Laserfiche WebLink
Routine maintenance is performed and records are kept? Yes® No ❑ <br /> Static city water pressure 68 psi <br /> Chum suction pressure 67 psi Churn discharge pressure 180 psi <br /> Was 300 GPM flow conducted? Yes Z No <br /> Hose size: 2.5 inch Tip size: 2.5 inch Hose length: 25 ft <br /> Pitot reading: 9/9/9/9 GPM: 2024 <br /> Was pump run for 10 minutes flowing? Yes ® No ❑ <br /> Were all fire pumps tested? Yes ® No Q <br /> Flow Chart <br /> NO.&SIZE OF PUMP PRESSURE Prrar FLOW RPM VOLTS AMPS COMMENTS <br /> NOZZELS PRESSURE <br /> DISCHG. SUCT. I NET <br /> Churn 154 67 87 - 0 1782 <br /> 4—2 Yz"HM 138 63 75 9/9/9/9 2024 1784 <br /> 4—2 t!"HM 115 155 160 21/20/20/18 2997 1783 <br /> -4- <br /> Problems found: <br /> Corrections made: <br /> Date corrections made: By: <br /> THIS IS TO CERTIFY THAT THE FIRE PUN? SYSTEM HAS BEEN PROPERLY <br /> TESTED AND INSPECTED FOR RELIABILITY TO COVER THE ITEMS LISTED <br /> IN THIS REPORT, IS CONSISTANT WITH MANUFACTURER'S REQUIRE1%1ENTS; <br /> AND ALL CORRECTIONS ARE TO BE MADE BY OWNER. <br /> Signature of Tester: "7 . <br /> Agency: Capitol Pump Resources Phone: (360) 493-1830 <br /> Witnessed By <br /> I IC;kw templates <br />