateral restraint for the hood should be included in <br /> the drawings. The details should be specific to the current project; the manufacturer's generic <br /> typical details do not satisfy this requirement. See IBC Sections 1603.1, 1604.2, and 1604.4. <br /> 6. The upblast exhaust fan details on Sheet H-07 should specify a flexible electrical cable and <br /> restraint. See IMC Section 506.5.4. <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with <br /> the laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Drew Martin, P.E., S.E. <br /> Associate Engineer/ Commercial Plans Examiner <br /> (425)257-8813 <br /> dmartin@everettwa.gov <br /> S:\BMartin\2023\M2303-045_R1.docx <br /> S <br /> 3200 Cedar Street 425.257.8810 everetteps@everettwa.gov <br /> Everett,WA 98201 425.257,8857 fax everettwa.gov/permits <br /> Page 2 of 2 <br />