GENERAL PLUMBING NOTES LEGEND ABBREVIATIONS on <br /> GENERAL: 11. MINIMUM PIPING INSULATION THICKNESS HEATING AND HOT-WATER SYSTEMS (STEAM, STEAM <br /> COLD WATER PIPING ACM AREA CONSTRUCTION MANAGER <br /> 1. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH ALL LOCAL CODES 5. THE GREASE INTERCEPTOR SHALL BE VENTED. CONDENSATE, HOT-WATER HEATING AND DOMESTIC WATER SYSTEMS). PLEASE REFER TO THE <br /> AND ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. LATEST EDITION OF IECC FOR MINIMUM PIPE INSULATION THICKNESS (TABLE C403.12.3) <br /> 6. ACCESS TO THE GREASE INTERCEPTOR SHALL BE PROVIDED WITH TWO (2) TEMPERED WATER PIPING (110'F) AVB ATMOSPHERIC VACUUM BREAKER 2 I¢- <br /> 2. ALL PLUMBING WORK SHALL BE PERFORMED BY A LICENSED PLUMBER. 24-IN. MANHOLES. COVER SHALL PROVIDE WATER/GAS-TIGHT SEAL AND HAVE MINIMUM INSULATION THICKNESS (IN INCHES) P c <br /> A MINIMUM 16,000 LBS. LOAD CAPACITY. ALL SURFACE WATER MUST DRAIN PIPING PER NOMINAL PIPE OR TUBE SIZE <br /> 3. ALL DIMENSIONS, CLEARANCES AND TOLERANCES SHALL BE VERIFIED PRIOR AWAY FROM MANHOLES. NOMINAL PIPE SIZE <1 1 TO 1.5 1.5 TO <4 4 TO <8 28 K m <br /> TO INSTALLATION. ALL ROUGH-IN LOCATIONS SHALL BE COORDINATED WITH HOT WATER PIPING (140'F) BSI BEVERAGE SYSTEM INSTALLER v ti <br /> THE MANUFACTURER'S SUBMITTAL INFORMATION. 7. PIPING INLET AND OUTLET SIDES SHALL BE CLEARLY LABELED ON THE TOP DOMESTIC COLD WATER 40'F TO 60'F 0.5 0.5 1.0 1.0 1.0 cn <br /> OF THE GREASE INTERCEPTOR TO INSURE PROPER INSTALLATION. TEMPERATE HOT WATER 105'F TO 140'F 1.0 1.0 1.5 1.5 1.5 O <br /> 4. ALL DIMENSIONAL INFORMATION IS AS FOLLOWS (UNLESS NOTED OTHERWISE): HOT WATER 141'F TO 200'F 1.5 1.5 2.0 2.0 2.0 - - RECIRCULATED HOT WATER PIPING CO CLEAN-OUT cc <br /> A. UNDERGROUND PIPE IS TO FOUNDATION DOMESTIC SUPPLY SYSTEMS: STORM DRAIN HORIZONTAL - - 1.0 1.0 1.0 <br /> B. OVERHEAD PIPE IS TO FINISHED WALL 1. THE INCOMING WATER SERVICE PIPE SHALL BE LOCATED A MINIMUM OF 10 <br /> C. ELEVATIONS ARE TO FINISHED FLOOR FT. FROM THE EXITING SANITARY PIPE. WHERE A 10 FT. SEPARATION IS NOT - - OVERHEAD LINES (BY P.C.) DC DOWNSPOUT COVER <br /> POSSIBLE, THE BOTTOM OF THE WATER SERVICE PIPE SHALL BE A MINIMUM <br /> 5. ALL MATERIALS, FIXTURES AND EQUIPMENT USED SHALL BE IN ACCORDANCE OF 12 IN. ABOVE THE TOP OF THE HIGHEST POINT OF THE SANITARY PIPE. <br /> WITH McDONALD'S SPECIFICATIONS. SPECIFICATIONS ARE CONTAINED WITHIN ---OW--- UNDERGROUND.SANITARY PIPING DFU DRAINAGE FIXTURE UNIT(S) �i N <br /> THESE DRAWINGS AND THE McDONALD'S PROJECT MANUAL. ANY CONTRACTOR 2. ALL UNDERGROUND SITE PLUMBING SHALL CONFORM TO NSF 61, SHALL BE ¢o N <br /> IN NEED OF A COPY OF THE McDONALD'S PROJECT MANUAL SHALL CONTACT TYPE K COPPER TUBING OR COPPER PIPE, POLYETHYLENE (PE), PEX OR <br /> THE McDONALD'S AREA CONSTRUCTION MANAGER. ANY VARIANCE FROM THE CPVC. IF CPVC IS USED, FOAM INSULATION SHALL BE INSTALLED AT ALL - <br /> McDONALD'S SPECIFICATIONS SHALL BE REVIEWED AND APPROVED BY THE <br /> CHANGES OF DIRECTION TO ACCOUNT FOR EXPANSION AND CONTRACTION. UNDERGROUND GREASE WASTE PIPING EC ELECTRICAL CONTRACTOR `} <br /> ENGINEER-OF-RECORD. 3. IF PEX PIPING IS USED, ALL MAINS SHALL BE UPSIZED BY 0.5" DIAMETER. Q <br /> --------- VENT PIPING FAC FIRE ALARM CONTRACTOR <br /> 6. SEE COORDINATION SCHEDULE FOR ADDITIONAL SCOPE OF WORK. 4. INCOMING WATER SERVICE PRESSURE SHOULD BE BETWEEN 50 AND 55 PSI Professional of Record: <br /> 7. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH ITS LISTING STATIC. WHERE WATER PRESSURE SERVICE EXCEEDS 80 PSI STATIC, AN <br /> APPROVED WATER-PRESSURE REDUCING VALVE WITH STRAINER CONFORMING ST ABOVE GROUND PRIMARY STORM PIPING FCO FLOOR CLEAN-OUT <br /> AND/OR THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. TO ASSE 1003 SHALL BE INSTALLED. WHERE INCOMING WATER PRESSURE IS M <br /> 8. WHERE POOR SOIL CONDITIONS EXIST OR WHERE SUBSTANTIAL SETTLEMENT BELOW 50 PSI STATIC, A PRESSURE BOOSTER SYSTEM SHALL BE INSTALLED. - <br /> OF EITHER THE PIPING, THE BUILDING OR ADJACENT WALKS, PLANTERS, ETC., 5. IF THE RESTAURANT HAS A COMBINED WATER AND FIRE SPRINKLER SERVICE, -sr- UNDERGROUND PRIMARY STORM PIPING FD FLOOR DRAIN <br /> MAY OCCUR,THE CONTRACTOR SHALL PROVIDE ADEQUATE UNDERSLAB THE INCOMING WATER SERVICE SHALL BE SIZED BASED ON THE FIRE DESIGN <br /> STAINLESS STEEL PIPE HANGERS OR APPROVED OTHER SUPPORT. SPRINKLER CONTRACTOR'S HYDRAULIC CALCULATIONS. STS ABOVE GROUND SECONDARY STORM PIPING FPC FIRE PROTECTION CONTRACTOR <br /> Architectural <br /> 9. ALL PIPE SLEEVES SHALL BE PROPERLY SEALED AND INSULATED TO PREVENT <br /> HEAT LOSS AND SEEPAGE. 6. PROVIDE A MINIMUM 1/2"ANNULAR CLEARANCE AROUND ALL PIPE SLAB Solutions Group <br /> PENETRATIONS. CD CONDENSATE PIPING FS FLOOR SINK <br /> 19401 <br /> 10. ALL PIPE INSULATION SHALL BE PROTECTED FROM DAMAGE FROM PIPE 0 <br /> HANGERS. PROTECTION SHALL BE LIGHT GAUGE GALVANIZED STEEL OR 7. A REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER (RPZ) SHALL BE SUITE TE A 98036 <br /> EQUAL. INSTALLED AT THE INCOMING SERVICE WHERE REQUIRED BY CODE. (MIN. 60" r' HOSE BIBB GC GENERAL CONTRACTOR LYNNWOOD,W WA <br /> A.F.F.) M4Wl NGLI T,P.E. <br /> 11. ALL PENETRATIONS OF FIRE-RATED WALLS SHALL BE FIRESTOPPED WITH AN S'N^'^N°u cHormPunGI PHONE:(/15IQPNOGI <br /> NC.COM <br /> APPROVED AND LISTED FIRESTOPPING SYSTEM. 8. AN EXPANSION TANK SHALL BE INSTALLED ON THE COLD WATER LINE INLET TJ CHECK VALVE GI GREASE INTERCEPTOR <br /> TO THE WATER HEATER. SEE EXPANSION TANK SCHEDULE. <br /> SANITARY AND VENT SYSTEMS: <br /> 1. THE BUILDING SANITARY PIPE SHALL BE LOCATED A MINIMUM OF 10 FT. FROM 9. ALL WATER SUPPLY PIPE WITHIN 5 FT. OF THE BUILDING AND INSIDE THE BALL VALVE GPF GALLONS PER FLUSH <br /> THE INCOMING WATER SERVICE. WHERE A 10 FT. SEPARATION IS NOT BUILDING SHALL COMPLY WITH NSF 61 AND SHALL BE TYPE L COPPER <br /> POSSIBLE, THE BOTTOM OF THE WATER SERVICE PIPE SHALL BE A MINIMUM TUBING, COPPER PIPE, PEX OR CPVC PIPE.OF 12 IN. ABOVE THE TOP OF THE HIGHEST POINT OF THE SANITARY PIPE. <br /> 10. CPVC PIPE SHALL BE FLOWGUARD GOLD OR FLOWGUARD BENDABLE AS dZ1 THERMOSTATIC MIXING VALVE GPM GALLONS PER MINUTE <br /> 2. ALL SANITARY AND VENT PIPE SHALL BE PVC TYPE DWV, ABS OR CAST-IRON MANUFACTURED BY LUBRIZOL. <br /> WHERE REQUIRED BY CODE. <br /> 11. CPVC PIPE SHALL BE CONNECTED WITH FLOWGUARD GOLD YELLOW LOW-VOC ® FLOOR DRAIN GW GREASE WASTE <br /> 3. ALL HORIZONTAL SANITARY PIPE SHALL BE INSTALLED WITH A MINIMUM PITCH SOLVENT CEMENT AS MANUFACTURED BY IPS WELD-ON OR OATEY. <br /> AS FOLLOWS: <br /> PIPE SIZE MIN. SLOPE 12. ALL CPVC PIPE SHALL BE INSULATED TO PREVENT EXPOSURE TO GREASE. ® CLEAN-OUT (FLOOR OR YARD) HIS HAND SINK OOOp�O0�v1A/yp000 <br /> 2 1 2 OR LESS 1 4 PER FT. 13. ALL SUSPENDED PIPE SHALL BE SUPPORTED AS FOLLOWS: 00 of 'C�O <br /> 3"TO 6" <br /> 8" OR IARGER 1 8" PER FT. MIN MATERIAL MAX. HORIZ. SPACING MAX. VERT. SPACING FLOOR SINK I.P.S. IRON PIPE SIZE (ALSO NPS) F' - <br /> COPPER PIPE 12 FT. 10 FT. <br /> 4. CLEANOUTS SHALL BE INSTALLED IN ALL HORIZONTAL DRAINAGE PIPE AND COPPER TUBING 51 1 4 6 FT. 10 FT. °a <br /> SHALL BE LOCATED NOT MORE THAN 100 FT. APART. (UNLESS OTHERWISE COPPER TUBING >1 1 2 10 FT. 10 FT. O PRESSURE GUAGE KEI KITCHEN EQUIPMENT INSTALLER <br /> oO gg000 <br /> DICTATED BY LOCAL CODES). CPVC 51" 3 FT. 10 FT. Op/�pL00002Q <br /> CPVC>1 1 4 4 FT. 10 FT. (fl LOW PRESSURE SWITCH KES KITCHEN EQUIPMENT SUPPLIER oaoo00 <br /> 5. CLEANOUTS SHALL BE INSTALLED AT ALL CHANGES OF DIRECTION GREATER Q� <br /> THAN 45 DEGREES. WHERE MORE THAN ONE CHANGE OF DIRECTION OCCURS PEX 51" 3 FT. 10 FT. Seal <br /> IN A SINGLE PIPE RUN, ONLY ONE (1) CLEANOUT SHALL BE REQUIRED FOR IPEX 21 1 4 4 FT. 1 10 FT. u <br /> EVERY 40 FEET OF DEVELOPED LENGTH. 14. A REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER (RPZ) SHALL BE ® HIGH PRESSURE SWITCH LAV LAVATORY o m «_ . <br /> INSTALLED AT THE INLET TO THE WATER FILTRATION SYSTEM. ALL PIPING z v <br /> 6. CLEANOUTS SHALL BE INSTALLED ON PIPES PRIOR TO ANY SLAB DOWNSTREAM OF THE RPZ SHALL BE COPPER OR CROSS-LINKED m <br /> u o°` <br /> PENETRATION. POLYETHYLENE (PEX). SOLENOID VALVE MC MECHANICAL CONTRACTOR � U ao "-c <br /> � o° o <br /> 7. WHERE PIPING IS LOCATED WITHIN WALL CAVITIES, ACCESS TO THE CLEANOUTS 15. ALL DEVICES, APPLIANCES, AND APPARATUS INTENDED TO SERVE SOME <br /> SHALL BE PROVIDED. SPECIAL FUNCTION (EX.: SODA MACHINE, COFFEE MACHINE, BEVERAGE rTA THREE-WAY VALVE MHT MALE HOSE THREADS 1. <br /> J m E om <br /> DISPENSERS, ETC.) SHALL BE PROVIDED WITH PROTECTION AGAINST BACKFLOW <br /> 8. CLEANOUTS ON 6-IN. AND SMALLER PIPES SHALL BE PROVIDED WITH A AND CONTAMINATION OF THE WATER SUPPLY SYSTEM. ALL BACKFLOW PP 'QA °C ° <br /> CLEARANCE OF NOT LESS THAN 18 IN. CLEANOUTS ON 8-IN. AND LARGER PREVENTION DEVICES SHALL BE ASSE LISTED AND APPROVED FOR THE DEVICE C� PRESSURE REGULATOR MS MOP SINK ^ v+ "a E <br /> PIPE SHALL BE PROVIDED WITH A CLEARANCE OF NOT LESS THAN 36 IN. OR APPLIANCE THEY SERVE. ® `o 09$;o <br /> �`9. ALL SUSPENDED SANITARY AND VENT PIPE SHALL BE SUPPORTED AS ALL WATER SUPPLY LINES SHALL BE PROVIDED WITH A QUARTER-TURN NCI DUAL CHECK VALVE OR RPZ NIPS NATIONAL PIPE THREAD STANDARD ° <br /> 16. °,`o <br /> FOLLOWS: SHUT-OFF VALVE BEFORE FINAL CONNECTION TO EQUIPMENT. N $w <br /> MAX. HORIZ. MAX. VERT. . ..AA'' <br /> MATERIAL SPACING SPACING 17. QUARTER-TURN SHUT-OFF VALVES SHALL BE INSTALLED UPSTREAM OF ANY IVV DVENT CHECK VALVE WITH ATMOSPHERIC NPT NATIONAL PIPE THREAD TAPERED <br /> ABS 4 FT. 10 FT. INLINE BACKFLOW PREVENTION DEVICE. <br /> PVC PE DNN 4 FT. 10 F7. 18. ALL VALVES AND BACKFLOW PREVENTION DEVICES SHALL BE INSTALLED WITH STRAINER 0/0 OWNER/OPERATOR 0 m e m° <br /> CAST-IRON <10 Fi. PIPE SECTIONS) 5 FT. 15 FT. FITTINGS THAT FACILITATE REMOVAL IN CASE OF FAILURE. m <br /> CAST-IRON (10 FT. PIPE SECTIONS) 10 FT. 15 FT. <br /> 19. ALL OVERHEAD WATER LINES SHALL BE INSULATED PER SCHEDULE THIS 0 ,:5 <br /> e„ o <br /> 10. ALL PLUMBING FIXTURES SHALL BE VENTED AND THE MAXIMUM DISTANCE RELIEF VENT OH OVERHEAD <br /> SHEET WITH EXTERNAL JACKETED INSULATION AND A MINIMUM INSTALLED a A <br /> FROM THE FIXTURE TRAP TO THE VENT SHALL BE AS FOLLOWS: R-VALUE OF 3.7. <br /> w G z`° <br /> TRAP SIZE SLOPE DISTANCE 40 ►" 2'-� <br /> 1 1 4 1 4 PER FT. 2'_g^ 20. PRIOR TO BUILDING TURNOVER, THE DOMESTIC WATER SUPPLY SYSTEM SHALL WATER-HAMMER ARRESTER P PUMP ® � ; 09 m <br /> e 1 1 2 1 4 PER FT. g'_g^ BE PURGED OF DELETERIOUS MATERIAL AND DISINFECTED. DISINFECTION t m m $ <br /> 1 4-PER 5'_p^ SHALL BE DONE IN ACCORDANCE WITH THE LOCAL HEALTH CODE, PLUMBING 9 ��o�v o <br /> 2" CODE OR IN ACCORDANCE WITH AWWA C651 OR AWWA C652. PC PLUMBING CONTRACTOR °`v'a�c5 mS <br /> 3" 1 8 . <br /> 3 4" & LARGER 1 8 PER FT. 10'-0" STORM DRAINAGE SYSTEMS: <br /> 11. ALL PLUMBING VENTS THROUGH THE ROOF SHALL TERMINATE A MINIMUM OF 1. ALL ROOF DRAINS SHALL BE SIZED IN ACCORDANCE WITH LOCAL CODES AND RC REFRIGERATION CONTRACTOR a a <br /> SHALL CONFORM TO ASME A112.21.2M OR A112.3.1. <br /> 12 INCHES ABOVE THE ROOF AND SHALL BE LOCATED A MINIMUM OF 8 FT. <br /> FROM ANY PARAPET WALL. WHERE A VENT TERMINATES WITHIN 8 FT. OF A 2. ALL STORM DRAINAGE PIPING SHALL BE ABS, PVC TYPE DWV OR CAST-IRON REDUCED PRESSURE PRINCIPLE w o o <br /> PARAPET WALL, THE VENT SHALL TERMINATE A MINIMUM OF 6 INCHES ABOVE WHERE REQUIRED BY CODE. RPZ BACKFLOW PREVENTERTHE o P o o <br /> 12. ALL PLUMBING VENTS SHALL TERMINATE A MINIMUM OF 10 FT. HORIZONTALLY 3. ALL SUSPENDED STORM DRAINAGE PIPE SUPPORT REQUIREMENTS SHALL BE to <br /> THE SAME AS THE SANITARY AND VENT REQUIREMENTS. SS SANITARY SEWER <br /> FROM ANY OUTDOOR AIR INTAKE. WHERE A PLUMBING VENT IS LOCATED <br /> o WITHIN 10 FT. OF AN INTAKE, THE VENT SHALL TERMINATE A MINIMUM OF 2 4. ALL HORIZONTAL STORM DRAINAGE PIPE PITCH REQUIREMENTS SHALL BE THE ST STORM SEWER (PRIMARY) <br /> FT. ABOVE THE INTAKE. SAME AS THE SANITARY AND VENT REQUIREMENTS. STS STORM SEWER (SECONDARY) <br /> U <br /> 13. ALL SIDE WALL VENT TERMINATIONS SHALL BE PROTECTED TO PREVENT BIRDS <br /> OR RODENTS FROM ENTERING OR BLOCKING THE VENT OPENING. 5. ALL HORIZONTAL STORM DRAINAGE PIPE SHALL BE INSULATED WITH 1"THICK ANTI-SIPHON, SPILL RESISTANT <br /> EXTERNAL JACKETED INSULATION AND A MINIMUM INSTALLED R-VALUE OF 3.7 SVB VACUUM BREAKER <br /> 14. ALL FLOOR DRAINS THAT DO NOT SERVE EQUIPMENT SHALL BE PROTECTED <br /> TO PROTECT AGAINST CONDENSATION. <br /> 3 AGAINST DRYING OUT EITHER THROUGH THE INSTALLATION OF A TRAP PRIMER, 6. CLEANOUTS SHALL BE INSTALLED IN ALL HORIZONTAL DRAINAGE PIPE AND TAB TEST AND BALANACE CONTRACTOR 3 <br /> DEEP SEAL TRAP OR PROSET TRAP GUARD. ALL TRAPS SHALL BE FILLED WITH SHALL BE LOCATED NOT MORE THAN 100 FT. APART. <br /> w AN INITIAL LAYER OF COOKING OIL. <br /> 7. CLEANOUTS SHALL BE INSTALLED AT ALL CHANGES OF DIRECTION GREATER UG UNDERGROUND r7 <br /> a 15. ALL APPLIANCES SHALL DRAIN TO AN APPROVED SANITARY WASTE RECEPTOR THAN 45 DEGREES. WHERE MORE THAN ONE CHANGE OF DIRECTION OCCURS N a <br /> (FLOOR SINK OR FLOOR DRAIN WITH FUNNEL). INDIRECT DRAINAGE FROM AN IN A SINGLE PIPE RUN, ONLY ONE (1) CLEANOUT SHALL BE REQUIRED FOR - <br /> APPLIANCE SHALL MAINTAIN AN AIR GAP BETWEEN THE PIPE OUTLET AND THE EVERY 40 FEET OF DEVELOPED LENGTH. z <br /> TOP OF THE RECEPTOR. THE MINIMUM DISTANCE BETWEEN THE PIPE OUTLET UR URINAL Z Q <br /> AND THE TOP OF THE RECEPTOR SHALL BE TWICE THE DIAMETER OF THE 8. CLEANOUTS SHALL BE INSTALLED ON PIPES PRIOR TO ANY SLAB <br /> APPLIANCE DRAIN PIPE. V VENT Z <br /> PENETRATION. <br /> uGREASE INTERCEPTORS: 9. WHERE PIPING IS LOCATED WITHIN WALL CAVITIES, ACCESS TO THE CLEANOUTS - -- $ <br /> 1. SEE SITE PLAN FOR THE SIZE AND LOCATION OF THE GREASE INTERCEPTOR. SHALL BE PROVIDED. J W �' m <br /> WC WATER CLOSET Q C_ o n <br /> E 2. THE GREASE INTERCEPTOR SHALL BE INSTALLED IN A LOCATION THAT IS 10. ROOF DRAINS AND OVERFLOW ROOF DRAINS SHALL BE PIPED INDEPENDENTLY. O Cr� <br /> o ACCESSIBLE FOR PUMPING. OVERFLOW ROOF DRAINS SHALL NOT BE CONNECTED TO THE PRIMARY ROOF 0 LJ yo o ? O <br /> 3. THE GREASE INTERCEPTOR SHALL BE CONSTRUCTED OF FIBERGLASS OR DRAINAGE SYSTEM. m s m o ro <br /> o WCO WALL CLEAN-OUT <br /> o ROTATIONALLY-MOLDED POLYETHYLENE. GREASE INTERCEPTOR CONSTRUCTION <br /> a SHALL CONFORM TO ALL LOCAL CODES. CONCRETE GREASE INTERCEPTORS <br /> ARE NOT PERMITTED UNLESS REQUIRED BY THE LOCAL AHJ. WSFU WATER SUPPLY FIXTURE UNIT(S) a ® 0 <br /> z N <br /> 4. GREASE INTERCEPTORS SHALL BE GRAVITY OR HYDROMECHANICAL TYPE, SIZED <br /> FOR THE APPLICATION LISTED. <br /> YC YARD CLEAN-OUT GENERAL NOTES U <br />