Laserfiche WebLink
3) For clarity, the structural exterior deck members should be shown as pressure treated on <br /> Detail 10/S5. Footings should be shown supporting the posts (to include sizing and <br /> reinforcement). <br /> 4) The enclosed space under the stairs should be separated from the stairs by minimum one- <br /> hour fire-resistive construction. Section 1009.6.3 <br /> 5) It should be verified that the elevator cab is capable to accommodate a stretcher(24"x84") <br /> operated in the lay-down position. The symbol for emergency medical services (star of life) <br /> symbol should be placed on both sides of the hoistway door frame. City of Everett Ordinance <br /> revisions to Section 3002.4 <br /> 6) e prove w I <br /> '"'1 Z .1 <br /> 7) The heights of the lavatories, urinals and toilets should be shown on the plans. ANSI <br /> Sections 604.4, 605.2 &606.3, <br /> 8) The plans should indicate that the walls between the warehouse and office spaces will be <br /> insulated to a minimum of R-19. Table 13-1 WSEC <br /> 9) Window U factors should be noted on the plans for the proposed glazing. Table 13-1 WSEC <br /> Please provide a response letter, which shows where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan <br /> review will begin. <br /> All required submittals must be of sufficient detail and contain sufficient information to <br /> ensure that the proposed structure will be constructed in compliance with all adopted <br /> codes. <br /> Sincerely, <br /> Tony R. Lee <br /> Building Official <br />