Laserfiche WebLink
Static city water pressure 69 psi <br /> Churn suction pressure 66 psi Churn discharge pressure 149 psi <br /> Was 300 GP1v1 flow conducted? Yes Z No❑ <br /> Hose size: 2.5 inch Tip size: 2.5 inch Hose length: 25 ft <br /> Pitot reading: 9/9/9 GPM: 1.524 <br /> Was pump run for 10 minutes flowing? Yes No ❑ <br /> Were all fire pumps tested? Yes Z No ❑ <br /> Flow Chart <br /> NO.&SIZE OF PUMP PRES911RE PrrOT FLOW' RPM VOLTS AMPS CONIMENTs <br /> NOZZEIS PRESSURE <br /> DISCHG. su CT. I NET <br /> f Churn 1 149 66 83 - 0 1770 <br /> 3—2 '/:"H.11 , 137 64 73 9/9/9 1524 1769 <br /> 4—2 'l:"RM I 111 59 52 12/12/11/11 2246 1770 <br /> Problems found: <br /> Corrections made: <br /> Date corrections made: By: <br /> THIS IS TO CERTIFY THAT THE FIRE PUMP SYSTEM HAS BEEN PROPERLY <br /> "TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED <br /> IN THIS REPORT; IS CONSISTAIti'T WITH MANUFACTURER'S REQUIREMENTS: <br /> AND ALL CORRECTIONS ARE TO BE MADE BY OVl'NER. <br /> Signature of Tester: <br /> Agency: Capitol Pump Resources Phone: (360) 493-1830 <br /> Witnessed Bv: <br /> HC kw templates <br />