Ltr. F. Gogal <br />July 26, 2007 <br />Page 2 <br />7. Provide fire -blocking in concealed spaces at not more than 10'-0" on center <br />horizontal and vertical. Show requirement on plans. <br />S. Provide minimum 3" x 3" x '/a " plate washers on all anchor bolts in braced wall <br />lines. <br />9. The Simpson HPAHD22 shown in the garage wall (between entry and garage) <br />appears to be located in the wrong place. It should be on the right side of the front <br />door in the same wall as the front door. Please verify. <br />10. Provide R-21 insulation in the walls along the stairs that go down to the study. The <br />. underside of the stairs is required to be insulated to minimum R-30. Show <br />requirement on plans. <br />Please prepare a response letter showing where each item in this correction letter is addressed <br />on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, f <br />Jeff Heil an <br />Development Technician <br />DEDI/PLNCKMSTR/HEILMAN/BASIC #245 (8812 3PD AVE SE) <br />