Laserfiche WebLink
Port Gardner Storage Facility Volume 7 Attachment O <br /> Page 45 <br />CITY OF EVERETT ⋅ 3200 Cedar Street ⋅ Everett, WA 98201 ⋅ (425) 257-8800 ⋅ Fax (425) 257-8882 <br /> <br />Bid Item #30 shall include crack repair only, as identified on the drawings. Per <br />Section 01 22 13 Measurement and Payment Bid Item #30, locations of concrete <br />repair will be coordinated with the Owner and confirmed prior to commencement <br />of the work. All other concrete repairs and infill work currently identified on the <br />Drawings shall be included in other area specific bid items. <br />Q245 - The gate mounting for gate tags 50-G-0001, 50-G-0002, 50-G-0004 & 50-G- <br />0005 is inconsistent in the drawing and schedule. Drawing D-50-1001 & D-50-3001 <br />shows thimble mounted gates but the schedule calls these gates to be wall mounted. <br />Which is correct? <br />Furnish the gates as described in Section 40 05 59.23. <br />Q246 - Specification 33 42 00 “Packaged Pump Station” includes a fiberglass pump <br />station. Please provide details for the FRP station cylinder such as depth, diameter and <br />pipe connections. <br />The Packaged Pump Station is shown as SDMH 46-07 on the drawings. See <br />Drawing C-10-6201 for depth and piping connections. The pump station Supplier, <br />Flygt, to determine the fiberglass wet well diameter for the packaged system from <br />the information provided. <br /> <br /> <br />