<br /> ® MICROMATIC® STANDARD
<br /> N11UNG4 RESPONSE UPRIGHT
<br /> SPRINKLER VK100 (K5.6)
<br /> The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
<br /> Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
<br /> Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
<br /> Approval Chart 1 (UL) Temperature KEY
<br /> Micromatic®Standard Response Upright S Sprinkler VK100 �Finish
<br /> pp A1Xt Escutcheon(if applicable)
<br /> Maximum 175 PSI (12 bar)WWP
<br /> Sprinkler Thread Size Nominal K-Factor Overall Length Listings and Approvals3
<br /> Base Part SIN (Refer also to UL Design Criteria.)
<br /> Number' NPT BSP U.S. metriO Inches I mm cULus" VdS LPCB E
<br /> Standard Orifice
<br /> 12986 VK100 1/2" 15 mm 5.6 80.6 1 2-1/4" 1 57 Al, B3,C4, D2, E5 -- -- --
<br /> 12993 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al, B3,C4, D2, E5 -- -- --
<br /> NOTICE-Product Below-Limited Availability(Contact Local Viking Office)
<br /> 10138 VK100 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B3,C4, D2, E5 -- -- --
<br /> 10193 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al, B3,C4, D2, E5 -- -- --
<br /> Approved Temperature Ratings
<br /> A- 135 OF(57°C), 155 OF(68°C), 175 OF(79°C),
<br /> 200 OF (93 °C), 286 OF (141 °C), and 360 OF (182 Approved Finishes
<br /> °C) 1 -Brass, Chrome,White Polyester56,and Black Polyester5,6
<br /> B-135 OF(57°C), 155 OF(68°C), 175 OF(79°C), 2-Brass and Chrome
<br /> and 200 OF(93°C) 3-Wax-Coated Brass and Wax Over Polyesters
<br /> C-286 OF(141 °C) 4- High Temperature 200 OF (93 °C)Wax Coating (corrosion resistant); maximum ambient tem-
<br /> D-500 OF(260°C)7 perature allowed at ceiling= 150 OF(65°C)
<br /> E - 155 OF (68 °C), 175 OF (79 °C), 200 OF (93 5-ENT5
<br /> °C), 286 OF(141 °C), 360 OF(182 °C), and 500 OF
<br /> (260°C)'
<br /> Footnotes
<br /> 'Base part number is shown. For complete part number, refer to Viking's current price schedule.
<br /> 2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
<br /> 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
<br /> °Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada.
<br /> s cULus Listed as corrosion resistant.
<br /> 6 Other colors are available on request with the same Listings and Approvals as the standard colors.
<br /> 7 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above
<br /> 300 OF(149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 OF(149 °C),
<br /> the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
<br /> DESIGN CRITERIA- UL
<br /> (Also refer to Approval Chart 1.) AM
<br /> cULus Listing Reauirements:
<br /> The Viking Micromatic®Standard Response Upright Sprinkler VK100 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with
<br /> the latest edition of NFPA 13 for standard spray sprinklers.
<br /> • Designed for use in Light, Ordinary,and Extra Hazard occupancies.
<br /> • The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
<br /> IMPORTANT:Always refer to Bulletin Form No. F 091699 -Care and Handling of Sprinklers.Also refer to Bulletin
<br /> Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
<br /> stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
<br /> APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances, and
<br /> standards, whenever applicable.
<br /> Form No. F_052014 19.10.14 Rev 19.1