elocit <br /> BUILDING TECHNICAL. SERVICES <br /> Energy Recovery Unit <br /> PROJECT: Zap Energy Lithium DATE: 6/26/2025 <br /> LOCATION: Everett,WA CONTACT: Darrin Williams <br /> PROJECT#: 70-25-28392 <br /> SYSTEM/UNIT: ERV-101 Tested By: Darrin Williams <br /> AREA: Machine Shop Date: 6/26/2025 <br /> Unit Data <br /> Unit Manufacturer Lossnay <br /> Unit Model Number LGH-F300RVX2-E <br /> Unit Serial Number 24070061546174 <br /> Unit Type Plate Exchanger <br /> Unit Condition New <br /> ERV-101/EF Filter <br /> Filter Manufacturer Mitsubishi <br /> Filter Type Washable Media <br /> Filter Qty-S1 1 <br /> Filter Size-S1 8x40x1 <br /> Test Data <br /> S/Fan Design Airflow 115 CFM <br /> S/Fan Actual Airflow 125 CFM <br /> S/Fan Design O/A 115 CFM <br /> S/Fan Actual O/A 125 CFM <br /> E/Fan Design Airflow 115 CFM <br /> E/Fan Actual Airflow 125 CFM <br /> E/Fan Design R/A 115 CFM <br /> E/Fan Actual R/A 125 CFM <br /> Notes: <br /> ERV-101 6/26/2025 Darrin Williams Fan set for medium-low speed at the control panel to achieve <br /> design airflow. <br /> ERV-101 Supply Outlet Summary <br /> System/Unit Area Served Design Final %Final Outlet Size LxW/ Instrument AK Factor <br /> Airflow Airflow Diff. Type D <br /> Outlet-01 Machine Shop 1 115 125 109 DG2 8 Flowhood 1.00 <br /> Totals: 1 115 125 109 - - - - <br /> ERV-101 Exhaust Inlet Summary <br /> System/Unit Area Served Design Prelim %Prelim Final %Final Inlet Type Size LxW/ Instrument AK Factor <br /> Airflow Airflow Diff. Airflow Diff. D <br /> Inlet-01 Machine Shop 115 245 213 125 109 EG 8 Flowhood 1.00 <br /> Totals: 115 245 213 125 1 109 - <br /> Velocity <br />