GENERAL NOTES: <br /> O O <br /> 1. WHEN STRANDED WIRE IS USED,ALL TERMINATIONS ARE MADE BY <br /> LOCATED BELOW FLOOR NEAR A PRESSURE TERMINAL BY TAILING OFF WITH SOLID CONDUCTORS <br /> INCOMING WATER LINE OR OTHER APPROVED MEANS OF TERMINATION. <br /> O2. ALL CONDUCTORS ARE COPPER;TYPE THHN/THWN <br /> D 44 <br /> GF11CI 3. RATING OF STANDARD PANEL IS 22,000 A.I.C. <br /> I <br /> 4. WIRING METHOD IN METALLIC CONDUIT OR M.C.CABLE. <br /> I S. BREAKER LOCK OUT DEVICE SHALL BE INSTALLED ON ALL <br /> 44,'W PERMANENTLY CONNECTED APPLIANCES.2020 NEC 422.31 <br /> GFCI <br /> 6. HVAC DISCONNECTS SHALL BE LABELED WITH AN IDENTIFICATION <br /> WP PLATE SHOWING CIRCUIT SOURCE PANELBOARD,CIRCUIT <br /> T GFCI NUMBER AND EQUIPMENT SERVED,WAC 296-46B-110 022 <br /> i <br /> O7. EXTERIOR WEATHER PROOF GFCI SHALL HAVE A"HEAVY DUTY" <br /> B WEATHER PROOF"IN USE'COVER.2020 NEC 406.9(B)(1) <br /> B. CONTROLLED RECEPTACLES SHALL BE LABELED PER 2020 NEC <br /> 406.3(E)WITH THE TEXT"CONTROLLED"AND THIS SYMBOL b <br /> 9. THIS PLAN IS NOT AN"AS-BUILT'CIRCUITS MAY BE RUN DIFFERENT <br /> ELECTRICAL PLAN THAN SHOWN BASED ON OBSTACLES ENCOUNTERED. <br /> SCALE: 114"=T-0" ars 17 <br /> CUSTOMER APPROVAL <br /> ❑APPROVED <br /> ❑APPROVED EXCEPT AS NOTED <br /> ❑ REVISE AS NOTED AND RESUBMIT <br /> APPROVED By Date <br /> PRELIMINARY <br /> NOT FOR CONSTRUCTION <br /> ELECTRICAL SYMBOLS <br /> SYMBOL DESCRIPTION AFF <br /> TO TOP REMARKS <br /> 8 ELECTRICAL PANEL 36" <br /> WEATHER PROOF <br /> DUPLEX RECEPTACLE CONTROLLED 20" 180 VA EACH <br /> wv WEATHER RESISTANT GFCI <br /> �fiG RECEPTACLE 20" 180 VA EACH <br /> rq DEDICATED DUPLEX UNDER 500 VA EACH <br /> RECEPTACLE—HEAT TRACE FLOOR PROVIDE GFEPD CIRCUIT BREAKER <br /> 6% nUGHT DIMMING CONTROL 48" 1 ZONE DIMMING CONTROL <br /> ,,;T WALL MOUNT TIMER 48" EXTERIOR LIGHTING CONTROL <br /> 7 DAY PROGRAMMABLE <br /> ® nUGHT PLUG LOAD CONTROL ABOVE CONTROLLED BY nUGHT ENABLED <br /> QTY. SIZE DESCRIPTION RELAY CEILING FIXTURE OCCUPANCY SENSORS <br /> ELECTRICAL PANEL 1 100 AMP SINGLE PHASE — NEMA 3R — 120/240 VOLT , PHONE/DATA ROUGH IN 4" 20" 3/4" FLEX STUBBED UP AND DOWN <br /> SO BOX w/SINGLE GANG MR <br /> HVAC 1 1.5 TON BARD 4 kW WALL HUNG HEAT PUMP 11 EER w/ECONOMIZER DS DOOR SWITCH — HVAC AS % FLEX CONDUIT FROM DOOR FRAME <br /> REQUIRED 18/2 TO HVAC UNIT <br /> HVAC CONTROLS 1 THERMOSTAT — BARD 1,8403-060 WALL HUNG HVAC UNIT AS SEE MECH SCHEDULE AND CALCS <br /> REQUIRED <br /> LIGHTING 3 2 x 4 LED TROFFER— nUGHT ENABLED— 6000 LUMEN— 48 WATTS— 4000K O HVAC THERMOSTAT 4B" 4" SQUARE BOX w/SINGLE GANG MR <br /> LITHONIA — 2BLT4 60L ADPT EZ1 LP840 N100 NES7ADCX PWS1836 18AWG STAT WIRE <br /> 14 WATT LED WITH VANDAL RESISTANT COVER AND INTEGRAL PHOTO CELL. w/INTEGRAL SENSORS nUGHT ENABLED LED TROFFER CEILING 48 VA EACH <br /> 1 CONTROLLED BY 7 DAY PROGRAMMABLE WALL TIMER FIELD SET FOR 6000 LUMEN EACH <br /> BUSINESS HOURS. LITHONIA — OVWPLED4OK12OPEDDBHP17M4 �0 LED WALL PACK 84" 14 VA EACH <br /> COPYRIGHT 2021,BLAZER INDUSTRIES.INC. MOBILE 20 881 <br /> Approved for Const Job No: <br /> THIS MATERIAL IS THE EXCLUSIVE PROPERTY BREAK ROOM for: <br /> OF BLAZER INDUSTRIES,INC.AND SHALL ■■ 10 x 30 File Copy: <br /> TO BE OTHERS EXCEPT A USED.ORS <br /> AUTHORIZED <br /> DISCLOSED _ Port of Everett - Norton Expansion <br /> TO OTHERS IXCEPT AS AUTHORIZED BY THE INDUSTRIES,INC. Drawn By: LDG E <br /> � <br /> DATE REVISION BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. P.O.BOX489 wxw.o4uerind.mm WA Pacific Mobile Everett,WA�� 945Dlney St. ■ AumsviIJe.OR=2S5'-4B9 Issue Date: 11-29-21 <br />