Permit Number: M2501-088 <br /> February 27, 2025 <br /> f. Please provide information demonstrating compliance with duct construction requirements <br /> of IMC 510.8 and Table 510.8. <br /> g. Ducts are required to have supports per IMC 510.9. See comment#1g. below. <br /> h. Please remove or differentiate from the drawings or indicate "NOT USED"for fume hood <br /> materials not meeting requirements of IMC 510. <br /> i. Please coordinate with the Fire Marshal's office regarding the submission of the "Hazardous <br /> Materials Management Plan." See IFC 5001.5.1. <br /> j. Please update your"Chemicals Exhausted" schedule to include all of the information <br /> required per IFC 5001.5.2. <br /> 2. ERV SPLIT-SYSTEM <br /> a. Heating/cooling calculations seem to indicate a conversion from semi-heated to heated <br /> space. This requires thermal envelope upgrades. Please address. See WSEC-0505.2. <br /> b. Heating cooling calculation do not include existing skylight. Please address. <br /> c. Please clarify outside air provisions comply with IMC 403.3 and WSEC-C403.2.2.1. <br /> d. Please address commissioning requirements. WSEC-C408. <br /> Please reach out with any questions or clarification regarding this comment letter via the contact <br /> information listed in the reviewer's signature lines below. <br /> Sincerely, <br /> — Scott Schreffler, Registered Architect <br /> Senior Building Plans Examiner I Permit Services <br /> 425.257.7287 1 3200 Cedar Street, 2nd Floor, Everett, WA 98201 <br /> EVERETT Phone Hours: M-F: 8:30 a.m.—12 p.m. & 1 p.m.—3 p.m. <br /> everettwa.gov/permits I onlinepermits.everettwa.gov <br /> 3200 Cedar Street © 425.257.8810 O permitservices@everettwa.gov <br /> Everett, WA 98201 8am-12pm, 1pm-3pm everettwa.gov/permits <br /> Page 2 of 2 <br />