. <br />e. The riser room should be identified on the plans. <br />f. A post indicator valve (PIV) is required if there is not direct access to the riser room from <br />outside of the building. <br />g. All plan sheets affected by these revisions. <br />h. All hydraulic calculations affected by these revisions. <br />If you have questions about the backflow requirements identified on the attached owner notification, please <br />contact Tim Markham at 425-257-8833. If you have questions about the PIV or other fire service equipment, <br />please contact Assistant Fire Marshal Jim Venturo at 425-257-8124. I can answer other questions regarding <br />this corrections letter. <br />Sincerely, <br />Meg Hal�y, ArcR+�ect, NCARB, Plans Examiner <br />Cc: AFM�Jim Vent�ro, Mike Ward, Paul McKee, Tim Markham, Benyam Stephanos <br />2 <br />