Laserfiche WebLink
• r <br /> 11p <br /> PUBLIC WORKS ._ ._ <br /> ' pug/FE-Tr Seat vie e-nlaili <br /> June 10, 2014 <br /> Mr. Don Ringman <br /> Don's Quality Repair <br /> 2411 Walnut St <br /> Everett, WA 98201 <br /> Project: Entry Deck Revisions for Permit <br /> Permit Number: 9~ It./.1 1411 - 00? <br /> Job Address: 2625 Hoyt Ave <br /> RE: Corrections Letter <br /> Dear Mr. Ringman, <br /> In response to your application for a construction permit, your plans have been examined and you are advised that <br /> revisions may be necessary before a permit can be issued. Please review and respond to the comments below. <br /> In order for the processing of your application to continue, it will be necessary to provide the Building <br /> Division with two complete new sets of construction documents reflecting the corrections requested. <br /> General <br /> 1. Based on permit history available in our offices, the rear entry deck is considered new work. <br /> Structural <br /> 1. The framing shown is not sufficient for the 100 psf live load required for an assembly building <br /> entrance, per IBC table 1607.1. <br /> a. The use of an architect or engineer to submit the framing plans and calculations would expedite <br /> the permit review process. <br /> Egress <br /> 1. Emergency lighting should be shown on the plans outside of the egress doors shown, per IBC section <br /> 1006.3. <br /> Construction <br /> 1. Ramps should be shown with a maximum 1:12 height, or slope of 8.33%. The ramps shown on the <br /> drawings indicate a slope of 11.86%. <br /> 2. The center stair may also require a guard, for a portion of the stair run. Guards are required where the <br /> open sided walking surface is more than 30 inches above the floor or stair below, per IBC section <br /> 505.3.3, 1013.2, and 1013.4. <br /> a. Guard openings should be shown on the drawings not to allow a sphere of less than 4 inches, <br /> per IBC 1013.4. <br /> b. Guard height should be shown on the drawings as minimum 42 inches. <br />