Mr. Todd Bullock <br /> Northshore Christian Academy <br /> Plan Check Number: B2401-071, First Building Review Letter <br /> March 11, 2024 <br /> General: <br /> 1. Sheet A1.1 designates applicable codes as year 2015 IBC. Please revise to 2018 IBC <br /> 2. Sheet A1.1 designates construction type as VB. The building was constructed under the 1997 <br /> UBC as II-N, which requires noncombustible construction. Comparable construction type is IIB. <br /> Architecture: <br /> 3. Sheet A2.3, please add a note calling out the 1-hour mechanical shafts. <br /> 4. Sheet A2.4, Upper Floor Plan. Room C234 requires panic hardware on the doors per 2018 IBC <br /> 1010.1.10. Please coordinate with door schedule. Please demonstrate that all doors on the exit <br /> path to the exterior, including existing doors, provide panic hardware. <br /> 5. Sheet A2.4, Upper Floor Plan. Room C217 exceeds the limits of Common Path of Egress Travel <br /> per Table 1006.2.1. This also creates a dead end corridor per 2018 IBC 1020.4.2. Please <br /> revise the plans to meet these limits. <br /> 6. Change of use from 'B'to'E' necessitates accessible means of egress. Please demonstrate how <br /> accessible egress is being provided per 2018 IBC 1009. Provide Two-way communication per <br /> 2018 IBC 1009.8. <br /> 7. Sheets A2.4, verify all door clearances are accessible per ICC 117.1-2009, 404.2.3. <br /> 8. Sheet A2.4, and A5.1, please demonstrate that bathroom facilities meet accessibility <br /> requirements of ICC 117.1-2009 as follows: <br /> a. Drawings 1 and 2, show dimensions for the vertical grab bars <br /> b. Drawing 3, please dimension the accessible stall per ICC 117.1-2009. <br /> 9. Sheet A2.5 shows a grid ceiling with lights. Proposed lighting and mechanical systems are <br /> unclear. Electrical and Mechanical may be separate permits, however; building permit review <br /> includes energy code review. Please provide energy code compliance worksheets for lighting <br /> and mechanical. waenergvcodes.com/web tool forms.Php?energy code=2018 <br /> This review has been performed for general compliance with the building codes as adopted and <br /> amended by the state of Washington and the city of Everett. Corrections and comments made <br /> during the review process do not relieve the project from compliance with code and permit <br /> requirements. The designers-of-record are responsible for a complete design in accordance with the <br /> laws of the state of Washington. <br /> If you have any questions or require additional clarification, please contact us. <br /> Respectfully, <br /> Scott Schreffler, RA <br /> Senior Architect/ Commercial Building Plans Examiner <br /> (425) 257-7287 <br /> sschreffler@everettwa.gov <br /> S:\#Common\Bldg Permit Reviews\1_Commercial Reviews\B2401-070 & -071 - Northshore Christian <br /> Academy\B2401-071 - NCA Bldg C - 1st Review Letter.docx <br /> 3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 2 <br />