<br /> ELECTRICAL SPECIFICATIONS PERMANEWEe
<br /> 260500 COMMON WORK RESULTS FOR ELECTRICAL 260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
<br /> A. SCOPE OF WORK A. RACEWAYS
<br /> 1. Comply with the General Conditions of this contract.The requirements of this specification are in addition to the 1. Electrical metallic tubing(EMT):Zinc-coated steel.
<br /> requirements of the General Conditions.
<br /> 2. Unless otherwise noted,provide demolition of existing power receptacles,light fixtures,raceways,wiring,voice/data outlets B. FITTINGS
<br /> and voice/data cabling. 1. Electrical Metallic Tubing(EMT):Steel set-screw type.Fittings 2"and larger shall be steel and may be setscrew type
<br /> 3. Provide all labor and material necessary to accomplish the work specified herein and as shown on the drawings. containing dual setscrews on each side of coupling.
<br /> 4. Coordinate work with all other trades. 2. Conduit Straps:Heavy duty,two-hole pressed steel.
<br /> S. Remove all waste and rubbish from the site on a daily basis. Project
<br /> C. 1. InteLET ANDDEVICES h-Mounaoxes. KAISER PERMANENTE
<br /> B. WARRANTY:Workmanship and materials shall be guaranteed for a period of one year from the date of foal acceptance by the 1. Interior Flush-Mounted:Same as above except provide plaster ring extension to finished surface.
<br /> Omer.Provide additional warranty for voice/data system as noted elsewhere.
<br /> D. JUNCTION AND PULL Boxes: EVERETT WAYFINDING
<br /> C. REGULATIONS 1. Interior:steel,screw cover,code gauge and size.Large junction and pull boxes shall be fabricated sheet steel with baked
<br /> 1. Electrical work shall comply with the following codes as presently applicable: enamel finish and return flange with screw retained cover.
<br /> a. National Electrical Code(NEC) 2929 PINE STREET
<br /> b. washmgton State Nonresidential Energy Code(NREC)with Everett amendments E. EXECUTION
<br /> c. Washington Administrative Code(WAC)with Everett amendments 1. General: EVERETT,WA 98201
<br /> d. Local City of Everett and State codes and regulations a. Coordination:The Contractor shall review all drawings,details and elevations prior to rough-in.Where equipment is
<br /> 2. Permits:Obtain and pay for all required permits. fumished by others,the Contractor shall ascertain the proper voltage,load and connection requirements prior to
<br /> 3. Safety Measures:Provide a safe environment to protect employees and all others from injury.Comply with"Safety and rough-in. Prepared For
<br /> Health Regulations for Construction,"Volume 36,No.75,Part 11,of the Federal Register by the U.S.Department of Labor. b. Materials:All materials of a specific type shall be provided by the same manufacturer throughout the project.
<br /> D. SUBMITTAL AND SHOP DRAWINGS:Prior to installation,submit catalog data for wiring devices in electronic PDF formal. 2. Raceway Types:Install raceway types and sizes as listed below: KAISER FOUNDATION
<br /> a. Electrical Metallic Tubing(EMT):NI areas other than above.May be used for feeders with integral green ground HEALTH PLAN, INC.
<br /> E. OPERATIONS AND MAINTENANCE MANUALS:Provide maintenance and operations data for all electrical equipment and conductor.
<br /> signal and communications systems in electronic PDF format. b. Flexible Metallic Conduit:Recessed fixture connections,interior concealed equipment connections,expansion joints NATIONAL FACILITIES SERVICES POST
<br /> and sound control.Not to be used exposed installations within the building.
<br /> F. RECORD DRAWINGS:Corrections and changes made during the progress of the work shall be neatly recorded as actually c. Minimum raceway size shall be 314 inch. OFFICE BOX 12916 OAKLAND,CA 94604
<br /> installed for as-built records.Submit to the Architect upon project completion.
<br /> 3. Raceway Installation:
<br /> G. CERTIFICATES OF INSPECTION:Submit signed-off permits from the Code Enforcing Agencies to the Owner upon project a. Concealment:All raceways shall be concealed in finished areas.Where existing wall surfaces are inaccessible,
<br /> completion. surface metal raceways for these exceptions may be provided when approved.
<br /> b. Exposed Raceways:Install exposed raceways as high as possible,above ductwork,parallel or at right angles to
<br /> H. PRODUCT LISTING OR LABELING:All electrical equipment shall be listed and labeled by Underwrites Laboratories,Inc. building lines.
<br /> c. Expansion and Earthquake Joints:Raceways shall not be installed in concrete slab or wall construction when passing
<br /> I. MATERIAL AND EQUIPMENT:NI materials and equipment shall be new unless noted otherwise.Protect all materials and through an expansion or earthquake joint.Raceways shall be installed in furred or suspended ceiling spaces with a
<br /> equipment from damage or corrosion. minimum of 24 inches of flexible conduit crossing the expansion or earthquake joints.
<br /> d. Routing:All raceways shall be Installed parallel or at right angles to the building construction unless prohibited by a
<br /> J. CUTTING AND PATCHING:Provide all required rutting and patching for the electrical work. physical obstruction.
<br /> e. Raceway Supports:Raceways shall be supported with heavy-duty,one-hole,pressed steel straps on interior
<br /> K. EXISTING CONDITIONS surfaces.Support pendant-mounted raceways on 3/8-inch rod with pear-shaped hanger or trapeze-type hanger with Hellmuth,Obata&Kassabaum,Inc.
<br /> 1. General:Specific scope of demolition wore and operating conditions to be encountered shall be verified by on-slte review 3/8-inch rod(minimum)and 1-51&inch square preformed channel and pipe clamps.Parallel,surface-mounted 1200 Fifth Avenue,Suite 500,Seattle,
<br /> prior to submitting bid.Demolition work in general is noted or shown on the documents based upon available"drawings of raceways shall be supported from 1-5/8-inch square preformed channel and pipe clamps.
<br /> record"and may not show the actual conditions as they presently exist. f. Independent Support:Conduits shall not be supported from the ceiling suspension system,ducts,pipes or other WA 98101 USA
<br /> 2. OwnenRetained Equipment:The Owner may wish to retain certain specific Items scheduled for demolition.The systems foreign to the electrical installation.The entire electrical installation shall be kept independent from any other t+1 206 834 3110
<br /> Contractor shall carefully remove these items,provide protection and packaging as may be required to protect the trade.
<br /> equipment and turnover said equipment to the Owner at a place designated on the jobsite.Any equipment that the Owner g. Pull boxes with Govers:Shall be provided as shown on the drawings or as required by Code.All pull boxes shall be
<br /> does not desire to retain shall become the property of the Contractor and be removed from the site. located so as to be accessible..
<br /> 3. Unused Conduit and Wiring:All unused conductors resulting from this project shall be removed.All unused conduit shall h. Empty Raceways:Provide a nylon pull string in all empty raceways. a rer.oa"a�ma imeren"a praoer, re 1®zoza
<br /> be removed except where located in or above existing construction which is not being altered and would require removal In Association with
<br /> and replacement of the existing construction. 4. Boxes and Fittings:
<br /> 4. Existing Tal/Dam Cables and outlets:Provide demolifion of existing voice data outlets except where otherwise shown. a. General:Boxes shall be supported securely and independently.Mount boxes on building surfaces or support with
<br /> Verify extent of work prior to submitting bid.Property support and maintain in service any remaining voiceldata system trapeze hanger as described in Raceway Installation.Junction boxes shall not be used unless the number of bends,
<br /> wiring installed exposed above suspended ceilings within the project area.Secure cables to structure above using tie pulling length,or circuit requirements necessitates their installation.Junction or pull box openings must be Mazzelti
<br /> wraps secured to independent tie wires suspended from structure above. accessible. Electrical&Low Voltage Engineering
<br /> S. Existing Raceways:Property support all existing raceways above suspended ceilings where work is taking place.Verify b. Sound Control:Where boxes are mounted in a common wall,they shall wherever possible,be offset horizontally co 20134th Ave Suite 200
<br /> extent of work prior to submitting bid. that they are not mounted back-to-back.Connect offset boxes with flexible conduit not to exceed 18 inches In length. Seattle,WA 98121
<br /> L. DEMOLITION SKA Design
<br /> 1. Coordinate scope of electrical demolition with architectural drawings. Environmental Graphic Design
<br /> 2. Unless otherwise noted,remove all systems,devices,outlets,switches,pull boxes,junction boxes,etc.As required to 472 E.Colorado Boulevard
<br /> completely take out the electrical items within scope or shown to be removed.Disconnect and remove all electrical Pasadena,CA 91101
<br /> provisions to equipment being removed.Remove all wiring,conduit,raceways,outlet boxes,etc.Supporting or serving the 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
<br /> items removed.
<br /> 3. Remove branch circuit wiring and conductors back to panelboard or to last outlet or junction box that will remain in service. A. GENERAL:Label all junction boxes,terminal cabinets,etc.,with the circuit number or low-voltage system contained within.
<br /> Where complete circuits are demolished,remove wiring and raceway back to the branch circuit panelboard.Revise the
<br /> penelboard schedule to indicate that the demolished circuits breaker is°spare". B. EQUIPMENT NAMEPLATES:Shall be engraved in 1/16 inch thick phenolic letters a minimum of 3/16 inch high.Coloring shall
<br /> 4. Remove all conductors,wiring,and conduit(where present)including,but not limited to,power and voiceldata in demolition be white letters on black background for normal equipment and white letters on red background for emergency equipment.
<br /> area that are no longer in use or already abandoned.No conductors or cables shall be abandoned in place.Remove
<br /> existing wiring and conduit back to source. C. WIRING DEVICE FACEPLATES:Label all receptacles with panel and circuit number.
<br /> 5. Concealed conduit that cannot be removed due to inaccessibility may be abandoned.Conductors shall be removed and
<br /> conduit cut flush with surface
<br /> 6. Outlet boxes that cannot be removed,due to flush mounting in partitions not being removed shall be provided with a blank 262726 WIRING DEVICES
<br /> device plate unless noted to be filled and finished flush with wall.
<br /> 7. Maintain continuity of all feeders,systems control wiring,miscellaneous auxiliary systems,etc.That pass through the A. WIRING DEVICES
<br /> Key Plan
<br /> renovated space at all times.Any damage,disruption or disconnection to these systems shall be repaired immediately, 1. Approved Manufacturers:Cooper,Hubbell,P&S or Leviton.All part numbers refer to Hubbell.
<br /> replaced andlor re-routed as required to maintain continuity of the systems.Provide wiring and mceway necessary to 2. Receptacle Color:White for normal power,red for emergency power.
<br /> maintain continuity of electrical service to existing outlets that remain when power to such outlets is interrupted because of 3. Receptacle Orientation:
<br /> demolltion of other devices on the same circuit. a. Install receptacles vertically.
<br /> 8. Seal openings in fire rated partitions created by the removal of electrical equipment.Maintain fire rating of wall or partition. b. Install receptacles with the ground pin up.
<br /> 9. Symbols shown are typical and locations are approximate and they are not Intended to limit the amount of demolition. B. RECEPTACLES
<br /> Coordinate with existing conditions and these notes and remove all applicable systems and components conflicting with 1. Duplex Receptacles:Specification-grade,20-ampere,125-volt,grounded type,HBL5352 series.
<br /> finished design Intent. 2. Double Duplex Receptacles:Specification-grade,20-ampere,125-volt,grounded type,HBL5352 series.
<br /> 3. Ground Fault Interruption Receptacles:Specification-grade,20-ampere,125-volt,Class A,5-milliampere sensitivity,
<br /> M. ANCHORAGE AND BRACING:Provide complete seismic anchorage and bracing for the lateral and vertical support of conduit GF5352 series.
<br /> as required by the International Building Code. 4. Weather/TampenResistant Receptacles:Specification-grade,20-ampere,125-volt,grounded type,GFR5362TR series.
<br /> N. FIRESTOPPING:Provide fire stopping for all penetrations through rated walls,ceilings,and floors. D. DEVICE PLATES:Thermoplastic,P&SlSiems or approved equal.
<br /> 1. General:Install devices level,plumb and square with building lines.
<br /> 0. PAINTING:Paint all exposed raceways,except SURFACE MOUNTED RACEWAY(SMR),in finished areas to match adjacent
<br /> surfaces. E. RECEPTACLE MOUNTING HEIGHT:+18"to the centedine of the box unless otherwise noted.
<br /> Professional seals
<br /> G. SELECTION OF RECEPTACLES
<br /> 1. Unless more stringent requirements are specified in Contract Documents,comply with NFPA 70 for selection of C•S
<br /> 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES receptacles. 1C pits$'gyp,
<br /> 2. Indoors:
<br /> A. WIRE AND CABLE: a. Within 6'of sinks:GFCI Receptacles F ea
<br /> b. Offices,couldors,waiting rooms and similar in clinics,medical and dental offices,and outpatient facilities:Tamper- y _
<br /> 1. Branch Circuits:Type THHN or THWN,600 volt-insulation,stranded or solid copper conductor. resistant Receptacles.
<br /> Minimum conductor size: c. Pediatric Locations:Tamper-resistant Receptacles.
<br /> a. Neutral:#12AWG
<br /> b. Ground:#12 AWG 270500 COMMON WORK RESULTS FOR COMMUNICATIONS ) C'
<br /> c. Phase conductors(more than six in a raceway):#10 AWG ONAL
<br /> d. Phase conductors(six or less in a raceway):#12 AWG A. Provide conduit,backbox,and pullstring for communications and data devices shown on the plans.Cabling and faceplates shall
<br /> 1. Color Coding Requirements:1201208 Volt,lPhase,4 be provided by Owner's IT vendor.Wire Systems Na. Description Datea a. Phase A:Black B. All signal and communications cabling shall be plenum rated.Cabling shall be run open above the ceiling via junction-hooks in 1 Building Pemnit 04/2312025
<br /> b. Phase B:Red
<br /> c. Phase C:Blue accessible locations.
<br /> d. Neutral:White C. Provide metallic raceways for cables installed in walls,above inaccessible ceilings,exposed or where subject to physical
<br /> e. Ground:Green damage.Raceway fill shall not exceed 40 percent.Raceway size shall be 1 inch minimum.
<br /> f. Travelers:Yellow(For 3-And 4-Way Switching)
<br /> g. Controls:Black With W he Numbers On Each Conductor D. Provide STI EZ-PATH or equivalent fire rated pathway where cabling pathways cross fire-rated walls.
<br /> 2. Splices and Terminations:Lighting and receptacle branch circuit conductors up to No.10 AWG shall be spliced with Wing E. Equipment and wiring shown on the drawings and speed herein are to assist the contractor in preparing their bid.Additional
<br /> Nut type connectors.
<br /> equipment and wiring maybe required.Contractor shall provide all equipment and wiring as determined by the equipment
<br /> 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS manufacturer
<br /> A. GENERAL:Provide through the entire electrical system.A separate green equipment grounding conductor shall be provided in 283111 DIGITAL,ADDRESSABLE FIRE-ALARM SYSTEMS
<br /> all lighting and power raceways.
<br /> A. The existing fire alarm system must remain in operation at all times.Provide a'Yre watch'if the existing fire alarm must be
<br /> B. RECEPTACLE GROUNDING:Connect the ground terminal of all receptacles by utilizing a separate grounding conductor taken out of service.
<br /> between the receptacle grounding screw and the ground conductor provided in the branch circuit.Integral mounting straps
<br /> within the receptacle connected to the device mounting straps are not approved as a grounding method.