Laserfiche WebLink
fapdol <br /> Resources <br /> 5891 Mullen Road SE • Lacey, WA 98503 <br /> (360) 493-1830 - - <br /> Fax: (360) 923-1841 <br /> Email: hcaulfield@capitolpump.com <br /> DIESEL <br /> FIRE PUMPS <br /> (EVNPI) <br /> Address: 9801 271h Ave West, Everett WA <br /> Occupied as- Building 40-29 Boeing, Everett <br /> Inspected by: Kyle Nunley Certificate#N-08336 <br /> Date of Inspection: 11/07/2023 Type of Test: Quarterly❑ Annual <br /> Fire Dept. Official Contacted: <br /> Pump Model: 6AEF14G Impeller: 13.38 Serial No.: 9927069366-10-A <br /> Pump Design Conditions: 1500 GPM @ 75 PSI <br /> Controller Model: FD120 Serial No: 16BY816D <br /> Engine Model: JU4H UFADSG Serial No.: PE404SL247444 <br /> Block Heater Operational: Yes ® No❑ <br /> Batteries: 13.3/13.3 Engine Hours: 306.6 <br /> Controller Voltage: 240 volts Interrupting Capacity: N/A amps <br /> Fire Pump: <br /> Cut-in Pressure: 140 psi Cut-out Pressure: Manual psi <br /> Timer set at: NIA min. <br /> Jockey Pump: <br /> Cut-in Pressure: 150 psi Cut-out Pressure: 160 psi <br /> Timer set at: N/A min. <br /> Pump starts on water from roof? Yes❑ No ❑ N/A <br /> Pump starts on pressure drop? Yes® No❑ N/A <br /> Pump Motor: Diesel ® Electric ❑ Other <br /> Routine maintenance is performed and records are kept? Yes No ❑ <br /> CPR -Care- Pride -Response- Pumps -Valves - Controls -Sales- Service •Rental -Repair•Testing <br /> _ Y <br />