Laserfiche WebLink
COMMENT/CORRECTION: <br /> 6. Please clarify and confirm that walls removed to expand existing bathroom are not structural <br /> supporting the roof framing. <br /> RESPONSE: Initial investigation shows that the interior wall marked to be removed is non- <br /> bearing or non-structural wall. Further verification,and confirmation after stripping of wall is <br /> done by the contractor and noted on the plan. <br /> COMMENT/CORRECTION: <br /> 7. Provide a CO alarm in Bedroom Bon the first floor due to existing fireplace(IRC 315.2.1, IRC <br /> 315.5) <br /> RESPONSE: CO alarm is added in Bedroom B.', <br /> COMMENT/CORRECTION: <br /> 8. Confirm and indicate on the plans the presence of smoke and CO alarms in the existing <br /> bedrooms on the second floor(IRC 314.3) <br /> RESPONSE: Location of smoke and CO alarms are now shown in Existing Upper Floor Plan. <br /> COMMENT/CORRECTION: <br /> 9. Provide a note indicating interconnected smoke alarms (IRC 314.4) <br /> RESPONSE: This note was indicated on the plan. See smoke alarm note on sheet A6. <br /> All comments under Building use from Residential Building Review for B2401-012 were address <br /> through this response. <br /> Sincerel • - <br /> Y DESIGN LLC <br /> Applicant <br />