Laserfiche WebLink
Eintegra <br /> NEUDORFER <br /> ENGINEERS <br /> AN Integra COMPANY <br /> Air Handling Unit <br /> PROJECT: Boeing 40-26 Tower Relocation DATE: 3/3/2025 <br /> LOCATION: Everett,WA CONTACT: Tony Amort <br /> PROJECT#: 2024-0419 AUTHOR: <br /> SYSTEM/UNIT: HVAC-25/Outside Airflow Tested By: Tony Amort <br /> Date: 2/25/2025 <br /> Unit Data Final Data <br /> Type of Traverse Rectangular Sum of Readings 8397 FPM <br /> Instrument Used Pitot Tube Average Reading 350 FPM <br /> Outer Height 16.00 in. Reading Std. Dev. 80.225 FPM <br /> Outer Width 34.00 in. Design Total Flow 1450 CFM <br /> Insulation Width 0 in. Actual Total Flow 1323 CFM <br /> Rect.Correction Factor 1 Static Pressure -0.08 in. <br /> Air Flow Area 3.78 sq.ft. <br /> Number Of Rows 6 <br /> Readings Per Row 4 <br /> Total Readings 24 <br /> Traverse Data Points <br /> O O O O <br /> L1 C� C1 C� <br /> Row 1 ® 354 Fin 5% <br /> Row 2 420 427 � 326 <br /> Row 3 ® 415 3dD 352 <br /> Row 4 ® 393 303 235 <br /> Row 5 369 ® 3d1 Fn <br /> Row 6 267 276 24D 176 <br /> 34 <br /> Neudorfer Engineers <br />