Laserfiche WebLink
March 14, 2024 D [ECIEVE <br /> Scott Schreffler, RA <br /> Senior Architect/ Commercial Building Plans Examiner MAR 2 0 2024 <br /> City of Everett Permit Services(425) 257-7287 CITY OF E V E R E TT sschreffier@everettwa.gov Permit Services <br /> Review Type: Building <br /> In response to the comments from Residential Building Review for B2401-012 dated February <br /> 29, 2024. <br /> GENERAL <br /> COMMENT/CORRECTION: <br /> 1. This review is for compliance to the IRC. Owner is responsible for compliance with other AFH <br /> requirements.AFH Section R330 referenced herein refers to WAC-51-0330, part of WAC 51-51 <br /> State Building Code adoption and amendments. (WAC 51-51). <br /> RESPONSE: This is noted. <br /> COMMENT/CORRECTION: <br /> 2. Historical photos shows accessory structures in the back yard. Please indicate if these are <br /> existing structures to remain or to be removed. If to remain, please show on the site plan and <br /> include horizontal dimensions,size and distance to property lines.Any structures larger than <br /> 200 square feet require a permit. Include this structure in your permit application if larger than <br /> 200 square feet. (IRC 105.2) <br /> RESPONSE: Existing accessory structures are added on the site plan. Covered patio is noted <br /> to be removed. .r <br /> COMMENT/CORRECTION: <br /> 3. Mechanical, Plumbing and Electrical permits are required. Please refer to the following website <br /> link for applications and/or checklists. Permit Applications,submittal checklists &fee schedules <br /> I Everett. WA-Official Website (everettwa.eov) <br /> RESPON'�.=: Differed submittal (not required per permit tech). <br /> Energy— Sheet A2 <br /> COMMENT/CORRECTION: <br /> 1. Please select either"Yes"or"No"on the WSEC form to the far left of the sheet. <br /> RESPONSE: Alteration worksheet table is revised. <br /> COMMENT/CORRECTION: <br /> 2. Please show ventilation exhaust systems in the plans for the toilet rooms, laundry and kitchen, <br /> and that the exhaust vents on the exterior are at least 3 feet away from any openings into the <br /> building. <br /> RESPONSE: There will be no changes to existing kitchen and toilet exhaust. New exhaust <br /> vent for laundry will exit on Bedroom C exterior wall. It is T-7"from the <br /> proposed new window. <br />