Laserfiche WebLink
ei0at <br /> BUILDING TECHNICAL SERVICES <br /> Fan Unit <br /> PROJECT: Zap Energy Lithium DATE: 6/26/2025 <br /> LOCATION: Everett,WA CONTACT: Darrin Williams <br /> PROJECT#: 70-25-28392 <br /> SYSTEM/UNIT: EF-1/Machine Shop Hood Tested By: Darrin Williams <br /> AREA: EF-1 Date: 6/26/2025 <br /> Unit Data Final Data <br /> Fume Hood MFG LOC Scientific Inc. Minimum FPM 85 FPM <br /> Height of Sash Opening 18.00 in. Maximum FPM 108 FPM <br /> Width of Sash Opening 63.00 in. Average FPM 98 FPM <br /> Total Sash Opening 7.88 sq.ft. Total CFM 772 CFM <br /> Sash Position At Test 18.00 in. <br /> Number Of Rows 1 <br /> Readings Per Row 4 <br /> Velocity Data Points <br /> c c c c <br /> Row 1 1C2 0 0 0 <br /> Velocity <br />