i Permit Inspections <br /> V E R E T T City of Everett <br /> WASHINGTON <br /> Run condensate drain per manufacturer's instructions.Slope minimum of1%per the IMC. <br /> Support pex pipe above and next to tankless with code approved fasteners per the UPC appendix I. <br /> Replace entire washing machine drain with 2"pipe and add vent per the UPC chap 7,8,9,and 10.Standpipe must be between 18"and 30"with trap in <br /> vertical alignment. <br /> *** Have manufacturers installation instructions for tankless water heater onsite for review during next inspection. <br /> *** List is not exhaustive.Ok to have plumber call for questions or clarification. <br /> Submit Delete Note <br /> 12/20/2023 12/20/2023 PLUMB 08-FINAL** JASON CORRECTION see notes <br /> MORRISSEY REQUIRED <br /> Notes: <br /> 12/19/2023 6:46 AM Tony Diwan <br /> Contact Name:Tony Diwan <br /> Site Address:2331 ROCKEFELLER AVE LAUNDRY <br /> Phone:2532009300 <br /> e-Mail:SUNNYDIWAN@GMAIL.COM <br /> -Strap all water heaters with earthquake straps per UPC chap 5,make sure to provide stand off support for tanks as they are several inches away from <br /> supporting walls.-Install foam pads under each tank per UPC chap 5 and WSEC.-Plumb water supplies to water heaters in parallel distribution so there <br /> is even draw from each tank to provide adequate hot water.-Run relief lines to within 6"of the floor per UPC chap 6.-Remove tankless water heaters <br /> and cap gas line.-Cap waste and water lines to downstairs unit that is being removed.-Replace vent fittings with drainage fittings on washer drain per <br /> UPC 7,and 9.Long sweeps.-Fix bottle neck on washer drain where it connects to vertical drain. Must be 2"undiminished on drain. <br /> 12/26/2023 12/26/2023 PLUMB 08 FINAL** JASON CANCELLED eTRAKiT Inspection Request <br /> MORRISSEY <br /> Notes: <br /> 12/21/2023 1:46 PM Tony Diwan <br /> Contact Name:Tony Diwan <br /> Site Address:2331 ROCKEFELLER AVE LAUNDRY <br /> Phone:2532009300 <br /> e-Mail:SUNNYDIWAN@GMAIL.COM <br /> -Rescheduled to 12/27/23.Contractor unable to make inspection window work.Only one inspector today. <br /> 12/27/2023 12/27/2023 PLUMB OS FINAL** JASON CORRECTION see notes <br /> MORRISSEY REQUIRED <br /> Notes: <br /> -Replace San tee on back for AW vent with approved 2"ABS combo per UPC chap 7,9.-Support ABS pipe every 4'horizontally per UPC chap 3.-Replace <br /> crushed 2"mission coupling on common vent in basement storage room.Use approved reducing fittings and shielded mission coupling to transition <br /> between 2"ABS and 11/2"galvanized vent. <br /> 12/29/2023 12/29/2023 PLUMB 08-FINAL** JASON APPRVD-PERMIT see notes <br /> MORRISSEY FINAL <br /> Notes: <br /> 12/27/2023 2:55 PM Tony Diwan <br /> Contact Name:Tony Diwan <br /> Site Address:2331 ROCKEFELLER AVE LAUNDRY <br /> Phone:2532009300 <br /> e-Mail:SUNNYDIWAN@GMAIL.COM <br /> -Two gas tankless water heaters removed.3 new 50 gallon electric tanks installed for common hot water system. <br /> I <br /> Printed:Tuesday,02 January,2024 3 of 3 rk <br /> SUPERION <br />