Laserfiche WebLink
Port Gardner Storage Facility Volume 7 Attachment O <br /> Page 44 <br />CITY OF EVERETT ⋅ 3200 Cedar Street ⋅ Everett, WA 98201 ⋅ (425) 257-8800 ⋅ Fax (425) 257-8882 <br /> <br />Conduit C10101 is to be used as a spare raceway, size is 2”. Install pull rope in <br />raceway. <br />Q240 - C40002B in DB0006B is not shown on conduit schedule. Please clarify conduit <br />size and cable needed. <br />Conduit C40002B is to be used as a spare raceway, size is 3-1/2”. Install pull rope <br />in raceway. <br />Q241 - Spec section 26 05 36 2.02 B.1.c. states "Cable tray widths shall be 24 and 36 <br />inches as shown on drawings" However drawing EG-70-2001 the cable tray are <br />measuring out to 12" and 24". Please confirm the size of the cable. <br />Use cable tray widths as identified on Drawings & Schedules. <br />Q242 - Drawing EG-70-3001 show a "Cable Transition System." Please provide more <br />detail e.g. manufacturer catalog number. <br />The system used during design was based on the Roxtec (www.roxtec.com) <br />sealing solution for transition & support of cables when routing through building <br />wall. <br />Q243 - Drawing EP-70-1002: 1. Raceway Identifier missing for (7) mechanical devices <br />(e.g. 70-EF-01, 70-UH-0104...) 2. Raceway Identifier C70001 & C70002 contradicts <br />Cable Raceway Schedule destination, which is appropriate. 3. Raceway Identifier <br />missing for (70-MCC-0001). <br />1. Raceway identifier intentionally omitted as those loads are to be field run <br />between the exhaust fans & unit heaters in question back to 70-PNL-3001. <br />See panel schedule on EP-70-7001. <br />2. C70001 & C70002 are mislabeled raceways on drawing EP-70-1002. Relabel <br />C70001 & C70002 to C30001A & C30002A respectively (not in cable/raceway <br />schedule). Each of these 2” conduits route cables 30-C0001 & 30-C0002 <br />(36C #14 TCER cable) between the HPU (70-LCP-5000) and cable tray <br />CTC002, then continuing to 30-CJB-0001 & 30-CJB-0002 for Area 30 <br />Flushing Gate Equipment. <br />3. 70-HPU-5000 is powered from 70-PNL-3000, not the MCC. The raceway <br />identifier has been intentionally omitted as the loads in that circuit are to be <br />field run. <br />Q244 - Concrete repair is shown on numerous drawings for this project. Please confirm <br />ALL types of concrete repairs, including but not limited to concrete infill repairs, for this <br />project will be covered under Bid Item #30.