Structural Design Associates <br /> En ineerin Structures to Last <br /> SDAAIO012 <br /> Three vertical braces are present in the attic. see Image 5. The purpose of these framing members <br /> is unclear. The rafters which the braces are connected to show no signs of distress, are of the <br /> same dimension and spacing as the other rafters, and appear to be of the same quality and age as <br /> the other rafters. It is believed that these were installed to reduce the roof load on the exterior <br /> wall as the cantilevered floor joists below have sustained significant water damage and were <br /> poorly repaired, see Image 6. With these braces bearing on ceiling joists in the center of a room, <br /> the roof load is still being supported by the exterior wall. It is believed they were installed <br /> without the oversight of a design professional. The braces are not needed and may be removed <br /> once the lower-level framing is replaced. <br /> Please see attached plans for framing member replacements and verification of existing header <br /> sizes and grades. <br /> No destructive tests were conducted during this site visit. If during construction it is found that <br /> any of the conditions differ from what has been expressed above.notify this office immediately <br /> for a revision of the design. Please contact this office if you have any questions concerning this <br /> letter. <br /> Respectfully, <br /> Chris Lalonde. E.I.T. Chris Covington, P.E. <br /> y. C°V <br /> WAS <br /> y'�C <br /> C �e 343113 <br /> MAR 2 2 M 4 <br /> 3006 Rucker Ave. Nverea,\YVA 98201 Ph:425-339-0293 <br /> sdaeverett.com <br />