►-- • . <br /> l4. Egress and emergency lighting should be shown on the drawings, per IBC sedions <br /> 100G.3, lUll.l, and Table 1015.1. <br /> a. A discernible path of egress should be shown with illuminated exit signs on the <br /> drawings, per IBC section 1011.1, where two exits are required. <br /> b. Emergency lighting should be shown on the drawings, per IBC section 1006.1, <br /> where hvo exits are required. <br /> Construction <br /> 1. Door and window schedules should be shovan on the drawings. <br /> /l/1c�P��&'J a. Door widths are minimum 2'-10" per IBC section 1008.1.1. <br /> oN P���'� b. The height of window heads and silis should be shown in elevation. <br /> ��,3,�,, c. New doors shou' ��ave hardware referenced on the drawinys that is operable <br /> d� fa��af" without tight grasping, pinching or hvisting of the vdrist, per IBC sedion <br />_ �y;�r 1008.1.9.1. <br /> 2. New wall sedions with dimensions should be shown on the draw�ngs and referenced <br /> from the plans. <br /> � 3. A lighling plan indicating the amount of relights should be shown on the plans. <br /> Alterations that replace 60% or more of the luminaires should be shown to comply with <br /> WSEC C101.4.3.1. <br /> Accessibility <br /> � 1. The new lavatory in the service room should be shown in elevation to be 34 inches <br /> maximum above the floor. <br /> Deferred Mechanical Permit <br /> � i. A separate mechanical permit with dra�vings to show ventilation to meet the <br /> requiremenks of IMC table 403.3. The following should be included: <br /> a. Catalog cuts of new equipment <br /> b. Equipment tables showir.g cfm and economize�s <br /> c. Structural review for new units over 400 pounds s��pported on the rooF. <br /> / 2. A roof plan should be submitted to locate exhaust and supply equipment. <br /> ✓ 3. The hood over the stove should be identified as a 7ype I, Type II or Hazardous Exhaust <br /> hood, per IMC sections 506 through 510. <br /> These comments address building issues only. Revisions or additions may be required by other <br /> departments (such as Utilities, Planning or Fire). All required submittals must be of sufficient <br /> detaii and information to ensure that the proposed structure will be constructed in compliance <br /> with all adopted codes. You can reach me directly to discuss this letter by e-mail at <br /> mhalev a everettwa.aov or by phone at 425-257-8813. <br /> Sincerely, <br /> eg ley, RA <br /> lan R iew Architect - <br /> � � <br />