Architects and Engineers Specifications <br /> The power supply shall be Wheelock POWERPATH— Series PS-8, or equivalent.The unit shall be stand alone power supply intended <br /> for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC).The unit shall be UL 864 Listed for <br /> power limited operation of outputs and comply with NFPA 70(NEC),article 760. <br /> The power supply shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is <br /> connected. <br /> The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a <br /> "Dry contact"opening.The units shall be 8 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall <br /> operate over the voltage range of 8 to 33 VDC or FWR.The primary application of the unit shall be able to expand fire alarm system <br /> capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories <br /> or functions. The power supply shall provide four Class"B", two Class"A", or two Class "B"and one Class "A" NAC circuit(s). Eight <br /> Class"B"or Four Class"A"circuits shall be available with an optional PS-EXP module.The PS-8 unit shall supply up to 240 mA of <br /> auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm. <br /> The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at maximum rate of 0.750 Amps per <br /> hour. <br /> Input activation options shall be from not less than two NAC circuits or Dry Contact closures.These inputs shall have the capability of <br /> being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class"B" <br /> applications or 3 amperes each for Class"A"The outputs shall be programmable to generate a steady or Temporal (Code 3) output <br /> and or a synchronized strobe or horn output.The power supply shall provide independent loop supervision for either Class"A"or Class <br /> "B"FACP NAC circuits and shall have the capability to"steer"all alarm or trouble conditions to either incoming NAC circuit.The units <br /> shall have common trouble terminals.The power supply shall be powered from a 120 VAC source with a current consumption of xx <br /> amperes max.The unit shall incorporate short circuit protection with auto reset.The power supply shall incorporate a built in battery <br /> charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure.The charger <br /> shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby <br /> current for battery back up shall be 0.129 Amps max.The power supply shall have the ability to latch trouble LED's so the circuit in <br /> trouble can be identified.The cabinet dimensions shall be 17"H x 15"W x 5.5"D. <br /> The power supply shall be Wheelock POWERPATH— Series PS-6, or equivalent.The unit shall be stand alone power supply intended <br /> for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC).The unit shall be UL 864 Listed for <br /> power limited operation of outputs and comply with NFPA 70(NEC),article 760. <br /> The power supply shall support a full 6A of notification power even if the battery is in a degraded mode and only AC power is <br /> connected. <br /> The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a <br /> "Dry contact"opening.The units shall be 6 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall <br /> operate over the voltage range of 8 to 33 VDC or FWR.The primary application of the unit shall be able to expand fire alarm system <br /> capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories <br /> or functions. The power supply shall provide four Class"B", two Class"A", or two Class "B"and one Class"A" NAC circuit(s). Eight <br /> Class"B"or Four Class"A"circuits shall be available with an optional PS-EXP module.The PS-6 unit shall supply up to 200 mA of <br /> auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm. <br /> The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at a maximum rate of 0.750 Amps <br /> per hour. <br /> Input activation options shall be from not less than two NAC circuits or Dry Contact closures.These inputs shall have the capability of <br /> being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class"B" <br /> applications or 3 amperes each for Class"A" The outputs shall be programmable to generate a steady or Temporal (Code 3) output <br /> and or a synchronized strobe or horn output.The power supply shall provide independent loop supervision for either Class"A"or Class <br /> "B"FACP NAC circuits and shall have the capability to"steer"all alarm or trouble conditions to either incoming NAC circuit.The units <br /> shall have common trouble terminals.The power supply shall be powered from a 120 VAC source with a current consumption of xx <br /> amperes max.The unit shall incorporate short circuit protection with auto reset.The power supply shall incorporate a built in battery <br /> charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure.The charger <br /> shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby <br /> current for battery back up shall be 0.130 Amps max.The power supply shall have the ability to latch trouble LED's so the circuit in <br /> trouble can be identified.The cabinet dimensions shall be 17"H x 13"W x 3.5"D. <br /> WARNING:PLEASE READTHESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS <br /> PRODUCT.FAILURETO COMPLY WITH ANY OFTHESE INSTRUCTIONS,CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLA- <br /> TION AND/OR OPERATION OFTHESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR <br /> DEATH TO YOU AND/OR OTHERS. <br /> NOTE:Due to continuous development of our products,specifications and offerings are subject to change without notice in accor- <br /> dance with Wheelock Inc.standard terms and conditions. <br /> MIAFAS <br /> WE ENCOURAGE AND SUPPORT NICET CERTIFICATION <br /> 1 YEAR WARRANTY <br /> S9100 PS-6&8 06/11 <br /> NJ Location <br /> 273 Branchport Ave. <br /> Long Branch,NJ 07740 <br /> :00 <br /> ,. <br /> www.coopern <br /> Cooper Notification is Wheelock' AMEDC SAFEPATH® WAVE s COOPER Notification <br />