GENERAL NOTES CONTRACTOR <br /> GROUNDING NOTES INTERCONNECTION NOTES BLOSSOM SOLAR <br /> SITE NOTES 2.5.1 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR 2.7.1 LOAD SIDE INTERCONNECTION SHALL BE IN <br /> 2.1.1 A LADDER WILL BE IN PLACE FOR INSPECTION IN ACCORDANCE THEIR PURPOSE, AND GROUNDING DEVICES EXPOSED TO THE ACCORDANCE WITH NEC 705.12. <br /> WITH OSHA REGULATIONS. ELEMENTS SHALL BE RATED FOR SUCH USE. 2.7.2 THE SUM OF THE UTILITY OCPD AND INVERTER <br /> 2.1.2 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS 2.5.2 PV EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE CONTINUOUS OUTPUT MAY NOT EXCEED 120 PERCENT OF BLOSSOM SOLAR <br /> SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE WITH NEC 690.43 AND NEC TABLE 250.122. BUSBAR RATING PER NEC 705.12. <br /> BATTERIES. 2.5.3 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND 2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) <br /> 2.1.3 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY ENCLOSURES CONSIDERED GROUNDED IN ACCORDANCE WITH OUTPUT CIRCUIT CURRENT AND THE RATING OF THE #3507 ARLINGTON,WA, 98223 <br /> PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. NEC 250.134 AND 250.136(A). OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL <br /> 2.1.4 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING 2.5.4 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED IN NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE LIC. NO. -0 <br /> AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED IN ACCORDANCE WITH NEC 690.45 AND INVERTER BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE <br /> ACCORDANCE WITH SECTION NEC 110.26. MANUFACTURER'S INSTALLATION PRACTICES LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY <br /> 2.1.5 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND 2.5.5 EACH MODULE WILL BE GROUNDED AS SHOWN IN SOURCE OCPD IN ACCORDANCE WITH NEC 705.12. <br /> MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. 2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT <br /> MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING 2.5.6 THE GROUNDING CONNECTION TO A MODULE SHALL BE COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT <br /> SERVES TO PROTECT THE BUILDING OR STRUCTURE. ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT PROTECTION DEVICES SHALL NOT EXCEED AMPACITY OF <br /> INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. BUSBAR. HOWEVER, THE MAIN OVERCURRENT PROTECTION <br /> EQUIPMENT LOCATIONS 2.5.7 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, DEVICE MAY BE EXCLUDED IN ACCORDANCE WITH NEC <br /> 2.2.1 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS IN SHALL BE COLORED GREEN OR MARKED GREEN IF#4 AWG OR 705.12. <br /> ACCORDANCE WITH NEC 110.26. LARGER PER NEC 250.119 2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) IN <br /> 2.2.2 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE 2.5.8 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC ACCORDANCE WITH NEC 705.12. <br /> RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY 690.47 AND NEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS 2.7.6 SUPPLY SIDE TAP INTERCONNECTION IN ACCORDANCE <br /> NEC 690.31 (A),(C)AND NEC TABLES 310.15 (13)(2)(A)AND 310.15 (B)(3)(C). INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE WITH TO NEC 705.12 WITH SERVICE ENTRANCE <br /> 2.2.3 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV SYSTEM PROVIDED IN ACCORDANCE WITH NEC 250, NEC 690.47 CONDUCTORS IN ACCORDANCE WITH NEC 230.42. PROJECT NAME &ADDRESS <br /> MODULES IN ACCORDANCE WITH NEC 690.34. AND THE AHJ. 2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER <br /> 2.2.4 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED 2.5.9 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL PETER LABIB <br /> PERSONNEL IN ACCORDANCE WITH NEC APPLICABLE CODES. 690.41(B)(1)AND (2) TO REDUCE FIRE HAZARDS FASTENING PER NEC 705.12. 2316 KENILWORTH PL, <br /> 2.2.5 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED EVERETT, WA, 98203 <br /> FOR OUTDOOR USAGE WHEN APPROPRIATE. DISCONNECTION AND OVERCURRENT PROTECTION NOTES APN #: 00734800001300 <br /> 2.6.1 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT AHJ: CITY OF EVERETT <br /> STRUCTURAL NOTES WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING UTILITY: SNOHOMISH COUNTY <br /> 2.3.1 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED IN ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED "LINE PUD <br /> ACCORDANCE WITH THE CODE-COMPLIANT INSTALLATION MANUAL. SIDE" (TYPICALLY THE UPPER TERMINALS). <br /> TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND 2.6.2 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY SYSTEM DETAILS <br /> RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH DC SIZE:AC <br /> DC-(STC) <br /> AC SIZE:22.8000 KW AC <br /> EDGE OF THE ARRAY/SUBARRAY, IN ACCORDANCE WITH RAIL 2.6.3 PV SYSTEM CIRCUITS INSTALLED ON OR IN HABITABLE (48)SILFAB SOLAR SIL-440 QD(440W) <br /> MANUFACTURE (18)TESLAR'S INSTALLATION PRACTICES. BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO ( 1588000-7.68)TESLA PV RAPID SHUTDOWN <br /> N MCI-2(1 PER <br /> 2.3.2 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN s MODULE) <br /> SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & ACCORDANCE WITH 690.12 <br /> SEALED PER LOCAL REQUIREMENTS. 2.6.4 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO REVISIONS <br /> 2.3.3 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED NEC 690.8, 690.9, AND 240. REV DESCRIPTION DATE <br /> AND SEALED W/APPROVED CHEMICAL SEALANT PER CODE BY A 2.6.5 INVERTER ON-GRID BRANCHES SHALL BE CONNECTED TO A <br /> LICENSED CONTRACTOR. SINGLE BREAKER OR GROUPED FUSE DISCONNECT(S) IN <br /> 2.3.4 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO ACCORDANCE WITH NEC 110.3(B). <br /> GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING 2.6.6 IF REQUIRED BY THE AHJ, SYSTEM WILL INCLUDE <br /> MANUFACTURER OR PROFESSIONAL ENGINEERING GUIDANCE. ARC-FAULT CIRCUIT PROTECTION IN ACCORDANCE WITH NEC <br /> 2.3.5 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL 690.11 AND UL1699B. <br /> BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. <br /> SHEET TITLE <br /> WIRING & CONDUIT NOTES NOTES <br /> 2.4.1 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR <br /> THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON <br /> MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT DRAWN DATE 4/11/2025 <br /> UP-SIZING. <br /> 2.4.2 CONDUCTORS SIZED IN ACCORDANCE WITH THE NEC DRAWN BY AN <br /> 2.4.3 AC CONDUCTORS TO BE COLORED OR MARKED PER NEC SHEET NUMBER <br /> 2.4.4 LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED <br /> IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING <br /> OR LABELING PER NEC PV-05 <br />