GENERAL CONSTRUCTION NOTES
<br />t. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE LOCAL BUILDING CODE, THE LATEST
<br />EDITION AND ALL OTHER APPLICABLE CODES AND ORDINAKCES.
<br />2. CONTR4CTOR SHALL CONSTRUCT SITE IN ACCORDANCE WITH THESE DRAWINGS AND SPRWT
<br />INTEGRATED CONSTRUCTION STANDARDS FOR WIRELESS SITES (LATEST REVISION). THE
<br />SPECIFICATION IS THE RULING DOCUMENT AND ANY DISCREPANCIES BEfWEEN THE SPECIFICATION
<br />AND THESE DRAWINGS SHOULD BE BROUGHT TO THE ATTENTION OF THE ENGMEER PRIOR TO
<br />PROCEEDING WITH CONSTRUCTION.
<br />3. CONTR4CTOR SHALL VISIT THE JOB SITE AND SHALL FAMILIARIZE HIMSELF WITH ALL CONDITIONS
<br />AFFECTING THE NEW WORK AND SHALL MAKE PROVISIONS AS TO THE COST THEREOF. FIELD
<br />CONDITIONS AND DIMENSIONS AND CONFIRMING THAT THE WORK MAY BE ACCOMPLISHED AS
<br />SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ENGINEER PRIOR TO THE COMMENCEMENT OF WORK. NO
<br />COMPENSATION WILL BE AWAROED BASEO ON CLAIM OF LACK OF KNOWLEDGE OF FIE�D
<br />CONDITIONS.
<br />4. PLANS ARE NOT TO BE SCALED. THESE PLANS ARE INTENDED TO 8E A DIAGRAMMATIC OUTLINE
<br />ONLY UNLESS OTHERWISE NOTED. THE WORK SHALL INCLUDE FURNISHINC MATERIALS,
<br />EQUIPMENT AND APPURTENANCES, AND LABOR NECESSARY TO EFFECT ALL INSTALLATIONS AS
<br />INDICATED ON THE DRAWINGS.
<br />5. DIMENSIONS SHOWN ARE TO FINISH SURFACES UNLESS OTHERWISE NOTED. SPACING BEfWEEN
<br />EQUIPMENT IS REQUIRED CLEARANCE THEREFORE, IT IS CRITICAL TO FlELD VERIFY DIMENSIONS,
<br />SHOULD TNERE BE ANY QUESTIONS REGARDING THE CONTR4CT DOCUMENTS, EXISTING CONDITIONS
<br />AND/OR DESIGN INTENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING THE WORK.
<br />6. DEfAILS ARE INTENDED TO SHOW DESIGN INTENT. MODIFICATIONS MAY BE REqUIRED TO SUIT
<br />JOB DIMENSIONS OR CONDITIONS, AND SUCH MODIFICATIONS SHALL BE INCWDED AS PART OF
<br />THE WORK.
<br />7. CONTRACTOR SHALL RECEIVE CLARIFICATION IN WRITING, AND SHALL RECEIVE IN WRITING
<br />AUTHORIZATION TO PROCEED BEFORE STARTING WORK ON ANY ITEMS NOT CLEARLY DEFINED OR
<br />IDENTIFIED BY THE CONTRACT DOCUMENTS.
<br />8. CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK USING THE BEST CONSTRUCTION SKILLS
<br />AND ATTENTION. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS,
<br />MEfHODS, TECHNIQUES, SEQUENCES AND PROCEDURES AND FOR COORDINATING ALL PORTIONS
<br />OF THE WORK UNDER CONTR4CT, UNLESS OTHERWISE NOTED.
<br />9. CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFEfY OF THE WORK AREA, ADJACENT AREAS
<br />AND BUILDING OCCUPANTS THAT ARE LIKELY TO BE AFFECTED BY THE WORK UNDER THIS
<br />CONTRACT. WORK SHALL CONFORM TO ALL OSHA REQUIREMENTS.
<br />10. CONTRACTOR SHALL COORDINATE HIS WORK WITH THE SUPERWTENDENT OF BUILDINGS &
<br />GROUNDS AND SCHEDULE HIS ACTIVITIES AND WORKING HOURS IN ACCORDANCE WITH THE
<br />REQUIREMENTS.
<br />11. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATWG HIS WORK WITH THE WORK OF OTHERS
<br />AS IT MAY RELATE TO RADIO EQUIPMENT, ANTENNAS AND ANY OTHER PORTIONS OF THE WORK.
<br />12. INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURERS
<br />RECOMMENDATIONS UNLESS SPECIFICALIY OTHERWISE INDICATED OR WHERE LOCAL CODES OR
<br />REGULATIONS TAKE PRECEDENCE.
<br />13. MAKE NECESSARY PROVISIONS TO PROTECT EXISTING SURFACES, EQUIPMENT, IMPROVEMENTS,
<br />PIPING EfC. AND IMMEDIATELY REPAIR ANY DAMAGE THAT OCCURS �URING CONSTRUCTION.
<br />14. IN DRILLMG HOLES INTO CONCRETE WHETHER FOR FASTENING OR ANCHORING PURPOSES, OR
<br />PENETRATIONS THROUGH THE FLOOR FOR CONDUIT RUNS, PIPE RUNS, ETC., MUST BE CLEAF2LY
<br />UNDERSTOOD THAT REINFORCING STEEL SHALL NOT 8E DRILLED INTO, CUT OR DAMAGED UNDER
<br />ANY CIRCUMSTANCES (UNLESS NOTED OTHERWISE). LOCATIONS OF REWFORCWG STEEL ARE NOT
<br />DEFINITELY KNOWN AND THEREFORE MUST BE SEARCHED FOR BY APPROPRIATE MEfHODS AND
<br />E�UIPMENT.
<br />15. REPAIR ALL EXISTING WALL SURFACES DAMAGED DURING CONSTRUCTION SUCH THAT THEY MATCH
<br />AND BLEND IN WITH ADJACENT SURFACES.
<br />16. SEAL PENETRATIONS THROUGH FIRE RATED AREAS WITH U.L LISTED AND FIRE CODE APPROVED
<br />MATERIALS.
<br />17. KEEP CONTRACT AREA CLEAN, HAZAR� FREE, AND DISPOSE OF ALL DIRT, DEBRIS, AND RUBBISH.
<br />EQUIPMENT NOT SPECIRED AS REMAINING ON THE PROPERN OF THE OWNER SHALL BE
<br />REMOVED. LEAVE PREMISES IN CLEAN CONDITION AND FREE FROM PAINT SPOTS, DUST, OR
<br />SMUDGES OF ANY NATURE. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTNNING ALL ITEMS
<br />UNTIL COMPLETION OF CONSTRUCTION.
<br />18. MINIMUM BEND RADIUS OF AMENNA CABLES SHALL BE IN ACCORDANCE WITH CABLE
<br />MANUFACTURERS RECOMMENDATIONS.
<br />79. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITIES, WHICH WTERFERE
<br />WITH THE ExECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED, PLUGGED OR
<br />OTHERW6E DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE
<br />WORK, SUBJECT W THE APPROVAL OF THE ENGWEER.
<br />20. CONTRACTOR SHALL MINIM2E DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION
<br />CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION SHALL BE IN CONFORMANCE WITH
<br />JURISDICTIONAL OR STATE AND LOCAL GUIDELINES FOR EROSTION AND SEDIMENT CONTROL AND
<br />COORDINATED WITH LOCAL REGULATORY AUTHORITIES.
<br />21. LIGHT SHADED LINES AND NOTES REPRESENT WORK PREVIOUSLY DONE. DARK SHADED LINES
<br />AND NOTES REPRESENT THE SCOPE OF WORK FOR THIS PROJECT. CONTRACTOR SHALL VERIFY IF
<br />EXISTWG CONSTRUCTION IS COMPLETE. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY EXISTING
<br />CONDITIONS THAT DEVIATE FROM THE DR4WINGS PRIPOOR TO BEGINNING CONSTRUCTION.
<br />22. CONTRACTOR SHALL SECURE ALL NECESSARY PERMITS AND/OR WIRING CERTIFICATES REQUIRED
<br />FOR THE ELECTRICAL SERVICE UPGRA�E IN A�DITION, CONTRACTOR SHALI PROVIDE ALL
<br />NECESSARY COORDINATION AND SCHEDULING WITH THE SERVING ELECTRICAL UTILIN AND LOCAL
<br />INSPECTION AUTHORITIES.
<br />ELECTRICAL NOTES
<br />i. ELECTRICAL COMRACTOR SHALL SUPPLY AND INSTALL ANY/ALL ELECTRICAL WORK INDICATED. ANY/ALL
<br />CONSTRUCTION SHALL BE IN ACCORDANCE W/DRAWINGS AND ANY/ALL APPLICABLE SPECIFlCATIONS. If ANY
<br />PROBLEMS ARE ENCOUNTERED BY COMPLYWG WITH THESE REQUIREMENTS, CONTRACTOR SHALL NOTIFY
<br />'CONSTRUCTION MANAGER' AS SOON AS POSSIBLE, AFTER THE DISCOVERY OF THE PROBLEMS, AND SHALL
<br />NOT PROCEED WITH THAT PORTION OF WORK, UNTIL THE 'CONSTRUCTION MANAGER' HAS DIRECTED THE
<br />CORRECTIVE ACTIONS TO BE TAKEN.
<br />2 ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND FAMILIARIZE HIMSELF WITH ANY/ALL CONDITIONS
<br />AFFECTING ELECTRICAL AND COMMUNICATION INSTALLATION AND MAKE PROVISIONS AS TO THE COST THEREOF.
<br />ALL EXISTING CONDITIONS OF ELECTRICAL EQUIP., LIGHT FIXTURES, ETC., THAT ARE PART OF THE FlNAL
<br />SYSTEM, SHALL 8E VEPoFlED BY THE CONTRACTOR, PRIOR TO THE SUBMITTAL OF HIS 810. FAILURE TO
<br />COMPLY WITH THIS PARAGRAPH WILI. IN NO WAY RELIEVE CONTRACTOR OF PERFORMING ALL WORK
<br />NECESSARY FOR A COMPLEfE AND WORKING SYSTEM.
<br />3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC AND ALL CODES
<br />AND LOCAL ORDINANCES OF THE LOCAL POWER & TELEPHONE COMPANIES HAVING JURISDICTION AND SHALL
<br />INCLUDED BUT NOT BE LIMITED T0:
<br />A. UL -- UNDERWRITERS LABORATORIES
<br />B. NEC - NATIONAL ELECTRICAL CODE
<br />C. NEMA -- NATIONAL ELECTRICAL MANUFACTURERS ASSOC.
<br />D. OSHA -- OCCUPATIONAL SAFEfY AND HEALTH ACT
<br />E IBC -- WTERNATIONAL BUILDING CODE
<br />F. NFPA - NATIONAL FIRE CODES
<br />4. DO NOT SCALE ELECTRICAL DRAWINGS, REFER TO SITE PLANS AND ELEVATIONS FOR E7(ACT LOCATIONS OF
<br />ALL EQUIPMENT, AND CONFIRM WITH 'CONSTRUCTION MANAGER' ANY SIZES AND AND LOCATIONS WHEN
<br />NEEDED.
<br />5. ExISTING SERVICES: CONTRACTOR SHALL NOT INTERRUPT E%ISTING SERVICES WITHOUT WRITTEN PERMISSION
<br />OF THE GDff.
<br />6. CONTRACTOR SHALL PAY FOR ANY/ALL PERMITS, FEES, WSPECTIONS AND TESTING CONTRACTOR IS TO
<br />OBTAIN PERMITS AND APPROVED SUBMITTALS PRIOR TO THE WORK BEGINNING OR ORDERING EqUIPMENT.
<br />7. THE TERM "PROVIDE" USED IN CONSTRUCTION DOCUMENTS AN� SPECIFICATIONS, INDICATES THAT THE
<br />CONTRACTOR SHALL FURNISH AND INSTALL.
<br />8. CONTRACTOR SHALL CONFlRM WITH LOCAL UTILIiY COMPANY ANY/ALL REQUIREMENTS SUCH AS THE: LUG
<br />SIZE RESTRICTIONS, CONDUIT ENTRY, SIZE OF TRANSFORMERS, SCHEDULED DOWNTIME FOR THE OWNERS'
<br />CONFIRMATION, ETC. ANY/ALL CONFLICTS SHALL BE BROUGHT TO THE ATfENTION OF THE CONSTRUCTION
<br />MANAGER, PRIOR TO BEGINNING ANY WORK.
<br />9. MINIMUM WIRE SIZE SHALL BE �J12 AWG, NOT INCLUDING CONTROL WIRING, UNLESS NOTED OTHERWISE. ALl
<br />CONDUCTORS SHALL BE COPPER WITH THWN INSULATION.
<br />10. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALlOY WITH THREADED HUBS IN
<br />WEf/DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS.
<br />11. IT IS N0T THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF THE CONSTRUCTION.
<br />CONTRACTOR IS El(PECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLEfE ELECTRICAL SYSTEM AND
<br />PROVIDE ALL RE�UIREMENTS FOR THE EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
<br />12. ELECTRICAL SYSTEM SHALL BE AS COMPLETELY AND EFFECTIVELY GROUNDED, AS REQUIRED BY
<br />SPECIFICATION, SET FORTH BY SPRWT.
<br />13. ALL WORK SHALL BE PERFORMED BY A LICENSED E�ECTRICAL CONTRACTOR IN A FIRST CLASS, WORKMAN�IKE
<br />MANNER. THE COMPLETED SYSTEM SHALL BE FULL OPERATNE ANO SUBJECT TO REGUL4TORY INSPECTION
<br />AND APPROVAL BY CONSTRUCTION MANAGER.
<br />14. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF
<br />CONSTRUCTION.
<br />15. CONTRACTOR SHALL GUARANTEE ANY/ALL MATERIALS AND WORK FREE FROM DEFECTS OR A PERIOD OF NOT
<br />LESS THAN TWO YEARS FROM DATE OF CUSTOMER'S ACCEPTANCE.
<br />16. THE CORRECTION OF ANY DEFECTS SHALI BE COMPLETED WITHOUT ANY ADDITIONAL CHARGE AND SHALI
<br />INCWDE THE REPLACEMENT OF THE REPAIR OF ANY OTHER PHASE OF THE INSTALLATION, WHICH MAY HAVE
<br />BEEN DAMAGED THEREIN WITHIN 48 HOURS.
<br />17. ADEQUATE AND REQUIREO LIABILIN INSURANCE SHALL BE PROVIDED FOR PROTECTION ACAINST PII6LIC LOSS
<br />AND ANY/ALL PROPERTY DAMAGE FOR THE DURATION OF WORK.
<br />18. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOxES, COVER PLATES AND DEVICES FOR ALL
<br />OUTLETS AS INDICATED.
<br />19. DITCHING AN� BACK FlLL CONTRACTOR SHALL PROVIDE FOR ALL UNDERGROUND WSTALLED CONDUIT AND/OR
<br />CABLES INCLUDING EXCAVATION AND BACKFlLLING AND COMPACTION. REFER TO NOTES AND REQUIREMENTS,
<br />EXCAVATION, AND BACKFILLING.
<br />20. MATERIALS, PRODUCTS AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW AND SHALL
<br />APPEAR ON THE LIST OF LLL APPROVED ITEMS AND $HALL MEET OR EXCEED THE REQUIREMENTS Of THE
<br />NEC, NEMA AND IEEE.
<br />21. CONTR4CTOR SHALL SUBMIT SHOP DRAWINGS OR MANUFACTURES CATALOG INFORMATION OF ANY/ALL
<br />LIGHTING FIXTURES, SWITCHES AND ALL OTHER ELECTRICAL ITEMS FOR APPROVAL BY THE CONSTRUCTION
<br />MANAGER PRIOR TO INSTALLATION.
<br />22. ANY CUTTING OR PATCHING DEEMED NECESSARY FOR ELECTRICAL WORK IS THE ELECTRICAL CONTRACTORS
<br />RESPONSIBILIN AND SHALL BE INCLUDED IN THE COST FOR WORK AND PERFORMED TO THE SATISFACTION
<br />OF THE 'CONSTRUCTION MANAGER' UPON FINAL ACCEPTANCE.
<br />23. THE ELECTRICAL CONTRACTOR SHALL LABEL ALL PANELS WITH ONLY NPEWRITTEN DIRECTORIES. ALL
<br />ELECTRICAL WIRING SHALL BE THE RESPONSIBILIT/ OF THE ELECTRICAL CONTR4CTOR.
<br />24. D�SCONNECT SWITCHES SHALL BE H.P. RATED HEAVY-DUTY, QUICK-MAKE AND OUICK-BREAK ENCLOSURES,
<br />AS REQUIRED BY EXPOSURE NPE.
<br />25. ALL CONNECTIONS SHALL BE MADE WITH A PROTECTIVE COATING OF AN ANTI-OXIDE COMPOUND SUCH AS
<br />"NO-OxIDE A" BY DEARBORNE CHEMICAL C0. COAT ALL WIRE SURFACES BEFORE CONNECTING. EXPOSED
<br />COPPER SURFACES, INCWDING GROUND BARS, SHALL BE TREATED - NO SUBSTITUTIONS.
<br />26. REACEWAYS: CONDUIT SHALL BE SCHEDULE 40 PVC MEETING OR EXCEEDING NEMA TC2 - 1990.
<br />CONTRACTOR SHALL PWG AND CAP EACH END OF SPARE ANO EMPN CONDUITS AND PROVIDE TWO
<br />SEPARATE PULL STRINGS - 200 L8S TEST POLYEfHYLENE CORD. ALL CONDWT BENDS SHALL BE A MINIMUM
<br />OF 2 fT. RADIUS. RGS CONDUITS WHEN SPEGRED, SHALL MEET UL-6 FOR GALVANIZED STEEL. ALL RTTINGS
<br />SHALL BE SUITABLE FOR USE WITH THREADED RIGID CONDUIT. COAT ALL THREADS WITH 'BRITE ZWC OR
<br />'GOLD CALV'.
<br />27. SUPPORT OF ALL ELECTRICAL WORK SHALL BE AS REQUIRED BY NEC.
<br />28. CONDUCTORS: CONTRACTOR SHALL USE 989, CONDUCTIVIN COPPER WITH TYPE THWN INSULATION, 600 VOLT,
<br />COLOR CODED. USE SOLID CONDUCTORS FOR WIRE UP TO AND INCLUDING N0. 8 AWG. USE STRANDED
<br />CONDUCTORS FOR WIRE ABOVE N0. 8 AWG.
<br />29. CONNECTORS FOR POWER CONDUCTORS: CONTRACTOR SHALL USE PRESSURE NPE INSULATE� TWIST-ON
<br />CONNECTORS FOR N0. 10 AWG AND SMALLER. USE SOLDERLESS MECHANICAL TERMINAL LUGS FOR N0. 8
<br />AWG AND LARGER.
<br />30. SERVICE 240/120V, SINGLE PHPSE, 3 WIRE CONNECTIONS AVAILABLE FROM UTILfTY COMPANY. OWNER OR
<br />OWNERS AGENT WILL APPLY FOR POWER.
<br />31. TELEPHONE SERVICE CONTRACTOR SHALL PROVIDE EMPN CONDUITS WITH MULE TAPE AS INDICATED ON
<br />DRAWINGS.
<br />32. ELECTRICAL AND TELCO RACEWAYS TO BE BURIED A MINIMUM OF 2' DEPTH.
<br />33. CONTRACTOR SHALL PLACE TWO LENGTHS OF WARNING TAPE AT A DEPTH OF 72" BELOW GROUND AND
<br />DIRECTLY ABOVE ELECTRICAL AND TELCO SERVICE CONDUITS. CAUTIONS TAPE TO READ "CAUTION BURIED
<br />ELECTRIC" OR "BURIED TELECOM".
<br />34. ALL BOLTS SHALL BE STAINLESS STEEL.
<br />ANTENNA & COAX NOTES
<br />1. VERIhY EACH COAXIAL CABLE LENGTH, DIAMETER, ROUTING, COLOR CODWG AND ALL APPURTENANCES WITH
<br />GDIT.
<br />2 THE M!J(IMUM COA7(IAL CABLE LENGTH AND CORRESPONDING COAXIAL CABLE DIAMEfER IS SHOWN ON SHEEf
<br />A-4. THIS CABLE LENGTH IS TO BE USED FOR FABRICATION OR CONSTRUCTION. ACTUAL ANTENNA CABLE
<br />LENGTH(S) MUST BE VERIFIED. COAXIAL CABLE SHALL BE PROVIDED BY GDIT.
<br />3. ALL COAX CABLES SHALL UTILIZE GROUND KITS, GROUNDED AS FOLLOWS:
<br />A. NEAR ANTENNA RAD CENTER ELEVATION,
<br />B. MIDDLE OF TOWER (MID-HEIGH OF ANTENNA), IF CABLE RUN IS OVER 200',
<br />C. BOTfOM OF TOWER,
<br />D. AT MASTER GROUND BAR 3'-0" FROM MMBS-BBU CABWE7
<br />THE WFORMATION CONTAWED IN THIS SET OF CONSTRUCTION �OCUMENTS IS PROPRIETARY BY NATURE ANY USE OR DiSCLOSURE OTHER THAN THAT WHICH RELATES i0 CARRIER SERVICES IS STRICTLY PROHIBITED.
<br />4. ALL TOP JUMPERS SHALL BE LENGTHS AS SHOWN AND INSTALLED BY CONTR4CTOR.
<br />5. ALL CABLES SHALL BE COLOR CODED AS SHOWN ON SHEEf RP-1 AND IN ACCORDANCE WITH SPRINT
<br />SPECIFICATIONS.
<br />6. BANDING SHALL BE IN ACCORDANCE WITH SHEEf A-4, RF-1 AND AS FOLLOWSt
<br />A. MAIN LINE COLOR BANDS SHALL BE 2" WIDE. MAINTAIN 1" SPACING BEfWEEN COLORS.
<br />B. FREQUENCY COLOR BANDS SHALL BE 2" WIDE WITH NO SPACE BEPNEEN COLORS.
<br />C. JUMPER COLOR BANDS SHALL BE 1" WIDE W(fH 1" SPACE.
<br />D. START COLOR &4NDS 2" BEYOND WEATHERPROOFING.
<br />E. START SELECTOR COLOR NEXT TO END CONNECTORS.
<br />7. FINAL COAxIAL ANTENNA CABLE SIZES SHALL BE DETERMINEO BY SAMSUNG RF ENGINEER. SEE ANTENNA
<br />SCHEDULE SHEET A-4. BASED ON FINAL CABLE RUN LENGTHS DEfERMINED BY GD.
<br />8. SEE CONSTRUCTION MANAGER FOR ANTENNA SUPPORT ASSEMBLY NPE.
<br />9. ALL COAXIAL CABLE WILL BE SECURED TO THE OESIGNED SUPPORT STRUCTURE AT �ISTANCES N0T TO EXCEED
<br />3' OR THE CABLE MANUFACTURES SPECIFlCATIONS WHICHEVER IS LESS, WITH HARDWARE SPECIFIED IN THE
<br />COAXIAL CABLE ROUTING DEfAILS OF THE SUPPLIED STRUCTURAL REPORT.
<br />10. PROVIDE AT LEAST 6" OF SIACK IN THE MAIN COAXIAL CABLES AT THE ANTENNA MOUNTING ELEVATION TO
<br />PROVIDE FOR FUTURE CONNECTOR REPLACEMENT.
<br />ANTENNA & HYBRID CABLE NOTES
<br />t. VERIFY EACH HYBRID CABLE LENGTH, ROUTING, DIAMETER, COLOR CODING AND ALL APPURTENANCES WITH GDIT.
<br />2 THE HYBRID CABLE AND DIAMEfER LENGTH IS SHOWN ON A-4. EXCESS CABLE LENGTHS TO BE DRESSED IN
<br />A MANNER APPROVED BY GDIT. CABLES CANNOT BE CUT TO FIT.
<br />3. HYBRID CABLE INTERNAL GROUND WIRE TO BE GROUNDED AT TOP AND BOTTOM PER SAMUSl1NGS (SPRINT)
<br />SPECIFICATIONS.
<br />4. EXCESS TOP 15' HYBRID CABLE FIBER JUMPERS TO BE DRESSED IN A MANNER APPROVED BY GDIT, CANNOT
<br />BE COILED, MUST BE SECURED TO WWER MOUNTS..
<br />5. ALL MAIN CABLES SHALL BE COLOR CODED AS SHOWN ON SHEEf RF-1 & IN ACCORDANCE WITH SPRINT
<br />SPECIFICATIONS.
<br />6. BANDING SHALL BE IN ACCORDANCE WITH SHEEf A-4, RF-1.
<br />A. MAM LME COLOR BANDS SHALL BE 2" WIDE MlilNTAIN 1" SPACING BEiWEEN.
<br />B. JUMPER COLOR BANDS SHALL BE 1" WIDE WITH 7" SPACE.
<br />C. START COLOR 8AND5 7' BEFORE MAIN CABLE END.
<br />Z FlNAL HYBRID CABLE SIZES SHALL BE DETERMINED BY SAMSUNG RF ENGWEER. SEE HYBRID CABLE SCHEDULE
<br />SHEET RF-1, BASED ON FINAL CABLE RUN LENGTHS DEfERMWED BY GDIT.
<br />8. ALL HYBRID CABLE WILL BE SECURED TO THE DESIGNED SUPPORT STRUCTURE AT DISTANCES NOT TO EXCEED
<br />3' HORIZONTALLY OR 4' VERTICALLY OR THE CABLE MANUFACTURER'S SPECIF�CATIONS WHICHEVER IS LESS, WITH
<br />HARDWARE SPECIFIED W THE HYBRID CABLE ROUTING DETAILS OF THE SUPPLIED STRUCTURAL SUPPORT.
<br />SITE WORK NOTES
<br />t. DO NOT EXCAVATE OR DISTURB BEYOND THE PROPERiY LWES OR LEASE LINES, UNLESS OiHERWISE NOTED.
<br />2. DO NOT SCALE BUILDING DIMENSIONS FROM DRAWING.
<br />3. SIZE, LOCATION AND NPE OF ANY UNDERGROUND UTILITIES OR IMPROVEMENTS SHALL BE ACCURATELY NOTEO
<br />AND PLACED ON AS-BUILT DRAWINGS BY GENERAL CONTRACTOR AND ISSUED TO ARCHITECT/ENGINEER AT
<br />COMPLETION OF PROJECT.
<br />4. ALL EXISTING UTILITIES, FAGLITIES, CONDITIONS AND THEIR DIMENSIONS SHOWN ON PLANS HAVE BEEN PLOTTE�
<br />FROM AVAILABLE RECORDS. THE ENGINEER AND OWNER ASSUME NOT RESPONSIBILITY WHATSOEVER !S TO THE
<br />SUFFICIENCY OR ACCURACY OF THE WFORMATION SHOWN ON THE PLANS OR THE MANNER OF THEIR REMOVAL
<br />OR ADJUSTMENT. CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING EXACT LOCATION OF ALL EXISTWG
<br />UTILITIES AND FACILITIES PRIOR TO SiART OF CONSTRUCTION. CONTRACTOR SHALL ALSO OBTAIN FROM EACH
<br />UTILITY COMPANY DETAILED INFORMATION RELATNE TO WORKING SCHEDULES AND METHODS OF REMOVING OR
<br />ADJUSTING EXISTING UTILITIES.
<br />5. CONTRACTOR SHALL VERIfY ALL EXISTING UTILITIES BOTH HORIZONTALLY AND VERTICALLY PRIOR TO START OF
<br />CONSTRUCTION. ANY DISCREPANCIES OR DOUBTS AS TO THE INTERPREfAT10N OF PLANS SHALL BE IMMEDIATELY
<br />REPORTED TO THE ARCHITECT/ENGINEER FOR RESOLUTION AND INSTRUCTION, AND NO FURTHER WORK SHALL
<br />BE PERFORMED UNTIL THE DISCREPANCY IS CHECKED AND CORRECTED BY THE ARCHITECT/ENGINEER. FAILURE
<br />TO SECURE SUCH INSTRUCTION MEANS CONTRACTOR WILL HAVE WORKED AT HIS/HER OWN RISK AND EXPENSE.
<br />6. CONTRACTOR SHALL CALL LOCAL DIGGER HOT LINE FOR UTILITY LOCATIONS 48 HOURS PRIOR TO START OF
<br />CONSTRUCTION.
<br />7. ALL NEW AND EXISTING UTILITY STRUCTURES ON SITE AND IN AREAS TO BE DISTURBEO BY CONSTRUCTION
<br />SHALL BE ADJUSTED TO FINISH ELEVATIONS PRIOR TO FINAL INSPECTION OF WORK.
<br />8. GRADING OF THE SITE WORK AREA IS TO 8E SMOOTH AND CONTINUOUS IN SLOPE AND IS TO FEATHER INTO
<br />EXISTING GRADES AT THE GRADING LIMITS.
<br />9. ALL TEMPORARY ExCAVATIONS FOR THE INSTALLATION OF FOUNDATIONS, UTILITIES, EfC., SHALL BE PROPERLY
<br />IAID BACK OR BRACED IN ACCORDANCE WITH CORRECT OCCUPATIONAL SAFEIY AND HEALTH ADMINISTRATION
<br />(OSHA) REQUIREMENTS.
<br />10. STRUCTURAL FILLS SUPPORTING PAVEMENTS SHALL BE COMPACTED TO 95% OF MAXIMUM STANDARD PROCTOR
<br />DRY DENSITY.
<br />11. NEW GRADES NOT IN BUILDING AND DRNEWAY IMPROVEMENT AREA TO BE ACHIEVED BY FILLING WITH APPROVED
<br />CLEAN RLL AND COMPACTED TO 95% OF STANDARD PROCTOR DENSfiY.
<br />12. ALL FILL SHAIL BE PL4CED IN UNIFORM LIFTS. THE LIFTS THICKNESS SHOULD NOT ExCEED THAT WHICH CAN
<br />BE PROPERLY COMPACTED THROUGHOUT ITS ENTIRE DEPTH WITH THE EQUIPMENT AVAILABLE.
<br />13. ANY FILLS PLACED ON EXISTING SLOPES THAT ARE STEEPER THAN 10 HORIZONTAL TO 1 VERTICAL SHALL BE
<br />PROPERLY BENCHE� INTO THE EXISTING SLOPE AS DIRECTEO BY A GEOTECHNICAL ENGWEER.
<br />14. CONTRACTOR SHALL CLEAN ENTIRE SITE DAILY AFTER CONSTRUCTION SUCH THAT NO PAPERS, THRASH, WEEDS,
<br />BRUSH OR ANY OTHER DEPOSRS WILL REMAIN. ALL MATERIALS COLLECTED DURING CIEANING OPERATIONS
<br />SHALL BE DISPOSED OF OFF-SITE BY THE GENERAL CONTRACTOR.
<br />15. ALL TREES AND SHRUBS WHICH ARE NOT IN DIRECT CONFILICT WITH THE IMPROVEMENTS SHALL BE PROTECTED
<br />BY THE GENER4L CONTR4CTOR.
<br />16. ALL SITE WORK SHALL BE CAREFULLY COORDINATED BY GENERAL CONTRACTOR WITH LOCAL UTILIN COMPANY,
<br />TELEPHONE COMPAY. AND ANY OTHER UTILIlY COMPANIES HAVING JURISDICTION OVER THIS LOCATION.
<br />Sprint�
<br />GENERAL DYNAMICS
<br />WIRELESS SERVICES
<br />=;r �; :, ; KDC
<br />t�� �! F, i ARCHII'ECTS.ENGINEERS, P.C.
<br />�730 300fH S711EFf SW SIME 300
<br />�� fl �� � LYNNNRIOD.WI19Y136
<br />��� ��. �i � FA� 4u25J612. &�6
<br />PROJECT NFOR�'�1ATI01�:
<br />N[l1A'ORK VISION 1v1MRS LAIINCI I
<br />EVERGREEN WAY
<br />SE54XC102
<br />6515 MORGAN ROAD
<br />EVERETT, WA. 98203
<br />SNOHOMISH COUNTY
<br />iaSUEi�A1e 1 1 -08-1 2
<br />i�uF�roR:CONSTRUCTION DWGS
<br />REVISIONS
<br />REV. DATE OESCRIPTION INITIALS
<br />A 07/OS/12 ISSUED FOR CONSTRUCTABILITY REVIEW yyqg
<br />B OS/08/12 ISSUED FOR 90% CD REVIEW yyAg
<br />C 08/31/12 i55UED FOR 100% CD REVIEW WAS
<br />D 10/26/121SSUED POR PRELIM.100� CD REVIEW ET
<br />E il/08/121SSUED FOR FINAL 100% CD ET
<br />NOT FOR CONSTRUCTION UNLESS
<br />LABELED AS CONSTRUCTION SET
<br />LIC:EVSUR�
<br />5773 REGISTERED
<br />AR ITEC
<br />KENN TH . C�AMP
<br />STATE OF WASHINGTON
<br />SHGE"1 "ITILE:
<br />GENERAL N OTES
<br />SHELCE NUMHLR: REVItiION:
<br />N-1 E
<br />122168
<br />
|