Laserfiche WebLink
POWERPATH"Operating Modes(refer to Installation Manual): <br /> Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening <br /> on DRY1 or DRY2.The unit returns to standby mode when the input is deactivated. <br /> Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification <br /> appliances.Audibles can also be silenced in this mode while the strobes continue to flash. <br /> In>Out Sync Mode:Accepts a synchronization signal on the input to provide a coded output or synchronized output.This signal <br /> may come from a FACP,another POWERPATH or a Wheelock DSM synchronization module.Caution:Do not use strobes on coded <br /> output circuits. <br /> True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the <br /> input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes <br /> on coded output circuits. <br /> Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns, <br /> bells or chimes.Caution:Do not use strobes on coded output circuits. <br /> Specifications and Ordering Information <br /> Model Number Order Input Voltage/Current Approvals <br /> Code UL I CSFM FM <br /> PS-6 105530 6 amp,red enclosure X X X <br /> PS-66 100257 6 amp,black enclosure X X X <br /> PS-8 105531 8 amp,red enclosure X X X <br /> PS-86 105830 8 amp,black enclosure X X X <br /> PS-6EXP 105083 6 amp power supply with preinstalled expansion module X X X <br /> PS-8EXP 105084 8 amp power supply with preinstalled expansion module X X X <br /> PS-EXP 105534 4 class B or 2 class A expansion module X X X <br /> PS-EXP-RETRO 105527 Field upgrade kit for models prior to January 20101 X X X <br /> Input Circuit Input Voltage and Current <br /> X=Approved <br /> Input voltage Range 8 to 33 VDC *=Pending <br /> Input Current @ 12 VDC 0.005 amps #=Contact Technical <br /> Input Current @ 24 VDC 0.005 amps Support for additional <br /> inforamation on upgrade <br /> Output Circuit Output Voltage and Current options <br /> Four(4)Class B or <br /> Two(2)Class A or <br /> One(1)Class A and Two(2)Class"B"or 24 VDC @ up to 3 amps per curcuit <br /> 8 Class B or 4 Class A <br /> (optional PS-EXP module necessary) <br /> Continuous duty up to 3 Amps per circuit,up to 4 Amps maximum per panel <br /> Standby Current 0.129 Amps <br /> Alarm Current 0.129 Amps <br /> Primary PS-6(120 VAC models) 105 to 130 VAC,50/60 Hz @ 4.25 Amps <br /> Primary PS-8(120VAC models) 105 to 130 VAC 50/60 Hz @ 5.32 Amps <br /> Primary PS-6E(240 VAC models) 210 to 260 VAC,50/60 Hz @ 2.42 Amps <br /> Primary PS-8E(240 VAC models) 210 to 260 VAC 50/60 Hz @ 3.22 Amps <br /> Secondary Power Charging Capacity 32 Amp hours @ 0.750 Amps per hour <br /> Enclosure can house up to two 12 AH batteries <br /> Aux Output <br /> CP Mode PS-6 up to 75 mA PS-8 up to 250 mA <br /> MP Mode 2.5A during non alarm <br /> Model Dimensions Weight Comments <br /> PS-6/PS-613 17"H x 13"W x 3.5"D 11.5lbs.(Ship)9.4lbs(Unit) Small profile <br /> PS-8/PS-813 17"H x 15"W x 5.5"D 17.7lbs(Ship) 15.6lbs(Unit) Additional room for modules <br /> Plugs into main pcb on all <br /> PS EXP 4.3"H x 3.7"W x 1"D 1 lb.(Ship&Unit) models <br />