Fire Department Comments—425.257.8100 <br /> Access: <br /> 1. Buildings exceeding three stories or 30'feet in height shall have at least two means of fire apparatus <br /> access for each structure.(IFC D104.1) <br /> 2. Buildings exceeding 62,000 square feet in area shall have at least two means of fire apparatus access <br /> for each structure. (IFC D104.2) <br /> 3. Aerial Fire Apparatus Access Roads are required where the vertical distance between the grade plane <br /> and the highest roof surface exceeds 30 feet. <br /> 4. Width:26'feet, exclusive of shoulders, in the immediate vicinity of the building or portion thereof_ <br /> Addressing <br /> 1. The address of the building shall have a minimum 10"H x 5"W numbers on the SE corner of the building <br /> on the south wall. The leading edge as emergency vehicles turn into the property. <br /> 2. Address Identification. When the address numbers are located on clear glazing such as doors,windows, <br /> or lights,the numbers shall be white or black to achieve contrast during all lighting conditions. <br /> 3. address Identification.Address numbers at least four inches(4")shall be prominently displayed on rear <br /> entrance or access doors when required by the Fire Chief or his/her designee <br /> Fire Lanes <br /> 1. Marking-approved signs,other approved notices or marking that include the words "NO PARKING-FIRE <br /> LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction <br /> thereof. (EMC 46.44& IFC D103.6) <br /> 2. An approved No PARKING—FIRE LANE signs shall be provided for fire apparatus access roads to <br /> identify such roads or prohibit the obstruction thereof.Signs shall have a minimum dimension of 12" <br /> inches wide by 18 inches high and have red letters on a white reflective background. (IFC D103.6& <br /> EMC 46.44) <br /> Water Supply <br /> 1. FDC. Fire Department Connection shall be located within 75'feet from a fire hydrant.. Location and <br /> positioning of the FDC will be determined by the fire code official. <br /> 2. Fire Hydrants and Fire Department Connections shall be a minimum of fifty feet away from the building <br /> or structure. (EMC 14.16.570-0) <br /> 3. FDC. Locking(KNOX)fire department connection (FDC) caps are required. <br /> Floor and Roof <br /> Page 11 of 13 <br /> Project No.SEPA18-021 <br /> EVERETT <br /> - ....... . <br />