Laserfiche WebLink
} <br /> 3. Please indicate handrails on both sides of the stair and ramps, with either extensions or returns, per <br /> IBC section 1012. Handrail sections and heights should be shown on the drawings to comply with IBC <br /> sections 1009.15 and 1012. <br /> Accessibility <br /> 1. Landings should have a clear length of 60 inches shown on the drawings, per ICC A117.1-2009 Section <br /> 405.7.3. <br /> 2. A 5'-0"turning radius at a changing in direction in the ramp should be shown on the drawings, per ICC <br /> A117.1-2009 Section 405.7.4. <br /> These comments address building issues only. Additional revisions, or additions, may be required by other <br /> departments (such as Utilities, Planning or Fire). All references refer to the 2012 International Building Code (IBC), <br /> the 2012 International Fire Code (IFC), the 2012 International Mechanical Code (IMC), and the 2012 Washington <br /> State Energy Code (WSEC), as amended by the State of Washington and adopted by the City of Everett. The <br /> current IBC referenced standard for accessible design is the 2009 "Accessible and Usable Buildings and Facilities" <br /> (ICC/ANSI A117.1). Federal ADA regulations and standards may be more restrictive. <br /> i cerely, <br /> Meg H: - Architect, NCARB, Plans Examiner <br /> Attach i �•nt: Handout for commercial decks, ramps, and stairs <br /> Cc: Mr. Les Lewis <br /> Bethel Baptist Church <br /> Everett, WA 98201 <br /> 2 <br />