<br /> ® MICROMATIC® STANDARD
<br /> RESPONSE UPRIGHT
<br /> N411UNG4 SPRINKLER VK100 (K5.6)
<br /> The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058
<br /> Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
<br /> Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
<br /> Approval Chart 2 (FM)
<br /> Temperature KEY
<br /> Micromatic®Standard Response Upright Sprinkler VK100 ;�Finish
<br /> Maximum 175 PSI (12 bar)WWP A1X�Escutcheon(if applicable)
<br /> Sprinkler Base SIN Thread Size Nominal K-Factor Overall Length FM Approvals'
<br /> Part Number' NPT BSP U.S. I metric2 Inches mm (Refer also to Design Criteria below.)
<br /> Standard Orifice
<br /> 12986 VK100 1/2" 15 mm 5.6 1 80.6 L2-14"±57
<br /> 57 Al, B2,C3, D1, E4, F6
<br /> 12993 VK100 -- 15 mm 5.6 80.6 Al, D1, E4, F6,G5
<br /> NOTICEOffice)
<br /> 10138 VK100 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2,C3, D1, E4, F6
<br /> 10193 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al,G5, D1, E4, F6
<br /> Approved Temperature Ratings
<br /> A-135 OF(57°C), 155 OF(68°C), 175 OF(79°C),200
<br /> OF(93°C),212 OF(100°C),286 OF(141 °C),and 360 OF
<br /> Approved Finishes
<br /> (182-C) 1 -Brass, Chrome,White Polyester',and Black Polyester'
<br /> B-135 OF(57°C), 155 OF(68°C), 175 OF(79°C),200 OF 2-Wax-Coated Brass(corrosion resistant)
<br /> (93°C)and 212 OF(100°C) 3-High Temperature 200 OF(93°C)Wax Coating(corrosion resistant); maximum ambient
<br /> C-286 OF(141 °C)
<br /> D-500 OF(260°C)5 temperature allowed at ceiling= 150 OF(65°C)
<br /> E-155 OF(68°C) 4-Wax-Coated Brass and Wax Over Polyester'
<br /> F-155 OF(68°C), 175 OF(79°C),200 OF(93°C),286 OF 5-White Polyester and Wax-Coated Brass(corrosion resistant)
<br /> (141 °C),360 OF(182°C),and 500 OF(260°C)5 6-ENT6
<br /> G-135 OF(57°C), 155 OF(68°C), 175 OF(79°C),and
<br /> 200 OF(93°C)
<br /> Footnotes
<br /> ' Base part number is shown. For complete part number, refer to Viking's current price schedule.
<br /> 2 Metric K-factor shown is for use when pressure is measured in bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
<br /> 'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
<br /> °Other colors are available on request with the same Approvals as the standard colors.
<br /> 5 Sprinklers of Ultra-High temperature rating are intended for use inside ovens,dryers,or similar enclosures with normal operating temperatures above
<br /> 300 OF (149 °C).Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 OF (149 °C),
<br /> the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
<br /> 6 FM approved as corrosion resistant.
<br /> Pill DESIGN CRITERIA- FM Pill
<br /> (Also refer to Approval Chart 2.)
<br /> FM Approval Requirements:
<br /> The Viking Micromatic® Standard Response Upright Sprinkler VK100 is is FM Approved as standard response Non-Storage upright sprinkler as
<br /> indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
<br /> Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
<br /> requirements, hydraulic design,ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
<br /> NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria.
<br /> IMPORTANT.Always refer to Bulletin Form No. F_091699 -Care and Handling of Sprinklers.Also refer to Bulletin
<br /> Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
<br /> stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
<br /> APSAD,VdS or other similar organizations, and also with the provisions of governmental codes, ordinances,and
<br /> standards, whenever applicable.
<br /> Form No. F_052014 19.10.14 Rev 19.1