Laserfiche WebLink
., �S}�stem Design <br /> . <br /> �-? �XLI1�1aER FLO[�VS <br /> After finding how many nozzles of each type are required for a system, the sum of all the nozzle flow <br /> numbers is used to determine the number and size of the cylinders required, in accordance��ith the <br /> cylinder flow number limits given below. <br /> Table 3-30. Cylinder Flow Number Limits <br /> Maximum Flow Numbers of Cylinders <br /> Cylinder Flow Number <br /> RG-1.25G 4—Single Cylinder Systems Only(cannot manifold) <br /> RG-2.5G 8—Single Cylinder Systems Only(cannot manifold) <br /> RG-4GS/RG4GM Can manifold up to 4 cylinders1 <br /> 1 Cylinder 12 <br /> 2 Cylinders 24 <br /> 3 Cylinders 36 <br /> 4 Cylinders 48 <br /> RG-6G Can manifold up to 2 cylindersl <br /> 1 Cylinder 18 <br /> 2 Cylinders 36 <br /> 1 Only like cylinders can be manifolded(i.e., four RG-4GS or RG-4GM; two RG-6G) <br /> �� /_ � <br /> i <br /> April 2009 3-42 P/N 60-9127100-000 <br />