<br /> ELECTRICAL SYMBOL SCHEDULE
<br /> DESIGNATION SYMBOLS SINGLE LINE SYMBOLS POWER PLAN SYMBOLS FIRE ALARM SYMBOLS ABBREVIATIONS
<br /> E1 KEY NOTE TAG JUNCTION BOX [E] FIRE ALARM MANUAL PULL STATION A,AMP AMPERE IG ISOLATED GROUND.
<br /> AUTOMATIC TRANSFERSWITCH El PUSH BUTTON STATION F-O FIRE ALARM DOOR HOLDER AC ALTERNATING CURRENT HOA HAND-OFF-AUTO
<br /> DETAIL REFERENCE BUBBLE Project
<br /> A DETAIL NUMBER �T TRANSFORMER � AUDIBLE ALARM,(H=HIGH LEVEL),CHIME OR SPEAKER, ACT ABOVE COUNTER TOP HP HORSEPOWER KAISER PERMANENTE
<br /> H SEE SPECIFICATIONS
<br /> E1.1 SHEET BEARING DETAIL
<br /> © PUSH PLATE(FOR AUTOMATIC DOOR) XXCD VISUAL FIRE ALARM,(CD=CANDELLA) AIC AMPERE INTERRUPTING CAPACITY HPF HIGH POWER FACTOR EVERETT W AYF I N D I N G
<br /> T UTILITY TRANSFORMER pB PUSH BUTTON(FOR AUTOMATIC DOOR) Fr-( VISUAL FIRE ALARM,WALL MOUNTED AFF ABOVE FINISHED FLOOR LED LIGHT EMITTING DIODE
<br /> AUDIBLEIVISUAL COMBO FIRE ALARM,(H=HIGH LEVEL,CD=CANDELLA) AFG ABOVE FINISHED GRADE LLF LIGHT LOSS FACTOR
<br /> 1,1.�1J ZT7/480 SURFACE MOUNTED PANELBOARD CHIME OR SPEAKER,SEE SPECIFICATIONS 2929 PINE STREET
<br /> Y T� 277/480 FLUSH MOUNTED PANELBOARD
<br /> AUDIBLENISUAL COMBO FIRE ALARM,CEILING MOUNTED ATS AUTOMATIC TRANSFER SWITCH LRC LIGHTING RELAY CABINET EVERETT,WA 98201
<br /> CONDUIT SYMBOLS TRANSFORMER
<br /> 120/208 SURFACE MOUNTED PANELBOARD � FIRE ALARM SMOKE DETECTOR O AF FRAME RATING IN AMPERES MCB MAIN CIRCUIT BREAKER
<br /> Prepared For
<br /> T 1201208 FLUSH MOUNTED PANELBOARD ® FIREMEN PHONE I RESCUE ASSISTANCE O AS SWITCH RATING IN AMPERES MLO MAIN LUGS ONLY
<br /> CONDUIT INSTALLED CONCEALED ABOVE CEILINGS,IN WALLS IN FINISHED PANEL KAISER FOUNDATION
<br /> AREAS,OR EXPOSED IN UNFINISHED AREAS 1NL1' IM FIRE ALARM ADDRESSABLE INPUT MODULE AT TRIP RATING IN AMPERES MCA MINIMUM CIRCUIT AMPS
<br /> 225A PANELBOARD HEALTH PLAN, INC.
<br /> ---- CONDUIT INSTALLED BELOW FINISHED FLOOR OR BELOW GRADE MCB � FIRE ALARM ADDRESSABLE OUTPUT MODULE AWG AMERICAN WIRE GAUGE MOCP MAXIMUM OVER CURRENT PROTECTION
<br /> WIRING DEVICE SYMBOLS NATIONAL FACILITIES SERVICES POST
<br /> ----0 CONDUIT TURNING UP FACP FIRE ALARM CONTROL PANEL AV AUDIOVISUAL (N) NEW OFFICE BOX 12916 OAKLAND,CA 94604
<br /> 9 CONDUIT TURNING DOWN GENERATOR _e 120V,SINGLE RECEPTACLE OUTLET C CONDUIT N NEUTRAL
<br /> 120V,SPECIAL MOUNTING HEIGHT SINGLE RECEPTACLE OUTLET CFOI CONTRACTOR FURNISHED OWNER INC NORMALLY CLOSED
<br /> CONDUIT STUBBED OUT WITH BUSHING �. TECHNOLOGY SYMBOLS CONTRACTOR
<br /> 0 o STATIONARY CIRCUIT BREAKER;RATING AS SHOWN ON PLANS NATIONAL ELECTRICAL ,
<br /> CONDUIT STUBBED OUT AND CAPPED �® _@ 120V,DUPLEX RECEPTACLE OUTLET CKT CIRCUIT NEMA MANUFACTURER'S ASSOCIATION
<br /> � SWITCH AND FUSE;RATING AS SHOWN ON PLANS
<br /> FLEXIBLE CONDUIT WITH SINGLE POINT OF CONNECTION AT --0'-0—/L SWITCH AND FUSE;RATING AS SHOWN ON PLANS =10 120V,SPECIAL MOUNTING HEIGHT DUPLEX RECEPTACLE OUTLET VOICEIDATA OUTLET CLG CEILING NILNIGHT LIGHT
<br /> v, ELECTRICAL EQUIPMENT =0 120V,CONTROLLED DUPLEX RECEPTACLE OUTLET CL CONNECTED LOAD NO NORMALLY OPEN
<br /> INLINE METER QN—AV-AUDIOVISUAL
<br /> TV TELEVISION CCT CORRELATED COLOR TEMPERATURE NTS NOT TO SCALE
<br /> —C GROUNDING CONDUCTOR 120V,5MA GFCI DUPLEX RECEPTACLE OUTLET W-WALL TELEPHONE OUTLET
<br /> �O METER AND CTS � 120V,SPECIAL MOUNTING HEIGHT 5MA GFCI DUPLEX RECEPTACLE OUTLET WAP-WIRELESS ACCESS POINT CRI COLOR RENDERING INDEX OFCI CONER TRACTOR
<br /> FURNISHED Helmuth,Obata&Kassabaum,Inc.
<br /> CONDUITHOATED, ROUTE TOATECO PANELBOARD,DUCTCABINET,ORTERMINAL CONTRACTOR INSTALLED 1200FifthAvenue,Suite500,Seattle,
<br /> BOARD INDICATED,AND TERMINATE CONDUCTORS TO CIRCUIT OVER Q- —ABOVE COUNTER,VOICEIDATA OUTLET
<br /> CURRENT PROTECTIVE DEVICE 120V,CONTROLLED 5MA GFCI DUPLEX RECEPTACLE OUTLET (D) DEMOLISH EXISTING OC OVER CURRENT WA 98101 USA
<br /> GROUND ® —CEILING/FLOOR,VOICEIDATA OUTLET t+1 206 834 3110
<br /> - 120V,DOUBLE DUPLEX RECEPTACLE OUTLET DF DEMAND FACTOR PB PULL BOX
<br /> 120V,SPECIAL MOUNTING HEIGHT DOUBLE DUPLEX RECEPTACLE OUTLET CR —CR-CARD READER DL DESIGN LOAD fd PH PHASE
<br /> KP-KEY PAD
<br /> 120V,CONTROLLED DOUBLE DUPLEX RECEPTACLE OUTLET ES-ELECTRIC STRIKE DC DIRECT CURRENT PNL PANEL um»oa�nlons:�lanaalp,op� ,g�re.:�d*M
<br /> SINGLE LINE DIAGRAM LEGEND InAssociationvan
<br /> 4 120V,SMA GFCI DOUBLE DUPLEX RECEPTACLE OUTLET CABLE TRAY DPDT DOUBLE POLE,DOUBLE THROW PVC POLYVINYL CHLORIDE CONDUIT
<br /> (E)-EXISTING TO REMAIN 40 120V,SPECIAL MOUNTING HEIGHT 5MA GFCI DOUBLE DUPLEX RECEPTACLE NOTES: DPST DOUBLE POLE SINGLE THROW P POLE Mazzetti
<br /> A. THE ABOVE SYMBOLS DENOTE CONDUIT AND BACKBOX LOCATION. Electrical&Low Voltage Engineering
<br /> D-DEMOLITION WORK 120V,CONTROLLED 5MA GFCI DOUBLE DUPLEX RECEPTACLE B. COORDINATE EXACT LOCATIONS AND FINAL MOUNTING HEIGHTS OF ALL DIST DISTRIBUTION PWR POWER 20134th Ave Suite 200
<br /> ------ () TECHNOLOGY DEVICES WITH ARCHITECTURAL ELEVATIONS, Seattle,WA 98121
<br /> (N)-NEW WORK -@ SPECIAL PURPOSE RECEPTACLE,VOLTAGE AND NEMA AS NOTED C. "INDICATES THE NUMBER OF VOICE/DATA CABLES IN THE CONDUITBACKBOX AND (E) EXISTING TO REMAIN (R) RELOCATE EXISTING
<br /> THE NUMBER OF VOICE/DATA JACKS ON THE FACEPLATE. SKA Design
<br /> EC EMPTY CONDUIT RCP REFLECTED CEILING PLAN Environmental Graphic Design
<br /> (F)FUTURE WORK 472 E.Colorado Boulevard
<br /> 100NG FEEDER TAG ELEC ELECTRICAL RSC RIGID STEEL CONDUIT Pasadena,CA 91101
<br /> WIRING DEVICE DESIGNATIONS ELECTRICAL DRAWING INDEX ELEV ELEVATOR SPOT SINGLE POLE,DOUBLE THROW
<br /> E001 ELECTRICAL COVER SHEET E,EM EMERGENCY SPST SINGLE POLE,SINGLE THROW
<br /> �22 CIRCUIT NUMBER(WHERE SHOWN) E020 ELECTRICAL SPECIFICATIONS
<br /> TV E103 DEMOLITION LEVEL 3-NORTH BUILDING-ELECTRICAL EMT ELECTRO METALLIC TUBING SWBD SWITCHBOARD
<br /> ATV-TELEVISION RECEPTACLE E203 LEVEL 3-NORTH BUILDING-ELECTRICAL EMS EMERGENCY MANAGEMENT SYSTEM SWGR SWITCH GEAR
<br /> WP-WEATHERPROOF,IN-SERVICE TYPE COVER E204 LEVEL 4-NORTH BUILDING-ELECTRICAL
<br /> USB-USB RECEPTACLE FA FIRE ALARM TB,TTB TERMINAL BACKBOARD
<br /> NOTES: FSD FIRE SMOKE DAMPER TC TERMINAL CABINET
<br /> A. ALL RECEPTACLES IN OFFICES,CORRIDORS,AND WAITING ROOMS SHALL BE Key Plan
<br /> TAMPER-RESISTANT. FVNR FULL-VOLTAGE,NON-REVERSING TEL TELEPHONE
<br /> B. ALL RECEPTACLES AT PATIENT BED LOCATIONS SHALL BE HOSPITAL-GRADE.
<br /> C. ALL NONLOCKING-TYPE RECEPTACLES IN OPERATING ROOMS SHALL BE HOSPITAL- FVR FULL-VOLTAGE,REVERSING V VOLT
<br /> GRADE.
<br /> FLA FULL LOAD AMPS(NAME PLATE) VD VOLTAGE DROP
<br /> FLC FULL LOAD CURRENT(NEC) VFD VARIABLE FREQUENCY DRIVE
<br /> (F) FUTURE VA VOLT AMPERES
<br /> GROUND FAULT
<br /> GFCI CIRCUIT INTERRUPTING W WATT
<br /> G,GND GROUND W WIRE
<br /> GEN GENERATOR XFMR TRANSFORMER
<br /> Prolesei,aal Seale
<br /> C C.SW
<br /> ELECTRICAL GENERAL NOTES A@y2��a
<br /> c�
<br /> ra o
<br /> A. WHERE GROUNDED CONDUCTORS OF DIFFERENT SYSTEMS ARE INSTALLED IN THE SAME RACEWAY,
<br /> CABLE,BOX,AUXILIARY GUTTER,OR OTHER TYPE OF ENCLOSURE,EACH GROUNDED CONDUCTOR 4 4 W�
<br /> SHALL BE IDENTIFIED BY SYSTEM PER NEC ARTICLE 200.6(D).MEANS OF IDENTIFICATION SHALL BE
<br /> PERMANENTLY POSTED AT EACH BRANCH CIRCUIT PANELBOARD.
<br /> B. PER NEC ART 210.5(C),UNGROUNDED CONDUCTORS OF MORE THAN ONE NOMINAL VOLTAGE VONAL
<br /> SYSTEM SHALL BE IDENTIFIED BY SYSTEM.PROVIDE MEANS OF IDENTIFICATION AS REQUIRED PER
<br /> THIS ARTICLE.
<br /> C. PER NEC ART 215.12,FEEDER IDENTIFICATION IS REQUIRED WHEN MORE THAN ONE NOMINAL No. Desmptian Date
<br /> VOLTAGE SYSTEM EXISTS.PROVIDE MEANS OF IDENTIFICATION AS REQUIRED PER THIS ARTICLE. 1 Building Pamrlt 04/2312025
<br /> D. VERIFY FINAL PLACEMENT AND CONNECTION REQUIREMENTS PRIOR TO ROUGHING IN EQUIPMENT
<br /> UTILITIES.
<br /> E. FINAL ACCEPTANCE OF WORK IN PLACE SHALL BE SUBJECT TO APPROVAL BY OWNER'S
<br /> REPRESENTATIVE.INSTALLATION APPROVAL SHALL BE BASED ON APPROVED SUBMITTAL,SHOP
<br /> DRAWINGS AND LOCAL INSPECTIONS.
<br /> F. SUBMIT RED-LINE RECORD DRAWINGS WITHIN TWO(2)WORK WEEKS OF DATE OF NOTIFICATION OF
<br /> FINAL APPROVAL.
<br /> G. ALL WORK SHOWN ON DRAWINGS IS IN PART SCHEMATIC,INTENDED TO CONVEY SCOPE OF WORK
<br /> AND GENERAL LAYOUT.VERIFY ALL EXISTING CONDITIONS AND MAKE ADJUSTMENTS AS REQUIRED.
<br /> ELECTRICAL DRAWINGS ARE LARGELY DIAGRAMMATIC AND,THEREFORE,REPRESENT
<br /> INSTALLATION INTENT AND GUIDELINES;IT IS THE CONTRACTOR'S RESPONSIBILITY TO COVER ALL
<br /> CONDITIONS ON THEIR PREPARED SHOP DRAWINGS.
<br /> H. PROVIDE UP-TO-DATE,ACCURATE,AND LEGIBLE CIRCUIT DIRECTORY WHICH APPLIES TO
<br /> PANELBOARDS AS REQUIRED BY NEC ART.408.4 DIRECTORY SHALL BE LOCATED ON THE FACE OR
<br /> ON THE DOOR OF EACH PANELBOARD.WITHIN EACH PANELBOARD PRIOR TO FINAL ACCEPTANCE OF
<br /> WORK IN PLACE.
<br /> I. LABEL ALL WIRING DEVICES WITH SOURCE PANELBOARD AND CIRCUIT NUMBER ON COVER PLATE.
<br /> SEE SPECIFICATIONS.
<br /> J. ALL INTERIOR OUTLET,JUNCTION AND PULL BOXES SHALL BE METALLIC,SIZED PER CODE FOR THE
<br /> NUMBER OF CONDUCTORS THEREIN.
<br /> K. ALL ELECTRICAL RACEWAYS SHALL BE CONCEALED IN THE WALLS AND ABOVE SUSPENDED CEILING
<br /> UNLESS OTHERWISE NOTED.
<br /> L. ALL CONDUCTORS SHALL BE#12 AWG MINIMUM TYPE THHN/THWN UNLESS OTHERWISE NOTED.
<br /> M. IN THE EVENT OF ANY INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS ANDIOR THE
<br /> SPECIFICATIONS,THE ONE WHICH PROVIDED THE MOST COMPLETE WORK OR HIGHER STANDARD
<br /> SHALL PREVAIL.
<br /> N. SUPPLY AND INSTALL ALL REQUIRED SUPPORTS AND BRACING OF EQUIPMENT AND CONDUITS FOR
<br /> PROPER EQUIPMENT INSTALLATIONS AND CODE COMPLIANCE.
<br /> 0. ALL EXPOSED CONDUITS SHALL BE INSTALLED AT RIGHT ANGLE TO ROOM OR STRUCTURE.
<br /> EXPOSED CONDUITS SHALL BE SUPPORTED FROM BUILDING STRUCTURE USING APPROVED PIPE
<br /> HANGERS.
<br /> P. ALL CONDUITS SHALL BE SIZED AS PER NEC UNLESS LARGER SIZES ARE NOTED ON THE DRAWINGS.
<br /> Q. ALL CUTTING,PATCHING AND PAINTING REQUIRED FOR THE CONCEALED INSTALLATION OF
<br /> CONDUITS SHALL BE PROVIDED BY THE CONTRACTOR.DO NOT CUT OR DRILL STRUCTURAL
<br /> MEMBERS WITHOUT WRITTEN APPROVAL FROM STRUCTURAL ENGINEER.ALL CUTTING AND
<br /> PATCHING SHALL BE NEAT,AND PATCHING SHALL MATCH ADJACENT SURFACE AS TO TEXTURE AND
<br /> FINISH.
<br /> R. ALL PENETRATIONS THROUGH FIRE RATED WALLS,FLOORS OR CEILINGS SHALL BE SEALED IN
<br /> ACCORDANCE WITH A UL APPROVED SYSTEM THAT MAINTAINS THE INTEGRITY OF THE EXISTING
<br /> FIRE RATING.PROVIDE AN ENCLOSURE OF EQUAL FIRE RESISTANT RATING AROUND ALL FIXTURES
<br /> AND EQUIPMENT INSTALLED IN OR PENETRATING FIRE RATED SEPARATIONS.
<br /> S. ALL DATA CABLING TO BE PROVIDED BY THE OWNERS'S IT VENDOR.COORDINATE ROUGH-IN WORK
<br /> WITH OWNER'S IT VENDOR.
<br /> Project No: 25.05007.00
<br /> Sheet TMle
<br /> ELECTRICAL COVER
<br /> SHEET
<br /> onemm l:ae„ea m cn.mwnecn aml:a,e.-lam.
<br /> Shoat Number
<br /> City of Everett Permit Services E 0 01
<br /> EVERETT Reviewed for Permit 06/30/2025