GENERAL NOTES: <br /> O O <br /> LOCATED BELOW FLOOR NEAR 1, WHEN STRANDED WIRE IS USED,ALL TERMINATIONS ARE MADE BY <br /> INCOMING WATER LINE A PRESSURE TERMINAL,BY TAILING OFF WITH SOLID CONDUCTORS <br /> O OR OTHER APPROVED MEANS OF TERMINATION. <br /> A <br /> 2. ALL CONDUCTORS ARE COPPER;TYPE THHN/THWN <br /> T D 44} <br /> GF�t1 3. RATING OF STANDARD PANEL IS 22.000 A.I.C. <br /> i <br /> i <br /> 4. WIRING METHOD IN METALLIC CONDUIT OR M.C.CABLE. <br /> Z-1 5. BREAKER LOCK OUT DEVICE SHALL BE INSTALLED ON ALL <br /> PERMANENTLY CONNECTED APPLIANCES.2020 NEC 422.31 <br /> GTI <br /> I 6. HVAC DISCONNECTS SHALL BE LABELED WITH AN IDENTIFICATION <br /> I <br /> WP PLATE SHOWING CIRCUIT SOURCE PANELBOARD,CIRCUIT <br /> T GFCI NUMBER AND EQUIPMENT SERVED.WAC 296-46B-110 022 <br /> i <br /> O 7. EXTERIOR WEATHER PROOF GFCI SHALL HAVE A"H EAVY DUTY" <br /> WEATHER PROOF'1N USE'COVER.2020 NEC 406.9(B)(1) <br /> 8. CONTROLLED RECEPTACLES SHALL BE LABELED PER 2020 NEC <br /> 406.3(E)WITH THE TEXT"CONTROLLED"AND THIS SYMBOL b <br /> 9. THIS PLAN IS NOT AN"AS-BUILT'CIRCUITS MAY BE RUN DIFFERENT <br /> THAN SHOWN BASED ON OBSTACLES ENCOUNTERED. <br /> ELECTRICAL PLAN <br /> SCALE: 1/4"=V-0" ars 1 I <br /> CUSTOMER APPROVAL <br /> ❑APPROVED <br /> ❑APPROVED EXCEPT AS NOTED <br /> ❑ REVISE AS NOTED AND RESUBMIT <br /> APPROVED By Date <br /> PRELIMINARY <br /> NOT FOR CONSTRUCTIOf\. <br /> ELECTRICAL SYMBOLS <br /> SYMBOL DESCRIPTION AFF TO TOP REMARKS <br /> ELECTRICAL PANEL <br /> 1B WEATHER PROOF 36" <br /> DUPLEX RECEPTACLE 20" 180 VA EACH <br /> CONTROLLED <br /> ��a WEATHER RESISTANT GFCI 20" 180 VA EACH <br /> RECEPTACLE <br /> r—� DEDICATED DUPLEX UNDER 500 VA EACH <br /> RECEPTACLE—HEAT TRACE FLOOR PROVIDE GFEPD CIRCUIT BREAKER <br /> Ef}p nUGHT DIMMING CONTROL 48" 1 ZONE DIMMING CONTROL <br /> T WALL MOUNT TIMER 48" EXTERIOR UGH71NG CONTROL <br /> 7 DAY PROGRAMMABLE <br /> nUGHT PLUG LOAD CONTROL ABOVE CONTROLLED BY nUGHT ENABLED <br /> OTY. SIZE DESCRIPTION 1 11 RELAY CEILING FIXTURE OCCUPANCY SENSORS <br /> ELECTRICAL PANEL 1 100 AMP SINGLE PHASE — NEMA 3R — 120/240 VOLT 4 D SO BOXw/A ROUGH <br /> GANG IN "MR 20" 3/4" FLEX STUBBED UP AND DOWN <br /> HVAC 1 1.5 TON BARD 4 kW WALL HUNG HEAT PUMP 11 EER w/ECONOMIZER DS DOOR SWITCH — HVAC AS 4i FLEX CONDUIT FROM DOOR FRAME <br /> REQUIRED 18/2 TO HVAC UNIT <br /> HVAC CONTROLS 1 THERMOSTAT — BARD #8403-060 WALL HUNG HVAC UNIT AS <br /> REQUIRED SEE MECH SCHEDULE AND CALCS <br /> LIGHTING 3 2 x 4 LED TROFFER— nLIGHT ENABLED— 6000 LUMEN— 48 WATTS— 4000K QT HVAC THERMOSTAT 48" 4" SQUARE BOX w/SINGLE GANG MR <br /> LITHONIA — 2BLT4 60L ADPT EZ1 LP840 N100 NES7ADCX PWS1836 18AWG STAT WIRE <br /> nUGHT ENABLED LED TROFFER CEILING 48 VA EACH <br /> 14 WATT LED WITH VANDAL RESISTANT COVER AND INTEGRAL PHOTO CELL. W/INTEGRAL SENSORS 6000 LUMEN EACH <br /> 1 CONTROLLED BY 7 DAY PROGRAMMABLE WALL TIMER FIELD SET FOR <br /> BUSINESS HOURS. UTHONIA — OVWPLED4OK12OPEDDBHP17M4 LED WALL PACK 84" 14 VA EACH <br /> COPYRIGHT 2021,BLAZER INDUSTRIES,INC. MOBILE BREAK ROOM for <br /> Approved for Const .lot No: 20081 <br /> THIS MATERIAL IS THE S.INC. NE SHOPERTY ALL <br /> OF BLAZER INDUSTRIES.INC.AND SHALL ■■ y <br /> File Copy: <br /> NOT BE REPRODUCED,USED,OR DISCLOSED 10 x 30 port of Everett - Norton ExpansionEmi <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE �0 DUSTRIES,INC. Drawn By: LDG <br /> DATE REVISION BY WRITTEN PERMISSION OF BLAZER INDUSTRIES. P.o.aoxaasvwklazedna.mm W,4 Pacific Mobile Everett,WA <br /> �� 945 Olney SL ■ Aumsville,OR 97325-0489 Issue Date: 11-29-21 <br />