m � <br /> GENERAL ELECTRICAL NOTES (NOT ALL MAY APPLY): <br /> GROUNDING: <br /> G1. ALL BRANCH AND FEEDER CIRCUITS SHALL BE GROUNDED BY TWO METHODS.THE FIRST METHOD SHALL PROJECT DEMOLITION NOTES: o <br /> INCLUDE AN INSULATED COPPER EQUIPMENT GROUNDING CONDUCTOR CONTAINED WITHIN THE SAME a j <br /> CONDUIT AS THE PHASE CIRCUIT CONDUCTORS AND SIZED PER NEC SECTION 250 REQUIREMENTS.THIS IR y <br /> INSULATED EQUIPMENT GROUNDING CONDUCTOR SHALL HAVE ONE END PROPERLY TERMINATED AT THE THE FOLLOWING PROVIDES A GENERAL SCOPE OF WORK FOR THE ELECTRICAL CONTRACTOR FOR THE <br /> EQUIPMENT GROUND BUS IN THE CORRESPONDING CIRCUIT BREAKER PANEL,AND THE OTHER END DEMOLITION REQUIREMENTS OF THIS SITE. THIS SECTION IS NOT ALL INCLUSIVE, AND THE CONTRACTOR w C <br /> TERMINATED AT THE GROUNDING CONTACT OF A GROUNDING RECEPTACLE AND TO THE JUNCTION BOX OR <br /> TO AN EQUIPMENT CABINET,AS APPLICABLE.THE SECOND METHOD PROVIDES EQUIPMENT GROUNDING VIA SHALL VISIT THE SITE AND COMPARE EXISTING CONDITIONS TO THE REQUIREMENTS DENOTED ON THE W <br /> METALLIC CONDUIT THAT IS CONNECTED AND TERMINATED IN FITTINGS LISTED FOR GROUNDING PER NEC CONSTRUCTION DOCUMENTS TO DETERMINE THE EXACT EXTENT OF THE DEMOLITION WORK REQUIRED. a <br /> SECTION 250 REQUIREMENTS. BOTH GROUNDING METHODS ARE REQUIRED h A McOOHALO'S RESTAURANT. E.C. SHALL PROVIDE ALL DEMOLITION WORK REQUIRED IN ORDER TO ALLOW FOR THE COMPLETE <br /> ISOLATED GROUND SHALL BE INSTALLED WHERE INDICATED ON PLAN AND AS SHOWN IN POS ISOLATED INSTALLATION AS DENOTED WITHIN THESE DRAWINGS. <br /> GROUND/DEDICATED CIRCUIT DETAIL. <br /> G2. THE BUILDING GROUNDING SYSTEM SHALL COMPLY WITH NEC ARTICLE 250, MCDONALD'S SPECIFICATIONS. GENERAL W N <br /> CAUTION: IT IS A SAFETY HAZARD AND AN NEC VIOLATION TO HAVE ANY NEUTRAL TO GROUND D1. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE SALVAGE REQUIREMENTS FOR ALL I' <br /> CONNECTIONS BEYOND THE MAIN ELECTRICAL DISCONNECT MEANS. MCDONALD'S GROUNDING STANDARDS <br /> PURPOSELY EXCEED THOSE GIVEN BY THE NEC.THE EC SHALL PROVIDE A BUILDING GROUNDING SYSTEM EQUIPMENT REMOVED AS PART OF THE DEMOLITION WORK WITH THE CONSTRUCTION PROJECT MANAGER. j <br /> MEETING NEC SECTION 250 REQUIREMENTS AS WELL AS MCDONALD'S STANDARDS, ALL EQUIPMENT TO BE SALVAGED AND/OR REUSED SHALL BE PROTECTED FROM DAMAGE UNTIL o <br /> G3. EC SHALL REFER TO "Pos ISOLATED GROUND/DEDICATED CIRCUIT DETAIL, FOR REQUIRED WIRING REINSTALLED OR THE TIME PERIOD WHEN IT IS TURNED OVER TO THE OWNER AND/OR THE PROJECT <br /> REQUIREMENTS OF COMPUTER PANEL. MANAGER. <br /> 04. METAL RACEWAYS CONTAINING A GROUNDING ELECTRODE CONDUCTOR SHALL BE BONDED AT BOTH ENDS AS D2. SEE THE GENERAL ELECTRICAL SPECIFICATIONS AND NOTES ON SHEET E1.0 FOR ADDITIONAL Professional of Record <br /> REQUIRED BY NEC SECTION 250 REQUIREMENTS. GENERAL REQUIREMENTS. <br /> CONDUIT AND WIRE: LIGHTING <br /> W1. THE FOLLOWING WIRING METHODS SHALL NOT BE USED: NON-METALUC SHEATHED CABLE(ROMEX, NM, 1. ALL LIGHT FIXTURES SHALL BE 120 VOLT UNLESS NOTED OTHERWISE. mw <br /> NMC, &NMS),ARMORED CABLE TYPE AC (BX), ELECTRICAL NON-METALLIC TUBING,TYPE ENT <br /> (SMURF-TUBE). 2. LIGHTING FIXTURES AND LAMPS HAVE BEEN CHOSEN TO ACHIEVE MAXIMUM ENERGY CONSERVATION DESIGN <br /> W2. CONDUIT RUNS MAY BE COMBINED EXCEPT WHERE ISOLATED GROUNDS ARE USED. IG CIRCUITS SHALL BE WHILE MAINTAINING ADEQUATE LEVEL OF ILLUMINATION. LAMP SPECIFICATIONS SHALL BE STRICTLY Architectural <br /> RUN IN SEPARATE CONDUITS.ALL HOME RUNS SHALL BE SIZED BASED ON DERATED CONDUCTOR FOLLOWED. ANY DEVIATION FROM LAMP SPECIFICATIONS SHALL BE APPROVED IN WRITING BY Solutions Group <br /> AMPACITIES AND INCREASE CONDUIT AND WIRE SIZE AS REQUIRED BY NEC SECTION 310 REQUIREMENTS. McDONALD'S CORPORATION. <br /> W3. CONDUIT SHALL HAVE A MAXIMUM OF 4 BENDS WITHOUT A JUNCTION BOX TO PREVENT DAMAGE TO CABLE 3. PROVIDE A WEATHERPROOF JUNCTION BOX IN PARAPET FOR FASCIA SIGNS. FINAL CONNECTION BY 19401 <br /> SUITE <br /> SUE 0 <br /> DURING PULLING.THE EC SHALL PIGTAIL#12 PULL WIRE AT EACH END FOR INSTALLER TO PULL CABLE. <br /> ALL LOW VOLTAGE CONDUIT STUB-UPS SHALL BE PROVIDED WITH A BUSHING. OTHERS. DETERMINEEXACT LOCATION OF SIGN WITH McDONALD'S PROJECT MANAGER PRIOR TO LYNNWOOD,W WA A 980315 <br /> INSTALLATION. JAMES YBABPA,P.E. <br /> W4. MINIMUM WIRE SIZE SHALL BE#12 AWG COPPER UNLESS NOTED OTHERWISE. MINIMUM CONDUIT SIZE PHONE:(425)409 E4% <br /> SHALL BE 1/2"UNLESS NOTED OTHERWISE.WIRES INSTALLED UNDERGROUND OR OUTDOORS SHALL BE 4. EC SHALL COORDINATE LOCATION OF ALL EXTERIOR LIGHTS WITH McDONALD'S PROJECT MANAGER TO EAWL:JYBAN PMKINC.00. <br /> THY- AVOID INTERFERENCE WITH ANY CORBELS, TRUSSES, BEAMS OR OTHER SPECIAL EXTERIOR <br /> W5. CONDUCTORS#10 AWG AND SMALLER SHALL BE SOLID COPPER. CONDUCTORS#8 AND LARGER SHALL BE TREATMENTS. INSTALL LIGHT FIXTURES WITH CORRECT ORIENTATION PER MANUFACTURER'S <br /> STRANDED COPPER. ALUMINUM CONDUCTORS SHALL NOT BE UTILIZED FOR FEEDER OR BRANCH CIRCUIT INSTRUCTIONS. <br /> DISTRIBUTION. <br /> 5. EC SHALL FIELD DETERMINETHAT ALL LIGHT FIXTURES SHOWN ON THIS PLAN DO NOT OBSTRUCT OR <br /> W6. RACEWAYS SHALL BE ANY OF THE FOLLOWING MATERIALS, INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CONFLICT WITH THE WORK OF OTHER TRADES. IF A DISCREPANCY IS FOUND, THE EC SHALL <br /> CODES: IMMEDIATELY NOTIFY THE GC BEFORE THE INSTALLATION OF SUCH FIXTURE(S). <br /> OUTDOORS: (FOR SPECIFIC APPLICATIONS AND APPROPRIATE FITTINGS, SEE TABLE W6) 6. ORDER LED EXIT SIGNS WITH LETTER COLORS THAT COMPLY WITH LOCAL CODES FROM SECURITY <br /> 1. EXPOSED: RMC, IMC. LIGHTING. <br /> 2. CONCEALED: RMC, IMC. <br /> 3. BELOW GRADE, SINGLE RUN: RNC, RMC. - FOR RED LETTERS USE #PRB (UNIVERSAL), QODOD <br /> 4. BELOW GRADE, GROUPED: RNC, RMC. - FOR GREEN LETTERS USE #PGB (UNIVERSAL), OR o0o A yoo22,, <br /> 5. CONNECTION To VIBRATING EQUIPMENT(INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, IF THE ABOVE EXIT SIGNS DO NOT COMPLY WITH LOCAL CODES USE: LED SIGN WITH BATTERY ��5,_.......6,Q�oo <br /> ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): LFMc, BACKUP, LETTER SIZE, COLOR, TYPE & DIRECTIONAL ARROWS AS REQUIRED BY THE LOCAL "`/`pF WASy;..'P o <br /> 6. BOXES AND ENCLOSURES: NEMA 250,TYPE 3R OR 4. AUTHORITIES. nO jtie RI ���`�S <br /> INDOORS: (FOR SPECIFIC APPLICATIONS AND APPROPRIATE FITTINGS, SEE TABLE W6) INSTALLATION METHODS Op <br /> 1. EXPOSED: EMT, IMC. o� IST ' <br /> 2.CONCEALED: EMT, IMC. 7. EC SHALL INSTALL ALL SOFFIT LIGHTING FIXTURES AWAY FROM BUILDING WALL. FIXTURES SHALL BE <br /> 3.CONNECTION TO VIBRATING EQUIPMENT(INCLUDING TRANSFORMERS AND HYDRAULIC, PNEUMATIC, LOCATED TO AVOID INTERFERENCE WITH STRUCTURAL MEMBERS ABOVE SOFFIT. NAL <br /> ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): FMC; EXCEPT USE LFMC IN DAMP OR WET OODD000�\,�� <br /> LOCATIONS. Seal <br /> 4. DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT. 8. THE USE OF "MC" CABLE IN LENGTHS OF 6 FEET OR LESS (WHERE PERMITTED BY LOCAL CODES) <br /> 5. BOXES AND ENCLOSURES: NEMA 250,TYPE 1, EXCEPT AS FOLLOWS:A. DAMP,WET OR KITCHEN SHALL BE ALLOWED FOR WIRING TO THE LIGHTING FIXTURES. "ROMEX" OR "BX" SHALL NOT BE ° <br /> LOCATIONS: NEMA 250,TYPE 4,STAINLESS STEEL. USED. ' 09 <br /> o <br /> 9. EC SHALL DETERMINETHAT NOT MORE THAN 3% VOLTAGE DROP EXISTS FROM THE LIGHTING PANEL V °2 oo c <br /> TO ANY EXTERIOR LIGHTING FIXTURE OR SIGNAGE BALLAST. J ;Pa°-Ea <br /> SPECIALITY LIGHTING J m m E orc <br /> 10. SEE THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND REQUIREMENTS FOR THE FACADE i = =gym Is ue <br /> ARCADE LIGHTING ELEMENTS, AND AWNING ELEMENTS. y m.g;A-o 8 2 <br /> 9g° <br /> © ° 03 <br /> WE�c <br /> c g j; <br /> Q Q <br /> TABLE W6: <br /> SYMBOLS AND ABBREVIATIONS (NOT ALL MAY BE USED) :sus <br /> LOCATION 2O8V. 48OV. LOW ENERGY- <br /> 4 EXPOSED SYMBOL DESCRIPTION SYMBOL DESCRIPTION <br /> INDOORS < 1"EMT COMPRESS. FIGS IMC THREADED FTGS EMT COMPR. FIGS bo SINGLE POLE SWITCH,3W=THREE WAY SWITCH,K=KEYED SWITCHED, B BUZZER <br /> w >1.25"IMC THREADED FIGS VS=VACANCY SENSOR <br /> w sj MANUAL SWITCH (T=THERMAL OVERLOADS) QB BUTTON FOR BUZZER <br /> 65 OUTDOORS RMC OR IMC THREADED FIGS RMC OR IMC THREADED FIGS RMC OR IMC THREADED FIGS <br /> CONCEALED <br /> j <br /> In TRANSFORMER o® PULLBOX <br /> WALLS <2"EMT SET SCREW FIGS <2"EMT SET SCREW. FIGS JB WITH DUPLEX CONVENIENCE OUTLET (FLUSH WITH CEILING) � PANELBOARD <br /> EMT <br /> o >2.5"IMC THREADED FTGS >2.5"IMC THREADED FTGS 1/2' 2"SET SCREW FIGS JB WITH SINGLE CONVENIENCE OUTLET I� CIRCUIT BREAKER <br /> 2.5"- 4"COMPR. FIGS <br /> o AIR HANDUNG <2"EMT COMPR. FIGS 2"EMT COMPS. FIGS < >2.5" EMT COMPR. FTGS JB WITH DUPLEX CONVENIENCE OUTLET A AMPERES <br /> rc CEIUNG/SPACE >2.5*IMC THREADED. FIGS IMC THREADED. FIGS JB WITH TWO DUPLEX CONVENIENCE OUTLETS ACM AREA CONSTRUCTION MANAGER <br /> o NON AIR <2"EMT SET SCREW FIGS <2"EMT COMPS. FIGS>2.5" EMT ® JB WITH SPECIAL PURPOSE OUTLET AFF ABOVE FINISHED FLOOR "dH <br /> M HANDLING >2.5"IMC THREADED. FIGS IMC THREADED. FIGS 1/2"- 2"SET SCREW FTGS ® JB WITH ISOLATED GROUND OUTLET _ C CONDUIT O1 <br /> CEILING SPACE 2.5"- 4"COMPR. FIGS © IG4700A, =IG5262 G <br /> 3 BELOW GRADE '© = IG4710, ❑O' =IG5261, CCT CIRCUIT r7 a <br /> z N INTERCOM STATION W/ 3/4"C- TO MAIN STATION DIF DETERMINE IN FIELD c0 <br /> INTERIOR IMC THREADED FIGS OR IMC THREADED FTGS IMC THREADED FTGS SCHEDULE <br /> ° SCHEDULE 40 OR 80 PVC 40 OR 80 PVC b TELEPHONE JACK EC ELECTRICAL CONTRACTOR M <br /> EXTERIOR SCHEDULE 40 OR 80 PVC SCHEDULE 40 OR 80 PVC OR SCHEDULE 40 OR 80 PVC OR QJ JUNCTION BOX - WALL OR CEILING MOUNTED GC GENERAL CONTRACTOR <br /> b OR RMC THREADED FTGS RMC THREADED FTGS RMC THREADED FIGS ❑J DISCONNECT SWITCH GFI/GFCI GROUND FAULT CIRCUIT INTERRUPTER < <br /> OS STUB UP THRU ROOF GND GROUND N 3. <br /> FLAT PANEL TELEVISIONS: Z <br /> 0T THERMOSTAT SENSOR W/ 1/2"C- UP TO CEILING SPACE IG ISOLATED GROUND W <br /> N TV1. EC SHALL PROVIDE A DUPLEX RECEPTACLE AND A LOW VOLTAGE BROADBAND CONNECTION FOR THE - (n W <br /> INSTALLATION OF FLAT PANEL TELEVISIONS. COORDINATE EXACT LOCATIONS WITH DECOR COMPANY. FOR M MOTOR CONNECTION JB JUNCTION BOX 0 W <br /> d BROADBAND CONNECTION, EC SHALL PROVIDE A 4 X 4 BOX WITH A 3/4"CONDUIT STUB-UP WITH A CONDUIT RUN CONCEALED IN CEILING OR WALLS KES KITCHEN EQUIPMENT SUPPLIER < a BUSHING INTO ACCESSIBLE CEIDNG SPACE. _ Z U' <br /> N SECURITY AND DRIVE-THRU CAMERAS: / CONDUIT RUN IN FLOOR SLAB MILO MAIN LUGS ONLY O 0 a 30 0 <br /> HOT (SHORT), NEUTRAL (LONG), EQUIP GRD (LONG WITH DOT), & Wrp WEATHERPROOF O L>d m I <br /> S1. EC TO PROVIDE ELECTRICAL POWER AND COMMUNICATION CONDUITS FOR BUILDING MOUNTED SECURITY AND IIIX dE X' DENOTES ISOLATED GRD W M <br /> a DRIVE THRU CAMERAS.COORDINATE FINAL LOCATIONS WITH SECURITY AND DRIVE THRU CAMERA INSTALLERS. <br /> U <br /> J-BOX WITH FINAL EQUIPMENT CONNECTION coCARBON <br /> 06 CEILING MOUNTED OCCUPANCY SENSOR <br /> NOTES AND DETAILS <br />