Laserfiche WebLink
Eintegra <br /> NEUDORFER <br /> ENGINEERS <br /> AN Integra COMPANY <br /> Air Handling Unit <br /> PROJECT: Boeing 40-26 Tower Relocation DATE: 3/3/2025 <br /> LOCATION: Everett,WA CONTACT: Tony Amort <br /> PROJECT#: 2024-0419 AUTHOR: <br /> SYSTEM/UNIT: HVAC-25/Return Airflow Tested By: Tony Amort <br /> Date: 2/25/2025 <br /> Unit Data Final Data <br /> Type of Traverse Round Sum of Readings 13005 FPM <br /> Instrument Used Pitot Tube Average Reading 650 FPM <br /> Diameter 30 in. Reading Std. Dev. 63.502 FPM <br /> Insulation Width 0 in. Design Total Flow 3330 CFM <br /> Rect.Correction Factor 1 Actual Total Flow 3192 CFM <br /> Air Flow Area 4.91 sq.ft. Static Pressure -0.14 in. <br /> Number Of Rows 2 <br /> Readings Per Row 10 <br /> Total Readings 20 <br /> Traverse Data Points <br /> N <br /> d <br /> O <br /> 46% <br /> �6 <br /> 615 <br /> 728 <br /> Hole 1 ® 695 ® 691 696 700 618 676 ® 598 M <br /> 703 <br /> 653 <br /> 632 <br /> 674 <br /> 30 <br /> Neudorfer Engineers <br />