Laserfiche WebLink
Form 5.4 <br /> Requirements for Transfer Lines of 1'/2-inch Diameter or Larger, <br /> Liquid Withdrawal from Containers <br /> A B C D E F <br /> Installed in the NFPA 58 <br /> Item Appurtenance Appurtenance Provided with the Feature facility? Section <br /> Reference <br /> Yes No (2020 Edition) <br /> Installed within 20 ft.of lineal pipe from the <br /> nearest end of the hose or swivel-type ✓❑ ❑ 6.14.2 <br /> connections. <br /> Automatic shutoff through thermal(fire) <br /> actuation element with maximum melting point ✓❑ ❑ 6.14.6 <br /> of 250 OF. <br /> Temperature-sensitive element installed within 5 <br /> ft. from the nearest end of the hose or swivel- ✓❑ ❑ 6.14.6 <br /> type piping connected to liquid transfer line. <br /> Manually operated remote shutoff feature 6.14.12.1 <br /> Emergency provided for ESV. ❑ ❑ <br /> 1 shutoff valve Manual shutoff device provided at a remote <br /> (ESV) location,not less than 25 ft.,and not more than ✓❑ ❑ 6.44.12.2 <br /> (Ref§ 6.14) 100 ft. from the ESV in the path of egress. <br /> An ESV is installed on each leg of a multi-leg <br /> piping each of which is connected to a hose or a <br /> swivel-type connection on one side and to a ✓❑ El6 and <br /> header of 1'/2 inch in diameter or larger on the 6.21.2.1.2.E(1) <br /> other side. <br /> Breakaway protection is provided such that in <br /> any pull-away break will occur on the hose or El ❑ 6.14.8 <br /> swivel-type connection side while retaining intact <br /> the valves and piping on the plant side. <br /> Number of ESV's in liquid withdrawal service 1 <br /> Note: If more than one ESV is installed in the facility,use one Form 5.4 for each ESV. <br /> A- 7 <br />