Laserfiche WebLink
Vjendo- <br />IF <br />SAN� <br />Item <br />Description <br />Controller Alarm <br />Part # <br />Action <br />Display or Symptom <br />1 <br />Ambient Temp. Sensor <br />Err 1 / Err 6 <br />1256245 <br />Sensor disconnected <br />2 <br />Evaporator Air Coil Temp. Sensor <br />Err 5 / Err 7 <br />1256245 <br />or out of range. <br />Check sensor wire <br />3 <br />Evaporator Outlet Pressure Sensor <br />Err 3 <br />1220143 <br />continuity to <br />4 <br />Evaporator TX Outlet Temp. Sensor <br />Err 4 <br />1256245 <br />controller, or replace <br />sensor <br />5 <br />Evaporator Air Out Temp. Sensor <br />Err 2 <br />1256245 <br />6 <br />Evaporator Fan Blade <br />Excessive noise from <br />1220804 <br />Replace fan blade <br />fan, blade wobble <br />Fan not turning, RSC not <br />Check 115 VAC is <br />7 <br />Evaporator Fan Motor <br />cooling <br />1262025 <br />getting to motor; <br />replace motor <br />Turn off power to <br />RSC and turn back <br />8 <br />Controller <br />RSC not cooling <br />1243039- <br />on; confirm remote <br />1.07 <br />refrigeration unit is <br />working properly; <br />replace controller <br />Moisture accumulating <br />If fan isn't turning, <br />9 <br />Condensation Fans <br />on bottom of RSC <br />1218646 <br />check fan is getting <br />24 VDC; replace fan <br />Confirm 24 VDC is <br />10 <br />Solenoid Valve <br />RSC not cooling <br />1220789 <br />getting to solenoid; <br />replace solenoid <br />8 Controller <br />5 Evap air out temp sensor <br />2 Evap air temp sensor <br />1 Ambient temp sensor <br />6 Evap fan blade <br />7 Evap fan motor <br />9 Condensation Fans <br />10 Solenoid valve <br />4 Evap TX out temp sensor <br />3 Evap outlet pressure sensor <br />30 <br />