Laserfiche WebLink
_(apitol Pump <br /> Resources <br /> 5891 Mullen Road SE - Lacey, WA 98503 <br /> (300) 49 4-18.30 <br /> Fax: (360) 923-1841 <br /> Email:hcaulfield@capitolpump.com <br /> CONFIDENCE TESTING <br /> DIESEL <br /> FIRE PUMPS <br /> (EVNP2) <br /> Address: 9801 271' Ave West,Everett WA <br /> Occupied i< Building 40-29 Boeing, Everett <br /> Inspected by: Kyle Nunley Certificate# N-08336 <br /> Date of Inspection: 11/07/2023 Type of Test: Quarterly❑ Annual <br /> Fire Dept, Official Contacted: <br /> Pump Model: 8AEF15G Impeller: 13.81 Serial No.: 9927080929 <br /> Pump Design Conditions: 2000 GPM @ 75 PSI <br /> Controller Model: FD120 Serial No: 16C2230D <br /> Engine Model: JU4H UFADW8 Serial No.: PE4045L261241 <br /> Block Heater Operational: Yes ® No❑ <br /> Batteries: 13.4/13.4 Engine Hours: 277.8 <br /> Controller Voltage: 240 volts Interrupting Capacity: N/A amps <br /> Fire Pump: <br /> Cut-in Pressure: 130 psi Cut-out Pressure: Manual psi <br /> Timer set at: N/A min. <br /> Jockey Pump: <br /> Cut-in Pressure: 150 psi Cut-out Pressure: 160 psi <br /> Timer set at: N/A min. <br /> Pump starts on water from roof? Yes❑ No ❑ N/A <br /> Pump starts on pressure drop? Yes ® No❑ N/A❑ <br /> Pump Motor: Diesel ® Electric ❑ Other <br /> t(TR -Care- "ride -Response- Pumps -Valves- Controls • Sales- Service - Rental -Repair-Testing <br />