Laserfiche WebLink
5. Provide carbon monoxide alarms outside of each separate sleeping area in the <br /> immediate vicinity of bedrooms, and on each level of the dwelling in accordance with <br /> the manufacturer's recommendations. R315 IRC. <br /> 6. Provide R-49 insulation in attic of living space per table 6-1 Wa. State Energy Code <br /> (WSEC). <br /> 7. Provide minimum 50 CFM fan in the main floor bathroom adjacent to the new bathroom <br /> in the addition. <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: jheilman@ci.everett.wa.us <br /> S:\1Common\Clerical\]Heilman\C1207-007(602 Kings PI).doc <br />