EALNIO N GTR
<br />SRFOE
<br />SPSTA EREERSGEITE G ID NTNOE
<br />HOFWAS
<br />N
<br />I
<br />C49625ARTERBIESE
<br />M
<br />EEYRPLANS ISSUED FOR
<br />BID
<br />ACTION DATE APRVD ACTION DATE APRVD ACTION DATE APRVD
<br />CONST RECORD
<br />Drawing
<br />Sheet No.
<br />Of Total
<br />Designed
<br />Drawn
<br />Checked
<br />Design Review Level
<br />500
<br />Plot dateFilepath\FilenameWO# UP-3525
<br />PORT GARDNER
<br />everettwa.gov
<br />3200 Cedar Street
<br />Everett, WA 98201
<br />425.257.8800
<br />NO. DATE APRVD REVISION
<br />12/2/2024 ZB
<br />STORAGE FACILITY -
<br />FACILITY CONSTRUCTION PACKAGE
<br />09/03/2025 ZBAutodesk Docs://157889 - PGSF/M-3525-70V23.rvt8/27/2025 8:24:03 AMM-70-7001
<br />378
<br />MECHANICAL
<br />OMES BUILDING SCHEDULES
<br />C. BIESEMEYER
<br />M. FULK
<br />R. LONG
<br />FAN SCHEDULE
<br />EQUIPMENT ID MANUFACTURER MODEL SERVICE LOCATION TYPE
<br />AIR ELECTRICAL PHYSICAL
<br />NOTESAIRFLOW
<br />(CFM)
<br />TEMP DB
<br />(°F)
<br />STATIC PRESSURE DROP
<br />(IN H20)
<br />MOTOR SIZE
<br />(HP)VOLT/PH L/W/H (IN)
<br />WEIGHT
<br />(LBS)
<br />70-EF-0101 COOK XWD VENTILATION COOLING OMES BUILDING WALL FAN 1000 70 0.25 128W 115/1 18/18/18 100 1
<br />70-EF-0102 COOK XWD VENTILATION COOLING OMES BUILDING WALL FAN 1000 70 0.25 128W 115/1 18/18/18 100 1
<br />70-EF-0103 COOK XWD VENTILATION COOLING OMES BUILDING WALL FAN 1000 70 0.25 128W 115/1 18/18/18 100 1
<br />25-EF-0101 COOK XWD VENTILATION COOLING OCS BUILDING WALL FAN 500 70 0.25 98W 115/1 12/12/12 75 1
<br />25-EF-0102 COOK XWD VENTILATION COOLING OCS BUILDING WALL FAN 500 70 0.25 98W 115/1 12/12/12 75 1
<br />NOTES:
<br />1.COORDINATE WITH MANUFACTURER REQUIREMENTS FOR LOUVER, BACKDRAFT DAMPER, AND WALL PENETRATION.
<br />AIR TO AIR HEAT EXCHANGER SCHEDULE
<br />EQUIPMENT ID MANUFACTURER MODEL LOCATION TYPE
<br />LOAD
<br />(BTUH)
<br />GENERATION AIR CONSUMPTION AIR
<br />VOLT/PH
<br />PHYSICAL
<br />NOTESAIRFLOW RATE
<br />(CFM)
<br />ENTERING/LEAVING
<br />TEMP DB/WB (°F)
<br />STATIC
<br />PRESSURE DROP
<br />(IN H2O)
<br />AIRFLOW RATE
<br />(CFM)
<br />ENTERING/LEAVING
<br />TEMP. DB/WB (°F)
<br />STATIC PRESSURE DROP
<br />(IN H2O)
<br />L/W/H
<br />(IN)
<br />EFFICIENCY
<br />(%)
<br />70-ERV-0101 MITSUBISHI LGH RVX2 OMES BUILDING ENERGY RECOVERY VENTILATOR 10,000 300 25/55 55/25 0.3 300 65/35 45/45 0.3 230/1 48/42/18 60
<br />CONDENSER UNIT SCHEDULE
<br />EQUIPMENT ID MANUFACTURER MODEL LOCATION
<br />CONNECTED
<br />AIR HANDLER TYPE AIR AMBIENT TEMP
<br />DB/WB (°F)
<br />CONDENSER ELECTRICAL PHYSICAL
<br />NOTESMIN SENS HEAT REJ
<br />CAPACITY (MBH)
<br />WORKING
<br />FLUID
<br />MAXIMUM
<br />(KW)MCA EER/COP
<br />(COOL/HEAT)
<br />VOLT/
<br />PH
<br />PHYS L/W/H
<br />(IN)
<br />PHYS WEIGHT
<br />(LBS)
<br />70-CU-0101 MITSUBISHI PUZ OMES BUILDING TB1 SPLIT SYSTEM DX COOLING PERFORMANCE 80 22,000 R410a 19 11 230/1 40/18/40 100 LOW AMBIENT
<br />SPLIT SYSTEM DX HEATING PERFORMANCE 80 22,000 R410a 4
<br />70-CU-0102 MITSUBISHI PUZ OMES BUILDING TB2 SPLIT SYSTEM DX COOLING PERFORMANCE 80 22,000 R410a 19 11 230/1 40/18/40 100 LOW AMBIENT
<br />SPLIT SYSTEM DX HEATING PERFORMANCE 80 22,000 R410a 4
<br />LOUVER SCHEDULE
<br />EQUIPMENT ID LOCATION TYPE
<br />DIMENSIONS FACE
<br />AREA
<br />(SQ FT)
<br />FREE
<br />AREA
<br />(SQ FT)
<br />FLOW
<br />(CFM)NOTESH (IN) W (IN)
<br />70-WL0101 OMES BUILDING INTAKE 24 24 4 1 1000 1
<br />70-WL-0102 OMES BUILDING INTAKE 24 24 4 1 1000 1
<br />70-WL-0103 OMES BUILDING INTAKE 24 24 4 1 1000 1
<br />25-WL-0101 OCS BUILDING INTAKE 18 18 2.25 0.5 500 1
<br />25-WL-0102 OCS BUILDING INTAKE 18 18 2.25 0.5 500 1
<br />NOTES:
<br />1.GRAVITY BACKDRAFT DAMPER.
<br />AIR HANDLING UNIT SCHEDULE
<br />EQUIPMENT ID SERVICE LOCATION
<br />SUPPLY FAN SUPPLY FAN MOTOR HEAT PUMP
<br />BASIS OF DESIGN UNIT WEIGHT
<br />(LBS)NOTESCFM ESP (°WG) HP VOLTS PH HZ
<br />CAPACITY
<br />(BTUH)
<br />70-AH-0101 OPERATION AND MAINTENANCE AREAS COOLING PERFORMANCE OMES BUILDING 750 0.5 121W 230 1 60 22,000 MITSUBISHI PEAD 100 1,2,6,8,9
<br />OPERATION AND MAINTENANCE AREAS HEATING PERFORMANCE OMES BUILDING 22,000
<br />70-AH-0102 OPERATION AND MAINTENANCE AREAS COOLING PERFORMANCE OMES BUILDING 750 0.5 121W 230 1 60 22,000 MITSUBISHI PEAD 100 1,2,6,8,9
<br />OPERATION AND MAINTENANCE AREAS HEATING PERFORMANCE OMES BUILDING 22,000
<br />NOTES:
<br />1.INSTALL UNIT IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTALLATION CRITERIA.
<br />2.REFER TO SPECIFICATIONS FOR ADDITIONAL DESIGN CRITERIA AND CONTROL SEQUENCE.
<br />3.UNIT SHALL BE SUITABLE FOR MOUNTING ON CONCRETE PAD.
<br />4.PROVIDE WITH FACTORY SUPPLIED TOTALLY ENCLOSED FAN MOTOR COVER.
<br />5.PROVIDE WITH UNIT-MOUNTED INLET SILENCER.
<br />6.PROVIDE WITH MERV 8, 2" PLEATED FILTERS AND FILTER MOUNTING RACK.
<br />7.PROVIDE UNIT WITH SECTIONS IN THE FOLLOWING ORDER: FAN, HEATING COIL, FACE AND BYPASS DAMPER, INSPECTION PLENUM, SOUND ATTENUATOR, FILTER.
<br />8.PROVIDE WITH SINGLE-POINT ELECTRICAL CONNECTION.
<br />9.PROVIDE WITH FACTORY INSTALLED CONTROLS.
<br />10.PROVIDE LIFTING LUGS FOR COMPONENTS WEIGHING OVER 100 LBS.
<br />11.PROVIDE 16-GAUGE STAINLESS STEEL IDENTIFICATION PLATE ON EACH SEPARATE EQUIPMENT COMPONENT AND CONTROL PANEL IN A READILY VISIBLE LOCATION.
<br />ELECTRIC UNIT HEATER / CABINET HEATER SCHEDULE
<br />EQUIPMENT ID AREA SERVED CFM
<br />TEMP. DIFF
<br />(°F)
<br />FAN ELECTRICAL DATA HEATER ELECTRICAL DATA MTG. HT
<br />(FT)
<br />THROW
<br />(FT)
<br />THROW
<br />DIRECTION
<br />BASIS OF
<br />DESIGN NOTESHP VOLT PH HZ KW AMPS VOLT PH HZ
<br />70-UH-0101 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0102 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0103 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0104 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0105 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0106 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0107 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />70-UH-0108 OMES BUILDING 700 32 0.07 240 1 60 7.3 31.4 240 1 60 7 FT 30 FT ADJUSTABLE REZNOR, EUH 1,3
<br />NOTES:
<br />1.PROVIDE BUILT IN STAGED THERMOSTAT, MAGNETIC CONTACTOR, SUB CIRCUIT FUSING, FAN DELAY ON SHUT DOWN, HEATING DELAY ON START UP, CONTROL TRANSFORMER, DISCONNECT SWITCH, MOUNTING BRACKETS AND THERMAL CUTOUT SWITCH FOR EACH ELEMENT.
<br />2.3-WIRE POWER FEED.
<br />3.PROVIDE WITH WALL MOUNTING BRACKET.
|