Laserfiche WebLink
Form 5.5 <br /> Requirements for Vapor Transfer Lines 11/4-inch Diameter or Larger <br /> A B C D I E F <br /> Installed in NFPA 58 <br /> Item the facilit ? Section <br /> # Appurtenance Appurtenance Provided with the Feature Reference <br /> Yes No (2020 edition) <br /> Installed within 20 ft.of lineal pipe from the nearest ❑ ❑ 6.14.2 <br /> end of the hose or swivel-type connections. <br /> Automatic shutoff through thermal(fire)actuation ❑ ❑ 6.14.6 <br /> element with maximum melting point of 250 IF. <br /> Temperature-sensitive element installed within 5 ft. <br /> from the nearest end of the hose or swivel-type piping ✓❑ ❑ 6.14.6 <br /> connected to liquid transfer line. <br /> Emergency Manually operated remote shutoff feature provided for ❑ El6.14.12.1 <br /> g Y ESV. <br /> 1 shutoff valve Manual shutoff device provided at a remote location, <br /> (ESV) not less than 25 ft.,and not more than 100 ft. from the 0 ❑ 6.14.12.2 <br /> (Ref§ 6.14) ESV in the path of egress. <br /> An ESV is installed on each leg of a multi-leg piping <br /> each of which is connected to a hose or a swivel-type 0 ❑ 6.14.5 and <br /> connection on one side and to a header of 1-1/4 inch in 6.21.2.6(1) <br /> diameter or larger on the other side. <br /> Breakaway protection is provided such that in any pull- <br /> away break will occur on the hose or swivel-type 0 ❑ 6.14.8 <br /> connection side while retaining intact the valves and <br /> piping on the plant side. <br /> Installed downstream of the hose or swivel-type <br /> connection. <br /> ❑ El <br /> BCK is designed for this specific application. 0 ❑ 6.14.4 <br /> Backflow A BCK is installed on each leg of a multi-leg piping <br /> 2 check valve each of which is connected to a hose or a swivel-type 0 ❑ 6.14.5 <br /> (BCK)** connection on one side and to a header of 1-1/4 inch in <br /> diameter or larger on the other side. <br /> Breakaway protection is provided such that in any pull- <br /> away break will occur on the hose or swivel-type 0 ❑ 6.14.8 <br /> connection side while retaining intact the valves and <br /> piping on the plant side. <br /> ** In lieu of an emergency shutoff valve,the backflow check valve(BCK)is only permitted when flow is only <br /> into the container and it shall have a metal-to-metal seat or a primary resilient seat with metal backup,not <br /> hinged with a combustible material(6.14.3,6.14.4). <br /> If a check mark is made in the "No" column of any one of Form 5.3, Form 5.4 or <br /> Form 5.5, then these items must be addressed and brought into compliance with <br /> the specific edition of NFPA 58 that the facility was constructed to. <br /> If the LP-Gas facility is designed using ALTERNATE PROVISIONS for the <br /> installation of ASME CONTAINERS, then continue the analysis below. <br /> Otherwise skip Section 5.3 and qo to Chapter 6. <br /> A - 8 <br />