Laserfiche WebLink
1 2 1 3 1 4 1 5 6 1 7 18 9 10 1 11 <br /> ELECTRICAL SPECIFICATIONS: <br /> PART 1 -GENERAL tgb architects <br /> 2.3 RACEWAY AND BOXES C. FLEXIBLE METAL CONDUIT SHALL BE USED WHERE REQUIRED TO MAKE <br /> x 1.1 GENERAL CONDITIONS CONNECTIONS TO VIBRATING OR ROTATING EQUIPMENT. <br /> A. RIGID STEEL CONDUIT,ZINC COATED;ANSI CODA:ALL FITTINGS SHALL BE SCREW <br /> A. THE WORK UNDER THIS DIVISION INCLUDES FURNISHING ALL PERMITS,MATERIALS, THREAD TYPE,COUPLINGS,LOCKNUTS,BUSHINGS,ETC.SHALL BE HOT DIPPED D. ALL RIGID STEEL CONDUIT INSTALLED IN CONTACT WITH EARTH SHALL BE PVC <br /> EQUIPMENT, LABOR,SUPERVISION,TOOLS,EXPENSES,TRAVEL,AND ITEMS NECESSARY GALVANIZED. COATED OR OTHERWISE PROTECTED WITH A BITUMASTIC MATERIAL <br /> FOR THE CONSTRUCTION,INSTALLATION,CONNECTION,TESTING AND OPERATION OF ALL t 425.778.1530 21911 76th Ave W.Ste 210 <br /> ELECTRICAL WORK FOR THIS PROJECT,AS INTENDED BY THE CONTRACT DOCUMENTS. B. ELECTRICAL METAWC TUBING,ZINC COATED:ANSI C80.3:COUPLINGS AND f 425.774.7803 Edmonds WA 98026 <br /> CONNECTORS SHALL BE STEEL GALVANIZED,COMPRESSION TYPE WITH GLAND SEALING E. MINIMUM SIZE OF CONDUIT SHALL BE CODE SIZE FOR THE NUMBER AND SIZE OF <br /> B. THE GENERAL CONDITIONS,SUPPLEMENTARY CONDITIONS AND SPECIAL CONDITIONS RINGS. CONDUCTORS UNLESS A LARGER SIZE IS INDICATED ON THE PLANS. info@tgbarchitecls.com <br /> ARE A PART OF THIS CONTRACT AND APPLY TO THIS SECTION AS FULLY AS IF REPEATED www.tgbarchitects.com <br /> HEREIN. C. FLEXIBLE METAL CONDUIT: UL 1:FLEXIBLE METAL CONDUIT SHALL BE GALVANIZED F. WHERE PENETRATIONS ARE MADE THROUGH PARTITIONS, PROVIDE SEALING MATERIAL <br /> STEEL OR ALUMINUM.WHERE EXPOSED TO DAMP OR WET LOCATIONS FLEXIBLE CONDUIT TO MAINTAIN THE FIRE RATING OF THE PARTITION.FOR EXTERIOR WALLS PROVIDE <br /> 1.2 CODES AND REGULATIONS SHALL BE LIQUID-TIGHT WITH OUTER SUITABLE LIQUID-TIGHT FITTINGS LISTED FOR THE SLEEVES AND SEALING TO PREVENT WATER AND MOISTURE PENETRATION AND TO <br /> PURPOSE. PREVENT VARMINT AND INSECT INTRUSION. <br /> A. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH APPLICABLE <br /> REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION AND THE UTILITY FURNISHING D. OUTLET AND JUNCTION BOXES:OUTLET AND JUNCTION BOXES SHALL BE 3.3 INSTALLATION OF CONDUCTORS AND EQUIPMENT CONNECTIONS <br /> SERVICES FOR THE SPECIFIC FACILITY LOCATION. GALVANIZED,ONE-PIECE PRESSED OR WELDED STEEL,KNOCKOUT TYPE EXCEPT AS <br /> B. CODES GOVERNING THIS WORK INCLUDE BUT ARE NOT UMRED TO THE LATEST <br /> OTHERWISE NOTED OR SPECIFIED. A ALL WIRING SHALL BE INSTALLED IN CONDUIT,WIREWAYS,OR GUTTERS EXCEPT ADOPTED EDITION OF THE FOLLOWING: E. PROVIDE FIRE-STOPPING WHERE CONDUIT PASSES THROUGH A RATED ASSEMBLY. WHERE OTHER RACEWAY SYSTEMS ARE SPECIFICALLY CALLED FOR. EVIDENCE <br /> NFPA 70(NATIONAL FIRE PROTECTION ASSOCIATION)NATIONAL ELECTRICAL CODE <br /> (NEC) AS AMMENDED BY WASHINGTON CITIES(2020 WCEC) 2.4 WIRING DEVICES(PROVIDE DEVICES PER DRAWINGS) B. INSTALL WIRING ONLY AFTER RACEWAY INSTALLATION HAS BEEN COMPLETED BASED <br /> NFPA 72(NATIONAL FIRE PROTECTION ASSOCIATION)NATIONAL FIRE ALARM AND CLEANED AND DRIED. EBD DESIGN <br /> SIGNALING CODE A. RECEPTACLES: SERVICES =- <br /> NFPA 101 (NATIONAL FIRE PROTECTION ASSOCIATION) LIFE SAFETY CODE 1. PROVIDE 20 AMP RECEPTACLES IN ALL CONVENIENCE AND DEDICATED LOCATIONS. C. PULLING LUBRICANTS APPROVED BY THE WIRE OR CABLE MANUFACTURE MAY BE <br /> CITY OF RENTON ORDINANCES AND REGULATIONS PLUG TAIL ACCEPTABLE. UTIUZED. <br /> WSEC-2018 COMMERCIAL 2. RECEPTACLES COVERS TO BE STAINLESS STEEL TYPE OR AS APPROVED BY <br /> OWNER. D. MAKE ALL CONNECTIONS AND SPLICES REQUIRED FOR COMPLETE AND OPERABLE <br /> 1.3 STANDARDS 3. GROUND PIN/NEUTRAL LOCATION TO BE CONSISTENT WITH FACILITY IN ALL ELECTRICAL INSTALLATION.CONNECTIONS AND SPLICES SHALL BE MADE ONLY IN <br /> RENOVATION OR EXPANSION PROJECTS,AND FOR NEW PROJECTS SHALL BE GROUND PIN JUNCTION, PULL OR OUTLET BOXES OR IN WIREWAYS,SWITCHBOARDS AND PANELBOARDS <br /> A. ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE UNDERWRITERS LABORATORIES DOWN. HAVING CODE SIZED GUTTER SPACE OR CROSS-SECTIONAL AREA WIRES#8 AND <br /> LISTED AND INSTALLED IN ACCORDANCE WITH THE LISTING AND LABELING OF THE 4. HEAVY DITTY SPECIFICATION GRADE. SMALLER CONNECTIONS SHALL BE MADE WITH SPRING TYPE CONNECTORS;WIRES6 AND <br /> EQUIPMENT. 5. TAMPER PROOF IN PUBLIC AREAS. LARGER,CONNECTIONS SHALL BE MADE WITH SPLIT-BOLT OR COMPRESSION TYPE <br /> B. INSTALLATION SHALL CONFORM TO THE NECA(NATIONAL ELECTRICAL CONTRACTORS <br /> B. SWITCH COVER PLATES TO BE STAINLESS STEEL TYPE OR AS APPROVED BY SOLDERLESS CONNECTORS,INSULATED AND TAPED.O .WNER <br /> ASSOCIATION)STANDARD OF INSTALLATION. E. UPON COMPLETION OF WORK, UPDATED ALL PANEL DIRECTORIES WITH CORRECT <br /> M. <br /> C. CIRCUITING: CIRCUIT INFORMATION. PROVIDE PRINTED CIRCUIT DIRECTORIES IN PANELS AFFECTED BY y a <br /> IJ <br /> 1.4 SUBMITTALS 1. CONVENIENCE DUPLEX RECEPTACLES-MAXIMUM OF SIX PER 20A CIRCUIT. THE PROJECT. PEN AND INK CHANGES TO THE EXISTING DIRECTORIES ARE NOT ��'� F Wit*A✓ <br /> A. ELECTRONIC COPIES, IN.PDF FORMAT,OF MATERIALS LIST,SHOP DRAWINGS AND 2. HOMERUN CONDUIT-MAXIMUM 4 CIRCUITS. ACCEPTABLE. ^eye <br /> DATA SHEETS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW.SUBMITTALS SHALL 3. POWER AND LIGHTING SHALL NOT BE ON THE SAME CIRCUITS(EXCEPT - <br /> BE MADE,AND FAVORABLE REVIEW SECURED BEFORE MATERIAL AND EQUIPMENT IS UNDER-CABINET LIGHTING). 3.4 GROUNDING <br /> INSTALLED. 4. 480/277V BRANCH CIRCUIT WIRING SHALL BE IN SEPARATE CONDUITS FROM 57724 <br /> 208/120V CIRCUIT WIRING. A PERMANENTLY AND EFFECTIVELY GROUND ALL CONDUIT,BOXES,ENCLOSURES AND IST1? � <br /> B. MATERIALS LIST SHALL INCLUDE: DEVICES, DISCONNECTS, LIGHT FIXTURES,LIGHTING EQUIPMENT TO COMPLY WITH NEC 250 AND ALL APPLICABLE CODES AND REGULATIONS. ZONAL ' <br /> CONTROL DEVICES AND OTHER ITEMS SPECIFIED OR CALLED FOR ON THE DRAWING.THE 2.5 FUSIBLE SWITCHES 0710812024 <br /> LIST SHALL INCLUDE MANUFACTURE,TYPE AND SUCH OTHER DESCRIPTIVE DATA AS MAY B. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL RACEWAYS <br /> BE REQUIRED TO DETERMINE THE ACCEPTABILITY OF EACH ITEM. A. TYPE GD,GENERAL DUTY,SINGLE THROW, 100 A AND SMALLER: UL 98 AND SIZED IN ACCORDANCE WITH NEC TABLE 250.122 WHETHER SPECIFICALLY CALLED FOR <br /> NEMA KS 1,HORSEPOWER RATED,WITH CARTRIDGE FUSE INTERIORS,LOCKABLE HANDLE ON THE PLANS OR NOT. <br /> C. SHOP DRAWINGS AND DATA SHEETS FOR EQUIPMENT AND SYSTEMS SHALL BE WITH CAPABILITY TO ACCEPT TWO PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED <br /> SUBMITTED WHERE REQUIRED IN THE FOR THOSE ITEMS. <br /> INFORMATION ON EACH COMPONENT,WIRING SPECIFICATIONS DIAGRAMS,LAYOUTS,DIMENSIONSUDE AND POSITION. 3.5 PROTECTION OF PREMISES <br /> SUFFICIENT OTHER DATA TO ESTABLISH COMPLIANCE WITH THE SPECIFICATIONS AND B. TYPE HD,HEAVY DUTY,SINGLE THROW, LARGER THAN 100 AMP: UL 98 AND <br /> ACCEPTABILITY OF THE EQUIPMENT OR SYSTEM. NEMA KS 1,HORSEPOWER RATED,WITH CUPS OR BOLT PADS TO ACCOMMODATE FUSES, A CONTRACTOR SHALL CLEAN WORK AREA AND REMOVE ALL CONSTRUCTION DEBRIS <br /> LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE PADLOCKS,AND INTERLOCKED DAILY PRIOR TO LEAVING THE PREMISES. <br /> D. SHOP DRAWINGS SHALL BE SUBMITTED IN EITHER HALF OR FULL SIZE AS WITH COVER IN CLOSED POSITION. <br /> FOLLOWS: B. THE CONTRACTOR SHALL PROTECT ALL EXISTING SURFACES, MATERIALS,EQUIPMENT <br /> C. ACCESSORIES: AND PROPERTY FROM DAMAGE AS RESULT OF CONSTRUCTION ACTIVITIES. DAMAGED <br /> 1. HALF SIZE SHALL BE 15 INCHES BY 21 INCHES MINIMUM. MINIMUM HALF SIZE 1. CLASS R FUSE KIT: PROVIDES REJECTION OF OTHER FUSE TYPES WHEN CLASS R SURFACES,MATERIALS,EQUIPMENT AND PROPERTY SHALL BE REPAIRED TO EXISTING <br /> FONT HEIGHT SHALL BE 1/16 INCH. WIDTH SHALL BE PROPORTIONAL NO LESS THAN FUSES ARE SPECIFIED. CONDITIONS AT NO COST TO THE OWNER. <br /> 70 PERCENT OF THE HEIGHT. 2.6 NONFUSIBLL SWITCHES 2. FULL SIZE SHALL BE 30 INCHES BY 42 INCHES MINIMUM. MINIMUM FULL-SIZE 3.6 TESTING OF ELECTRICAL SYSTEMS <br /> FONT HEIGHT SHALL BE 1/8 INCH. WIDTH SHALL BE PROPORTIONAL NO LESS THAN 70 A. TYPE GD,GENERAL DUTY,SINGLE THROW, 100 A AND SMALLER: UL 98 AND <br /> PERCENT OF THE HEIGHT. NEMA KS 1,HORSEPOWER RATED,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT TWO A EQUIPMENT INSTALLED OR MODIFIED UNDER THIS SECTION SHALL BE INSPECTED <br /> E. PROVIDE PRODUCT DATA AND SHOP DRAWINGS FOR THE FOLLOWING: PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION. AND TESTED FOR PROPER OPERATION IN ACCORDANCE WITH APPLICABLE NETA <br /> 1. WIRING DEVICES ACCEPTANCE TESTING STANDARDS. <br /> 2. DISCONNECTS B. TYPE HD,HEAVY DUTY,SINGLE THROW, LARGER THAN 100 AMP. UL 98 AND <br /> 3. LIGHTING FIXTURES NEMA KS 1,HORSEPOWER RATED,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE B. SYSTEMS SHALL BE TESTED FOR SHORT CIRCUITS,OPEN CIRCUITS,PHASE <br /> PADLOCKS,AND INTERLOCKED WITH COVER IN CLOSED POSITION. ROTATION AND SHALL BE FREE FROM MECHANICAL AND ELECTRICAL DEFECTS. <br /> 1.5 SUBSTITUTIONS C. TYPE HD,HEAVY DUTY,DOUBLE THROW, 1200 A AND SMALLER: UL 98 AND PROVIDENCE <br /> NEMA KS 1,HORSEPOWER RATED,LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT THREE C. THE CONTRACTOR SHALL CORRECT DEFICIENCIES AND PROVIDE RETESTING AT NO <br /> NO SUBSTITUTIONS ARE ALLOWED.ALTERNATIVE MANUFACTURERS WILL BE , . EXPENSE TO THE OWNER AND ENGINEER UNTIL THE EQUIPMENT AND SYSTEM IS <br /> C PADLOCKS AND INTERLOCKED WITH COVER IN CLOSED POSITION COLBY PET CT <br /> CONSIDERED FOR ELECTRICAL EQUIPMENT SPECIFIED AND SHOWN HEREIN.THE SPECIFIED SATISFACTORY TO THE OWNER AND THE ENGINEER. <br /> MANUFACTURER'S EQUIPMENT SETS THE LEVEL OF QUAUTY FOR THE WORK. 2.7 ENCLOSURES <br /> WORK AND EQUIPMENT NOT MEETING THE LEVEL OF QUALITY SHALL BE REJECTED. THE A. ENCLOSED SWITCHES AND CIRCUIT BREAKERS: NEMA AB 1,NEMA KS 1,NEMA GENERAL NOTES: <br /> ENGINEER HAS DISCRETION TO ACCEPT OR REJECT THE ALTERNATIVE MANUFACTURER'S 250,AND UL 50.TO COMPLY WITH ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION. 1. COMPLY WITH NEC AS ADOPTED AND AMENDED BY LOCAL AHJ. <br /> EQUIPMENT. 1. INDOOR,DRY AND CLEAN LOCATIONS: NEMA 250,TYPE 1. <br /> 1.6 PERMITS AND DRAWINGS 2. OUTDOOR LOCATIONS: NEMA 250,TYPE 3R. 2. ALL EXISTING WORK IS BASED ON RECORD DRAWINGS AND HAS NOT BEEN FIELD <br /> 3. WASH-DOWN AREAS: NEMA 250,TYPE 4X,STAINLESS STEEL. VERIFIED IN FULL.THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING <br /> A PERMITS AND INSPECTIONS SHALL BE OBTAINED,COORDINATED AND PAID FOR BY 4. OTHER WET OR DAMP, INDOOR LOCATIONS: NEMA 250,TYPE 4. INFORMATION RELEVANT FOR THE SCOPE OF THIS PROJECT. 1717 13th St <br /> THE ELECTRICAL CONTRACTOR. 5. INDOOR LOCATIONS SUBJECT TO DUST,FALLING DIRT,AND DRIPPING Everett,WA 98201 <br /> NONCORROSIVE LIQUIDS: NEMA 250,TYPE 12. 3. ALL SCOPE NOT IDENTIFIED FOR DEMOLITION OR MODIFICATIONS IS EXISTING TO <br /> B. THE CONTRACTOR SHALL PAY ALL FEES AND TAXES FOR THE TOTAL COST OF REMAIN.REFER TO MECHANICAL DRAWINGS FOR DEMOLITION SCOPE OF WORK. <br /> CONSTRUCTION,INCLUDING CONTRACTOR AND OWNER FURNISHED MATERIALS AND 2.8 GROUNDING <br /> EQUIPMENT AS SHOWN AND SPECIFIED. 4. ALL WORK SHALL BE DONE WITH MAXIMUM CARE EXERCISED DURING DEMOLITION CONSTRUCTION <br /> C. THE CONTRACTOR SHALL OBTAIN AND PAY THE PLAN REVIEW FEE. A. PROVIDE COPPER GROUNDING. AND MODIFICATIONS PROCESS.ANY ACCIDENTAL OR INTENTIONAL DAMAGE TO EQUIPMENT �/� <br /> TO REMAIN SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER. DOCUMENTS <br /> D. THE CONTRACTOR SHALL PAY FOR PLAN REVIEW FEES AND RE-INSPECTIONS B. PROVIDE DEDICATED NEUTRAL(NO SHARED NEUTRALS)WITH ALL BRANCH CIRCUITS REMOVED ELECTRICAL <br /> MO <br /> RESULTING FROM SUBSTITUTIONS. FEES DUE TO SUBSTITUTIONS SHALL BE AT NO COST IN EACH CONDUIT.USE OF MULTI-POLE BREAKERS OR BREAKER TIES IN LIEU OF 5. UNLESS OTHERWISE REQUESTED BY THE OWNER ALL RE EQUIPMENT,DEVICES,AND MATERIALS SHALL BE DISPOSED RE THE ELECTRICAL <br /> TO THE OWNER. DEDICATED NEUTRALS IS NOT PERMITTED. <br /> CONTRACTOR. <br /> E. THE CONTRACTOR SHALL INCLUDE APPLICABLE PLAN REVIEW FEES AND C. ALL CONDUITS WILL BE PROPERLY BONDED WITH INSULATED GROUND WIRE RUN <br /> RE-INSPECTION FEES IN CHANGE ORDER PROPOSALS. WITH CONDUCTORS. 6. ALL WORK SHALL BE DONE ON DE-ENERGIZED EQUIPMENT ONLY AND ALL LOTO <br /> (LOCK-OUT TAG OUT)PROCEDURES SHALL BE FOLLOWED AS REQUIRED PER NEC AND <br /> 1.7 RECORD DRAWINGS OSHA <br /> D. ALL PANELS AND TRANSFORMERS MUST HAVE A DEDICATED EQUIPMENT GROUNDING <br /> A ON A SET OF CONTRACT DRAWINGS KEPT AT THE SITE DURING CONSTRUCTION, CONDUCTOR IN ADDITION TO ELECTRODE OR BUILDING GROUNDS AS REQUIRED PER <br /> MARK ALL WORK THAT IS INSTALLED DIFFERENTLY FROM THAT SHOWN,INCLUDE ANY CODE. <br /> REVISED CIRCUITRY,MATERIAL OR EQUIPMENT. UPON CONCLUSION OF THE WORK, ELECTRICAL <br /> DELIVER TO THE OWNER REPRESENTATIVE A SET OF SIGNED AND DATED"AS-BUILD' 2.9 CIRCUIT BREAKERS <br /> DRAWINGS. <br /> 1.8 WARRANTY A. CIRCUIT BREAKERS SHALL BE THE SAME MANUFACTURER AS THE PANELBOARD OR SPECIFICATIONS <br /> SWITCHBOARD IN WHICH THEY ARE INSTALLED. <br /> A. ALL WORK SHALL INCLUDE A WARRANTY FOR MINIMUM PERIOD OF ONE YEAR <br /> FROM THE DATE OF ACCEPTANCE BY THE OWNER.THE WARRANTY PERIOD FOR CERTAIN B. CIRCUIT BREAKERS SHALL BE MOLDED-CASE BOLT-ON TYPE. PLUG-IN TYPES ARE ISSUANCE <br /> ITEMS SHALL BE LONGER,AS INDICATED IN THE SPECIFICATIONS FOR THOSE ITEMS. NOT ACCEPTABLE.MULTI-POLE BREAKERS SHALL HAVE INTERNAL TRIP AND SINGLE No. Description Date <br /> HANDLE OPERATION. PERMIT SET 071081202.1 <br /> B. SHOULD ANY MALFUNCTION DEVELOP DURING THE WARRANTY TIME PERIOD DUE TO <br /> DEFECTIVE MATERIAL,FAULTY WORKMANSHIP,OR NON-COMPLIANCE WITH PLANS, C. PROVIDE ALL NECESSARY MOUNTING HARDWARE,ACCESSORIES AND CLOSURE <br /> SPECIFICATIONS,CODE OR DIRECTIONS OF THE OWNER OR OWNER'S REPRESENTATIVE, DEVICES AS NECESSARY. <br /> THE CONTRACTOR SHALL FURNISH ALL NECESSARY LABOR AND MATERIALS TO CORRECT <br /> THE MALFUNCTION AT NO ADDITIONAL COST TO THE OWNER. D. SHORT CIRCUIT INTERRUPTING CAPACITY SHALL BE AS INDICATED ON PLANS OR TO <br /> MATCH RATING OF THE EXISTING PANELBOARD INTO WHICH THE CIRCUIT BREAKER IS TO <br /> PART 2- PRODUCTS BE INSTALLED. <br /> 2.1 MATERIAL 2.10 EQUIPMENT IDENTIFICATION <br /> A. MATERIALS SHALL BE NEW, FREE OF DEFECTS AND OF CURRENT MANUFACTURE. <br /> EXISTING MATERIALS SHALL NOT BE REUSED UNLESS SPECIFICALLY NOTED OTHERWISE. A. ENCLOSED CIRCUIT BREAKERS,DISCONNECT SWITCHES, RECEPTACLES AND LIGHT <br /> SWITCHES: PRINTED LABEL WITH(PANEL)NAME AND CIRCUIT NUMBER. (EXAMPLE: <br /> 2.2 WIRE AND CABLE(600 VOLT AND LESS) "PP4-23"FOR PANEL PP4,CIRCUIT 23) <br /> NORMAL POWER:9"BLACK LETTERS <br /> A. PRODUCTS SHALL COMPLY WITH UL 44 AND UL 83 SINGLE CONDUCTOR INSULATED <br /> WIRE. PART 3-EXECUTION <br /> B. WIRE AND CABLE FOR USE ON SYSTEMS OF 600 VOLTS AND LESS SHALL BE 600 <br /> VOLT WITH NEC TYPE THHN/THWN OR XHHW INSULATION FOR BRANCH CIRCUITS AND 3.1 INSTALLATION OF ELECTRICAL EQUIPMENT <br /> FEEDERS SMALLER THAN#2AWG.XHHW INSULATION SHALL BE USED FOR#2AWG AND <br /> LARGER FEEDER CONDUCTORS. A. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS,NECA <br /> 1. USE TYPE THHN/THWN CONDUCTORS FOR ALL BRANCH POWER AND LIGHTING STANDARD OF INSTALLATION AND IN ACCORDANCE WITH THE UL LISTING FOR THE <br /> CIRCUITS. EQUIPMENT OR MATERIAL <br /> 2. USE TYPE XHHW IN AMBIENT TEMPERATURES BELOW 32'F.USE TYPE XHHW-2 FOR ALL DISCONNECTS,FUSES,CIRCUIT BREAKERS SHALL BE PROVIDED AS INDICATED AND <br /> ALL WIRING CONNECTED TO GFCI BREAKERS. FOR PROPER PROTECTION OF THE EQUIPMENT SERVED.PROVIDE ALL FLEXIBLE CONDUIT, <br /> BOXES,PULL BOXES,FITTINGS,SEALS,AND OTHER MATERIALS REQUIRED FOR A <br /> C. ALL GROUNDING CONDUCTORS SHALL BE INSULATED. COMPLETE AN OPERATIONAL SYSTEM. <br /> THE WORK UNDER THIS DIVISION INCLUDES FURNISHING ALL PERMITS,MATERIALS, <br /> D. MC OR HCF-MC CABLE SHALL BE PERMITTED FOR LIMITED USE AS FOLLOWS: EQUIPMENT,LABOR,SUPERVISION,TOOLS AND ITEMS NECESSARY FOR THE <br /> CONSTRUCTION,INSTALLATION,CONNECTION,TESTING AND OPERATION OF ALL ELECTRICAL <br /> 1. TEMPORARY POWER PROVISIONS WORK FOR THIS PROJECT,AS INTENDED BY THE CONTRACT DOCUMENTS. <br /> 2. EQUIPMENT CONNECTIONS TO COMPENSATE FOR MOVEMENT AND VIBRATION. <br /> 3. TERMINAL CONNECTIONS TO LIGHT FIXTURES NOT TO EXCEED 6 FEEr IN LENGTH. <br /> 4. LIGHTING AND BRANCH CIRCUITS. <br /> 5. CONCEALED AREAS INDOORS. 3.2 INSTALLATION OF RACEWAY AND FITTINGS PROJECT INFORMATION <br /> 1032 <br /> A. INSTALL RIGID STEEL CONDUIT WHERE EXPOSED TO WEATHER,PLACED PROJECT NUMBER: B24-JGG <br /> UNDERGROUND,IN OR UNDER CONCRETE OR MASONRY CONSTRUCTION, IN CONTACT WITH DRAWN BYOJECT: <br /> JOG <br /> a EARTH AND AS INDICATED ON PLANS. DRAWN sY: cMB <br /> B. EMT MAY BE USED IN ABOVE GRADE INTERIOR DRY LOCATIONS AND WHERE <br /> PROTECTED FROM PHYSICAL DAMAGE. <br /> SHEET NO <br /> E0.01 -PET <br /> 1 2 3 4 5 6 7 8 9 10 11 <br />