Laserfiche WebLink
A 12 B <br /> 12 X PACKAGE•SPVU- HIGH EFFICIENCY WALL MOUNT HEAT PUMP - SCHEDULE <br /> DO FAN SENSIBLE HEATING NEAT CONNECTION <br /> BLOWER BLAMER EFFICIENCY VENiL COOLING WOUNG CAPACITY HEATING HEAT STRIPS <br /> UNIT BARD UMT UNrT MOTOR AIRFLOW SP® BLOWER GRADE VENTL (FA) FILTER OUTDOOR ENTERING ENTERING CAPACm' CAPACffY 47de9e COP UNIT UNIT STRIPS OUTPUT MCA MOCP UNIT <br /> TAG UNIT YODEL NUMBER S� CITY TYPE CFM SETTING HP (FEG) DEVICE CFM TYPE DR (DB)TEMP (DB)TEMP (CUB)TEMP STUN STUN BTUH 47dege HERTZ VOLTS PHASE KW BTUH AMPS AMPS WGT ADDITIONAL NOTES <br /> HP-1 W1BHB-AO42P4)= 1.5 1 am 709 MED 1/3 -- EOON YERV-8 11.30 95 80 67 18.136 14,290 18'Wo 3.3 80 240 1 06 27.3D4 57 BO 323 LZ3,4,5.8,7.9.10.11 <br /> ADDITIONAL NOTES <br /> 1-CAPACITY LISTED ABOVE ARE IN ACCORDANCE WITH MS/ARI STANDARD 320-2003 FOR SVW(SINGLE PACKAGE VERTICAL UNITS) SEQUENCE OF OPERATION- <br /> 2-COMPLIES WITH EFFICIENCY REWREMENTS OF ANSI ASHRAE/1ESNA 90.1-2016. <br /> 3-BARD THEWAOSTAT 060.7-DAY PROGRAM ABLE 1-UPON A COOLING CALL FROM THE ROOM THERMOSTAT THE UNIT WILL BE IN ECONOMIZER OR MECHANICAL <br /> 4-BARD INDOOR RI <br /> SINSOFt,�8403-057 COOLING MODE OR BOTH DEPENDING ON THE ECONOMIZER JADE CONTROLLER SEIPOINTS. <br /> 5-BARD 002 SENSOR R8103-067 2-UPON A HEATING CALL FROM THE ROOM THERMOSTAT THE UNIT WILL BE IN MECHANICAL HEATING AND THE <br /> 4-2'PLEATED FILTER MERV-8 ECONOMIZER WILL BE DISABLE,2ND STAGE HEAT STRIPS WALL COME ON IF THE ROOM TEMPERATURE DROPS <br /> 5-UNIT COLOR IS-BUCKEYE GRAY- <br /> S-FEAT STRIPS KIT WITH CIRCUIT BREAKER BELOW ITS SETPOINT AND DURING DEFROST. <br /> 7-PRE INSTALLED OUTDDOR THERMOSTAT.SET AT 4ODEG5&LAC CONTROL(R)OPT 3-CO2 SENSOR TO CONTROL THE VENTILATION MODE THROUGH THE OCCUPY CONNECTION AS REQUIRED BY ITS <br /> 10-ECONOYIZER,WI7N JADE CONTROLLER ENTHALPY/rW SENSOR SET POINTS <br /> PLENUM VA R I F I CAT I O N 11-,BSDM REF-70 PROVIDE A MEANS OF SHUTTING DOWN DF THE MECHANICAL HEATING AND COOLING SYSIFRI,NA DOOR SWITCH 4-THESE MODES WITH KEEP REPEATING AND REQUIRED BY THE THERMOSTAT. <br /> MLa TO IWFER ro VOLTAGE <br /> D SET CORRE T T ON lA'AND EnUPMDRY s" <br /> Ya TO LMTAL SITE WU.TAOE AND W CORRECT TAP a iRED6OIWER. <br /> ra TD MET Aw PR071AM ONGMTHOO 6TAT PDI LV ATION P E PROJECT <br /> RE <br /> Mta ro ser A1ND naI3C EOONO®L AND\IDRILA1Kx Ira RlO,ECr REVLWmoNrs <br /> SCALE:1!2"=1'-0" <br /> O O <br /> PLENUM #PWR139 <br /> 1.5 O <br /> TON 4 kW <br /> MECHANICAL NOTES: ------------- i0i <br /> WAWALL HUNG <br /> WA - 20181MC WAC AND 2018 WSEC HEAT PUMP <br /> 1020 CFM MAX <br /> 1. VENTILATION PROVIDED VIA NATURAL VENTILATION IN ACCORDANCE WITH IMC SECTION 402 INLIEU OF DOAS REQUIREMENTS. [WSEC SECTION C 403.3.5 EXCEPTION 1]2. MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUILDING SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF IMC WAC CHAPTER 6 UNLESS OTHERWISE EXEMPTED. <br /> 3. DUCT MATERIAL IS 26 GA. GALVANIZED WITH 2.2-FSK INSULATION. DUCTWORK SHALL BE <br /> SUPPORTED. [IMC WAC SECTION 603] PLENUM #PWS052 <br /> 4. ROUND FLEX DUCT SHALL BE UL LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR <br /> DUCTSAND AIR CONNECTORS.THE MINIMUM THERMAL PERFORMANCE SHALL BE AT R-6, AND <br /> MEASURED IN ACCORDANCE WITH ATSM C 518 OR ATSM C 177 AT 75DEG F MEAN O <br /> TEMPERATURE. INSTALLATIONSHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION <br /> INSTRUCTIONS. MECHANICAL PLAN <br /> 5. MATERIALALIN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25, SMOKE <br /> DEVELOPMENT OF 50. [IMC SECTION 602] <br /> SCALE:1/4"=1'-0" <br /> 6. LOW PRESSURE DUCT SYSTEMS SHALL HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS <br /> AND CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND <br /> SEALED WITH WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC MECHANICAL SYMBOLS <br /> SYSTEMS OR APPROVED TAPES INSTALLED IN ACCORDANCE WITH IMC WAC SECTION 603.9. <br /> 7. DUCT INSULATION SHALL COMPLY WITH IMC WAC SEC 604. <br /> SYMBOL DESCRIPTION <br /> 8. WHEN ISOLATION SLEEVES ARE USED AT LINE CONNECTIONS TO PLENUMS, THEY SHALL COMPLY ® 2'x2' SUPPLY AIR DIFFUSER <br /> NTH IMC WAC CHAPTER 6. <br /> 9. IF DIFFUSERS HAVE NO MANUAL DAMPERS, USE FLOW CONTROL AT WYES. TYPICAL AS NOTED ON TYPICAL DOOR SWITCH WITH 2'x2' RETURN AIR GRILLE <br /> PLAN. TIME DELAY WIRING FOR HEAT PUMPS <br /> 10. MINIMUM OUTSIDE AIR VENTILATION PER IMC WAC TABLE 403.3.1.1. THIS DRAWING IS SHOWN WITH AJUMPERWIRE <br /> INSTALLED ON TERMINALS 41 TO 02-DOOR -X- SUPPLY DUCT w/DIAMETER INDICATOR <br /> 11. OUTSIDE AIR DAMPERS SHALL COMPLY WITH WSEC, SECTION C403.7.8. SNITCH JUMPER'WRE.REMOVE JUMPER WHEN <br /> DOOR SWITCH IS INSTALLED,WIRED AS SHOWN. <br /> 12. ALL NEW SYSTEMS REQUIRE ECONOMIZERS UNLESS EXEMPTED BY EXCEPTIONS. [WSEC SECTION OT THERMOSTAT <br /> 403.5] 0 0 <br /> 13. DOOR SWITCH CONTROLS SHALL BE INSTALLED IN ACCORDANCE WITH WSEC 403.4.1.6 AT ALL r-----------1-ff <br /> DOORS THAT OPEN TO THE OUTDOORS. RT Natural Ventilation rates per IMC Section 402 <br /> 14. MECHANICAL DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR INSIDE DIMENSION. j 91 <br /> j 2 e <br /> 15. ELECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. i 3® W2E3 ®G room#name A2(sf) 4%(sf) openings check notes <br /> 16. CONTRACTOR SHALL ARRANGE ALL HVAC UNITS AND ASSOCIATED ITEMS FOR ACCESS <br /> 39 IBC Break Room 238 9.5 29.83 OK <br /> CLEARANCES. i i A® E® My <br /> 17. THERMOSTAT SCHEDULING TO BE PERFORMED ON SITE BY OTHERS. s® L® ®Y1 DOAS is not provided due to the exception for areas with natural ventilation under 2018 WSEC C403.3.5 Exception 1 <br /> 18. ALL HVAC EQUIPMENT LEAVES FACTORY WIRED FOR 240 VOLT OPERATION. 6®19. THE ACCEPTABLE OPERATING RANGE FOR THE 240V& 208V TAPS ARE: DH® B Natural Ventilation is provided per ZO181MCSection 402.1,402.2and 402.3. <br /> T®I I <br /> I <br /> IAA �L. FIELD 6® 01 1 Section 402.1-The Natural Ventilation shall be provided through the windows and exterior doors(SEE PLAN SHEETA-1 <br /> 240 253 -216 i I INSTALL"" O 0 ADD NEW UNIT LOW VOLTAGE <br /> I I WIRES for Iocation and sizinginformation). <br /> 208 220-187 � � TERM WAL TERMINAL aLOCI( <br /> 20.SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS 1 I MD <br /> BBLOM Section 402.2-The minimum openable area ofthese means of natural ventilation,shall meet the 4%offloorarea <br /> CONNECTED FOR THE APPLIED SITE VOLTAGE. �-- Ifi07-021 requirement.The exterior windows and doors provide direct natural ventilation to the spaces at the perimeter of the <br /> 21. AIR FILTERS IN HVAC UNITS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY OTHERS ON i DOOR SWITCH IFIELD SUPPLIED) <br /> SITE. I - SWITCH IS OPEN WHEN DOOR <br /> IS IN THE OPEN POSITION <br /> 22.REGISTER AIR FLOW TEST AND BALANCE OF HVAC SYSTEM TO BE PROVIDED AND PERFORMED BY I T - SWITCH I6 CLOSED WHENDOOR <br /> OTHERS ON SITE WHEN REQUIRED. L---__i7 IS IN THE CLOSED POSITION <br /> 23.HVAC SITE CONTRACTOR IS RESPONSIBLE FOR BALANCING THE SYSTEM. BALANCING SHALL BE IN THIS TOT WILL COMPLY NY"WSEC U031.I,6 <br /> ACCORDANCE WITH IMC WAC 403.3.1.5. CUSTOMER APPROVAL <br /> DDROV1L <br /> ❑APPROVED <br /> ❑APPROVED EXCEPT AS NOTED PRELIMINARY <br /> ❑ REVISE AS NOTED AND RESUBMIT <br /> APPROVED By Date NOT FOR CONSTRUCTION <br /> COPYRIGHT 2021,BLAZER INDUSTRIES.INC. MOBILE Approved for Const 4GI <br /> b No: 20061 <br /> THIS MATERIAL IS THE EXCLUSIVE PROPERTY BREAK ROOM for: <br /> OF BLAZER INDUSTRIES,INC.AND SHALL Y <br /> Flle Copy: <br /> NOT BE REPRODUCED,USED,OR DISCLOSED 10 x 30 port of Everett - Norton Expansion <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE DUSTRIES,INC. Drawn By:DATE REVISION BY WRITTEN PERMISSION OFBIAZERINDUSTAIES. P.o.aoxaes .w.Dla:ermo.wm M= <br /> WA Pacific Mobile Everett,WA <br /> �� 9a5olneySt. ■ Aumsville.OR97325-0469 IssueOate: <br />