FOUNDATION, EXCAVATION AND BACKFILL NOTES <br />1. ALL FINAL GRADED SLOPES SHALL BE A MAXIMUM OF 3 HOPo20NTAL TO 1 VERTICAL. <br />2. ALL EXCAVATIONS PREPARED FOR PLACEMENT OF CONCREfE SHALL BE OF UNDISTURBED SOILS, <br />SUBSTANTIALLY HORIZONTAL AND FREE FROM ANY LOOSE, UNSUITABLE MATERIAL OR FROZEN SOILS, AND <br />WITHOUT THE PRESENCE OF POUNDING WATER. DEWATERING FOR EXCESS GROUNO WATER SHALL BE <br />PROVIDED WHEN REQUIRED. COMPACTION OF SOILS UNDER CONCREfE PAD FOUNDATIONS SHALL NOT BE IESS <br />THAN 95% OF THE MODIFIED PROCTOR MN(IMUM DRY DENSIN FOR THE SOIL IN ACCORDANCE WITH ASTM <br />D1557. <br />3. CONCRETE FOUNDATIONS SHALL NOT BE PLACED ON ORGANIC OR UNSUITABLE MATERIAL IF INADEQUATE <br />BEARING CAPACIN IS REACHEO AT THE DESIGNEO EXCAVATION DEPTH, THE UNSATISFACTORY SOIL SHALL BE <br />EXCAVATED TO ITS FULL DEPTH AND EITHER BE REPLACED WITH MECHANICALLY COMPACTED GRANULAR <br />MATERIAL OR THE EXCAVATION SHALI BE FlLLED WITH CONCRETE OF THE SAME IYPE SPECIFlED FOR THE <br />FOUNDATION. CRUSHED STONE MAY BE USED TO STABILIZE THE BOTTOM OF THE EXCAVATION. ANY STONE <br />SUB BASE MATERIAL, IP USED, SHALL NOT SUBSTITUTE FOR REQUIRED THICKNE55 OF CONCRETE. <br />4. ALL EXCAVATIONS SHALL BE CLEAN OF UNSUITABLE MATERIAL SUCH AS VEGETATION, TRASH, DEBRIS, AND SO <br />FORTH PRIOR TO BACK FILLING. BACK FILL SHALL CONSIST OF APPROVED MATERIALS SUCH AS EARTH, LOAM <br />SANDY CLAY, SAND AND CRAVEL, OR SOfT SHALE, FREE FROM CLODS OR LARGE STONES OVER 2 1/2" MAX <br />DIMENSIONS. ALL BACK FILL SHALL BE PLACED IN COMPACTED LAYERS. <br />5. ALL FILL MATERIALS AND FOUNDATION BACK FlLL SHALL BE PLACE� MAXIMUM 6" THICK LIFTS BEFORE <br />COMPACTION. EACH LIFT SHALL BE WETTED IF REQUIRED AND COMPACTED TO NOT LESS THAN 95Y, OF THE <br />MODIRED PROCTOR MAXIMUM DRY DENSITY FOR SOIL IN ACCORDANCE WITH ASTM D1557. <br />6. NEWLY PLACED CONCRETE FOUNDATIONS SHALL CURE A MINIMUM OF 72 HRS PRIOR TO BACK FILLING. <br />7. FINISHEO GRADING SHALL BE SLOPED TO PROVIDE POSITIVE DRAINAGE AND PREVENT STANDING WATER. THE <br />FINAL (FINISH) ELEVATION OF SLAB FOUNDATIONS SHALL SLOPE AWAY IN ALL DIRECTIONS FROM THE CENTER. <br />FINISH GRADE OF CONCREfE PADS SHALL BE A MN(IMUM OF 4 INCHES ABOVE FINAL FINISH GRADE <br />ELEVATIONS. PROVIDE SURFACE FILL GRAVEL TO ESTABLISH SPECIFlED ELEVATIONS WHERE REQUIREO. <br />8. NEWLY GRADED SURFACE AREAS TO RECENE GRAVEL SHALL BE COVERED WITH GEOTEXTILE FABRIC TYPE: <br />iYPAR-3401 AS MANUFACTURED BY "CONSTRUCTION MATERIAL 1-800-239-3841" OR AN APPROVED <br />EQUIVALENT, SHOWN ON PLANS. THE GEOTEXTILE FABRIC SHALL BE BL4CK IN COLOR TO CONTROL THE <br />RECURRENCE OP VEGEfATIVE GROWTH AND EXTEND TO WITHIN 1 FOOT OUTSIDE THE SITE FENCING OR <br />ELECTRICAL GROUNDING SYSTEM PERIMETER WHICH EVER IS GREATER. ALL FABRIC SHALL BE COVERED WITH <br />A MINIMUM OF 4" DEEP COMPACTED STONE OR GRAVEL AS SPECIFlED. LE FDOT NPE No. 57 FOR FENCED <br />COMPOUND; FDOT NPE No. 67 POR ACCESS DRIVE AREA. <br />9. IN ALL AREAS TO RECENE FILL, REMOVE ALL VEGEfATION, TOPSOIL, DEBRIS, WET AND UNSATISFACTORY SOIL <br />MATERIALS, OBSTRUCTIONS, AND DELETERIOUS MATERIALS FROM GROUND SURFACE. PLOW STRIP OR BREAK <br />UP SLOPED SURFACES STEEPER THAN 1 VERTICAL TO 4 HORIZONTAL SUCH THAT FILL MATERIAL WILL BIND <br />WITH EXISTING/PREPARE� SOIL SURFACE. <br />10. WHEN SUB GRADE OR PREPARED GROUND SURFACE HAS A DENSITY LESS THAN THAT REQUIRED FOR THE <br />FlLL MATERIAL, SCARIFY THE GROUND SURFACE TO DEPTH REQUIRED, PULVERIZE, MOISTURE-CONDITION <br />AND/OR AERATE THE SOILS AND RE-COMPACT TO THE REOUIRED DENSIN PRIOR TO PLACEMENT OF FILLS. <br />11. IN AREAS WHICH EXISTING GRAVEL SURFACING IS REMOVED OR DISTURBED DURWG CONSTRUCTION <br />OPERATIONS, REPLACE GRAVEL SURFACING TO MATCH ADJACENT GRAVEL SURFACING AND RESTORED TO THE <br />SAME THICKNESS AND COMPACTION AS SPECIFIED. ALL RESTORED GRAVEL SURFACING SHALL BE FREE FROM <br />CORRUGATIONS AND WAVES. <br />12 EXISTING GRAVEL SURFACING MAY BE EXCAVATED SEPARATELY AND REUSED WITH THE CONDIT�ON THAT ANY <br />UNFAVORABLE AMOUNTS OF ORGANIC MATfER, OR OTHER DELEfERIOUS MATERIALS ARE REMOVED PRIOR TO <br />REUSE. FURNISH ANY ADDITIONAL GRAVEL RESURFACING MATERIAL AS NEEDED TO PROVIDE A FULL DEPTH <br />COMPACTED SURFACE THROUGHOUT SITE. <br />13. GRAVE� SUB SURFACE SHALL BE PREPARED TO REQUIRED COMPACTION AND SUB GRADE ELEVATIONS BEFORE <br />GRAVE� SURFACING IS PLACED AND/OR RESTORED. ANY LOOSE OR DISTURBED MATERIALS SHALL BE <br />THOROUGHLY COMPACTED AND ANY DEPRESSIONS IN TNE SUB GRADE SHALL BE FILLED AND COMPACTED <br />WITH APPROVED SELECTED MATERIAL GRAVEL SURFACING MATERIAL SHALL NOT BE USED FOR FlLLING <br />DEPRESSIONS IN THE SUB GR4DE. <br />14. PROTECT EXISTING GRAVEL SURFACING AND SUB GRADE IN AREAS WHERE EOUIPMENT LOADS WILL OPERATE. . <br />15. DAMAGE TO EXISTING STRUCTURES AN�/OR UTILITIES RESULTING FROM CONTRACTORS NEGLIGENCE SHALL BE <br />REPNRED AND/OR REPL4CED TO THE OWNERS SATISFACTION AT NO ADDITIONAL COST TO THE CONTRACT. <br />16. ALL SUITABLE BORROW MATERIAL FOR &4CK FILL OF THE SITE SHALL BE INCLUDED IN THE BID. EXCESS <br />TOPSOIL AND UNSUITABLE MATERIAL SHALL BE DISPOSED OF OFF SITE AT LOCATIONS APPROVED BY <br />GOVERNING AGENCIES AT NO ADDITIONAL COST TO THE CONTRACT. <br />ENVIRONMENTAL NOTES <br />1. ALL WORK PERFORMED SHALL BE DONE IN ACCORDANCE WITH ISSUED PERMITS. THE CONTRACTOR SHALL 8E <br />RESPONSIBLE FOR PAYMENT OF FINES AND PROPER CLEAN UP FOR AREAS IN VIOLATION. <br />2 CONTRACTOR AND/OR DEVELOPER SHALL BE RESPONSIBLE FOR CONSTRUCTION AND MAIMENANCE OF EROSION <br />AND SEDIMENTATION CONTROLS DURING CONSTRUCTION FOR PROTECTION OF A�JACENT PROPERTIES, ROADWAYS <br />AND WATERWAYS AND SHALL BE MAINTAINED IN PLACE THROUGH FINAL JURISDICTIONAL INSPECTION & RELEASE <br />OF SITE. <br />3. CONTRACTOR SHALL INSTALL/CONSTRUCT ALL NECESSARY SEDIMENT/SILT CONTROL FENCWG AN� PROTECTIVE <br />MEASURES WITHIN THE IIMITS OP SITE DISTURBANCE PRIOR TO CONSTRUCTION. <br />4. NO SEDIMENT SHALL BE ALLOWED TO EXIT THE PROPERTY. THE CONTRACTOR IS REPSONIBLE FOR TAKING <br />ADEQUATE MEPSURES FOR CONTROLLING EROSION. ADDITIONAL SEDIMENT CONTROL FENCING MAY BE REQUIRED <br />IN ANY AREAS SUBJECT TO EROSION. <br />5. THE CONTR4CTOR IS RESPONSIBLE FOR MAWTAINING POSITNE DRAINAGE ON THE SITE AT ALL TIMES WITH SILT <br />AND EROSION CONTROL MEASURES MAINTAINED ON THE DOWNSTREAM SIDE OF SITE DRAINAGE. ANY DAMAGE TO <br />ADJACENT PROPERTY AS A RESULT OF EROSION WILL 8E CORRECTED AT THE CONTRACTORS EXPENSE. <br />6. CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY INSPECTIONS AND ANY REPAIRS OF ALL SEDIMENT CONTROL <br />MEASURES INCLUDING SEDIMENT REMOVAL AS NECESSARY. <br />7. CLEARING OF VEGEfATION AND TREE REMOVAL SHALL 8E ONLY AS PERMITTED AND BE HELD TO A MINIMUM. <br />ONLY TREES NECESSARY FOR CONSTRUCTION OF THE FACILITIES SHALL BE REMOVED. <br />8. SEEDING SAND MULCHING AND/OR SODDING OF THE SITE WILL BE ACCOMPLISHED AS SOON AS POSSIBLE <br />AFTER COMPLETION OF THE PROJECT FACILITIES AFFECTING LAND DISTURBANCE. <br />9. CONTRACTOR SHALL PROVIDE ALL EROSION AND SEDIMENTATION CONTROL MEASURES AS REQUIRED 8Y LOCAL, <br />COUNN AND STATE CODES AND ORDINANCES TO PROTECT EMBANKMENTS FROM SOIL LOSS AND TO PREVENT <br />ACCUMULATION OF SOIL AND SILT IN STREAMS AND DRAINAGE PATHS LEAVING THE CONSTRUCTION AREA. THIS <br />MAY INCLUDE SUCH MEASURES AS SILT FENCES, STRAW BALE SE�IMENT BARRIERS, AND CHECK DAMS. <br />10. RIP RAP OF SIZES INDICATED SHALL CONSIST OF CLEAN, HARD, SOUND, DURABLE, UNIFORM IN QUALIN STONE <br />FREE OF ANY DEfRIMENTAL QUANTIN OF SOFT, FRIABLE, THIN, ELONGATED OR LAMINATED PIECES, <br />DISINTEGRATED MATERIAL, ORGANIC MATTER, OIL, ALKALI, OR OTHER DELETERIOUS SUBSTANCES. <br />STRUCTURAL STEEL NOTES <br />1. ALL STEEL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC MANUAL OF STEEL <br />CONSTRUCTION. STEEL SECTIONS SHALL BE IN ACCORDANCE WITH ASTM AS INDICATED BELOW: <br />W-SHAPES: ASTM A992, 50 KSI <br />ANGLES, BARS CHANNELS: ASTM A36, 36 KSI <br />HSS SECTIONS' ASTM 500, 46 KSI <br />PIPE SECTIONS: ASTM A53-E, 35 KSI <br />2 ALL EXTERIOR EXPOSED STEEL AND HARDWARE SHALL BE HOT DIPPED GALVANIZED. <br />3. ALL WELDING SHALL BE PERFORMED USING E70XX ELECTRODES AND WELDING SHALL CONFORM TO <br />AISC. WHERE FILLET WEID SIZES ARE NOT SHOWN, PROVIDE THE MINIMUM SIZE PER TABLE J2.4 IN <br />THE AISC "MANUAL OF STEEL CONSTRUCTION". PNNTED SURFACES SHALL BE TOUCHED UP. <br />4. NON-STURCUTRAL CONNECTIONS FOR STEEL GRATING MAY USE 5/8"0 ASTM A 307 BOLTS UNLESS <br />NOTED OTHERWISE.. <br />5. FIELD MODIFICATIONS ARE TO BE COATED WITH ZINC ENRICHED PAINT. <br />ONCRETE MASONRY NOTES <br />1. CONCRETE MASONRY UNITS SHALL BE MEDIUM WEIGHT UNITS CONFORMING TO ASTM C90, GW\DE N-i, <br />(F'M=1,500 PS). MEDIUM WEIGHT (115 PCF). <br />2. MORTAR SHALL BE TYPE "S" (MINIMUM 1,800 PSI AT 28 DAYS). <br />3. GROUT SHALL HAVE A MINIMUM COMPRESSNE STRNGTH OF 3,000 PSI AT 28 DAYS. <br />4. ALL CELLS CONTAINING REWFORCING STEEL OR EMBE�DED ITEMS AND ALL CELLS IN RETAINING WALLS <br />AND WALLS BELOW GRADE SHALL BE SOLID GROUTED. <br />5. A�L HOR�ZONTAL REWFORCEMENT SHALL BE PLACED IN BOND BEAM OR LINTEL BEAM UNITS. <br />6. WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL CONSTRUCTION JOINTS SHAL� <br />BE FORMED BY STOPPING THE GROUT POUR 1-t/2" BELOW TOP OF THE UPPERMOST UNIT. <br />7. ALL BOND BEAM BLOCK SHALL BE "DEEP CUT" UNITS. <br />B. PROVIDE WSPECTION AND CLEAN-OUT HOLES AT BASE OF VERTICAL CELLS HAVING GROUT LIFTS IN <br />EXCESS OF 4'-0" OF HEIGHT. <br />9. ALL GROUT SHALL BE CONSOLIDATED WITH A MECHANICAL VIBRATOR. <br />10. CEMENT SHALL BE AS SPECIFIED FOR CONCRETE. <br />11. REWFORCING BARS - SEE NOTES UNDER "STRUCTURAL CONCRETE NOTES" FOR REQUIREMENTS. <br />12. PROVIDE ONE BAR DIAMETER (A MINIMUM OF 1/2') GROUT BER4EEN MAIN REWFORCING AND MASONRY <br />UNITS. <br />13. LOW LIfT CONSTRUCTION, MAXIMUM GROUT POUR HEIGHT IS 4 FEEf. <br />14. HIGH UfT GROUTED CONSTRUCTION MAY BE USED IN CONFORMANCE W�TH PROJECT SPECIFICATIONS <br />AND SECTION 2104.6.1 OF U.B.C. <br />15. ALL CELLS IN CONCREfE BLOCKS SHA�L BE FILLED SOLID WITH GROUT, E%CEPT AS NOTEED IN THE <br />DRAWINGS OR SPECIFICATIONS. <br />16. CELLS SHALL BE IN VERTICAL ALIGNMENT, DOWELS IN FOOTINGS SHALL BE SET TO ALIGN WITH CORES <br />CONTAINING REINFORCING STEEI. <br />17. REFER TO ARCHITECTURAL DRAWINGS FOR SURFACE AND HEIGHT OF UNITS, LAYING PATTER AND JOINT <br />NPE. <br />18. SAND SHALL BE CLEAN, SHARP AND WELL GR4DED, FREE FROM INJURIOUS AMOUNTS OF DUST, WMPS, <br />SHALE, ALKAU OR ORGANIC MATERIAL. <br />19. BRICK SHALL CONFORM TO ASTM C-62 AND SHALL BE GRADE MW OR BETTER. <br />STRUCTURAL CONCRETE NOTES <br />1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACi 301-05, ACI 318-05 AND THE <br />SPECIFICATION FOR CAST-IN-PIACE CONCREfE. <br />2. ALL CONCREfE SHALL HAVE A MINIMUM COMPRESSNE STRENGTH fc'=3,000 PSI AT 28 DAYS UNLESS <br />NOTED OTHERWISE. <br />3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60, DEFORMED UNLESS NOTED <br />OTHERWISE. WEIDED WIRE FABRIC SHALL CONFORM TO ASTM A 185 WELDED STEEL WIRE FABRIC <br />UNLESS NOTED OTHERWISE SPLICES CLASS "B" AND ALL HOOKS SHALL BE STANDARD UNLESS NOTED <br />OTHERWISE. <br />4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS <br />SHOWN OTHERWISE ON DRAWINCS: <br />CONCRETE CAST AGAWSi EARTH ...............3 IN. <br />CONCRETE EXPOSED TO EARTH OR WEATHER: <br />�'6 AND LARGER ...............2 IN. <br />�5 AND SMALLER & WWF ...............t 1/2 IN. <br />CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT CAST AGNNST THE GROUND: <br />SLAB AND WALL ...............3/4 IN. <br />BEAMS AND COWMNS ...............1 1/2 IN. <br />5. A 3/4" CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE U.N.O.IN ACCORDANCE <br />WITH ACI 301 SECTIDN 42.4 <br />6. HOLES TO RECEIVE EXPANSION/WEOGE ANCHORS SHALL BE 1/8" LARGER IN DIAMEfER THAN THE <br />ANCHOR BOLT, DOWEL OR ROD AND SHALL CONFORM TO MANUFACTURER'S RECOMMENDATION FOR <br />EMBEDMENT DEPTH OR AS SHOWN ON THE DRAWINGS. LOCATE AND AVOID CUTfING EXISTING REBAR <br />WHEN DRILLING HOLES W ELEVA7ED CONCRETE SLABS. <br />7. USE AND WSTALLATION OF CONCRETE EXPANSION/WEDGE ANCHOR, SHALL BE PER ICBO & <br />MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURES. <br />THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARPoER SERVICES IS STRICTLY PROHIBITEO. <br />WEATHERPROOFING NOTES <br />STANDARD CONSTRUCTION SPECIFICATIONS FOR WIRELESS SITES <br />3.6 WEATHERPROOFING CONNECTORS AND GROUND KITS: <br />w ALL CONNECTORS AND GROUND KITS SHALL BE WEATHERPROOFED USING BUNL RUBBER <br />WEATHERPROOFING AND TAPE. THIS INSTALLATION MUST BE DONE IN ACCORDANCE WITH THE <br />MANUFACTURER'S RECOMMENDATION OR AS SHOWN ON THE CONSTRUCTION DRAWINGS (WHICHEVER IS <br />GREATER). IF NO DIRECTION IS PROVIDED, WEATHERPROOFING MUST BE �ONE PER THE FOLLOWING <br />INSTRUCTIONS. <br />1. THE COAXIAL CABLE CONNECTION OR GROUND KIT CAN BE ENCOMPASSED INTO COLD SHRINK AND <br />COMPLETEIY WRAPPED WITH 2 INCH WIDE ELECTRICAL TAPE OVERLAPPING EACH ROW BY <br />APPROXIMATELY �" AND EXTENDING PAST THE CONNECTION BY PNO INCHES AS DISCUSSED BELOW; OR <br />2. THE CON(IAL CABLE CONNECTION OR GROUND KR CAN BE WRAPPED WITH LAYERS OF <br />ELECTRICAL/BUiYL RUBBER/ELECTRICAL TAPE AS DISCUSSED BELOW; OR <br />3. THE COAXIAL CABLE CONNECTION OR GROUND KIT CAN BE WRAPPED WITH iW0 LAYERS OF 1.5 INCH <br />WIDE SELF-AMALGAMATWG TAPE COVERED WITH TNO LAYERS OF ELECTRICAL TAPE AS DISCUSSED <br />BELOW. <br />e. COLD SHRINK INSTALLATION PROCEDURE: <br />1. REQUIRED MATERIAL: COLD SHRINK TUBE, SPACERS AS NEEDED, BLACK ELECTRICAL TAPE-2 INCHES <br />WIDE <br />2. REQUIRED TOOLS: KNIFE AND TAPE MEASURE <br />STEP 1: THOROUGHLY CLEAN AND DRY THE SURFACE OF COAXIAL CABLE AND CONNECTOR TO REMOVE <br />ALL GREASE AND DIRT. MARK THE MNN FEED (LARGER DIAMEfER) COAXIAL CABLE AT LEAST TWO <br />INCHES ABOVE THE CONNECTION AS THE SPECIFIED START DIMENSION FOR THE COLD SHRINK. <br />STEP 2: SLIDE THE COLD SHRINK TUBE OVER THE PRE-CONNECTORIZED END OF THE LARGER <br />DIAMETER COAXIAL CABLE PRIOR TO MATING CONNECTOR WTERFACES. MAKE THE CONNECTION. <br />STEP 3: REMOVE WAX PAPER FROM A SPACER HALF AND PRESS ONTO CON(IAL CABLE DIRECTLY <br />BEHIND THE CONNECTOR. REMOVE THE WAX PAPER FROM THE OTHER SPACER HALF AND ALIGN THE <br />TWO SPACER HALVES WITH ADHESIVE PORTIONS FACING EACH OTHER. PRESS THE SPACER HALVES <br />TOGEfHER. THE SPACER WILL BE PLACED NEXT TO THE CONNECTOR ON THE SMALLER DIAMEfER <br />COA%IAL CABLE SIDE. <br />STEP 4: SLIDE THE COLD SHRINK TUBE OVER THE CONNECTION TO THE SPECIFIED START DIMENSION <br />MARK. HOLD THE COLD SHRWK TUBE AND COAXIAL CABLE IN ONE HAND 50 THAT THE EDGE OF COLD <br />SHRINK TUBE IS IN LINE WITH THE MARK. <br />STEP 5: WITH YOUR FREE HAND, BEGIN REMOVWG COLD SHRINK TUBE CORE. THE CORE WILL BE <br />REMOVED BY UNWINDING IN A COUNTERCLOCKW6E DIRECTION WHILE LIGHTLY PULLING THE ATTACHED <br />CORD AWAY FROM THE TUBE. <br />STEP 6: USE BOTH HANDS TO CONTINUE THE UNWINDING PROCESS AS THE COLD SHRINK TUBE BEGINS <br />TO COLlAPSE INTO POSITION. CONTINUE THE UNWINDING PROCE55 UNTIL THE CORE IS COMPLETELY <br />REMOVED AND THE COLD SHRINK TUBE IS INSTALLED. <br />STEP 7: EXCESS COLD SHRINK TUBE EXTENDING TWO INCHES BEYOND THE SPACER HALVES CAN BE <br />REMOVED OR LEFT IN PLACE. EXCESS COLD SHRINK TUBE CAN BE CAREFULLY CUT OFF WITH A KNIFE. <br />STEP 8: WRAP OVER THE COLD SHRINK TUBE WITH ONE LAYER OF BLACK ELECTRICAL TAPE 2 INCH <br />WIDTH OVERIAPPING EACH ROW BY 1/2 INCH. THIS TOP LAYER MUST BE WRAPPED USING A SHINGLED <br />EFFECT. THE LAYER SHALL BE WRAPPED SO THAT THE ENDS ARE IN THE UPWARD DIRECTION CREATING <br />A SHINGLEO EFFECT WffH THE TAPE SO WATER WILL BE REPELLED AND NOT ALLOWED TO COLLECT AND <br />POOL THIS TOP LAYER OF ELECTRICAL iAPE MUST EXTEND iW0 INCHES (THE TAPE WIDTH) PAST THE <br />COLD SHRINK TUBE ONTO THE UNDERLYING CABLE. TAPE SHALL BE WRAPPED SO THAT NO VOIDS OR <br />AIR PACKETS ARE PRESENL TAPE SHALL BE CUT WITH A SHARP KNIfE. <br />C. BUNL RUBBER TAPE INSTALLATION PROCEDURE: <br />1. REQUIRED MATERIAL BLACK ELECTRICAL TAPE-2 INCH WIDE AND BUNL RUBBER TAPE 2 TO 3 INCHES <br />WIDE. <br />2. REQl11RE0 TOOLS: KNIFE OR SCISSORS. <br />STEP 1: THOROUGHLY CLEAN AND DRY THE SURFACE OF COAXIAL CABLE AND CONNECTOR TO REMOVE <br />ALL GREASE AND DIRT. WRAP CONNECTOR/GROUND KIT WITH iW0 LAYERS OF BLACK ELECTRICAL <br />TAPE-2 INCH WIDTH OVERLAPPING EACH ROW BY APPROXIMATELY 1/2 INCH. THESE LAYERS OF TAPE <br />MUST 8E WRAPPED TIGHT ENOUGH SO THAT NO VOIDS OR NR PACKEfS ARE PRESENT AND MUST <br />EXTEND ONE WCH PAST THE CONNECTOR/GROUN� KIT ON EACH SIDE.'(WO ROWS SHALL BE APPLIED, <br />ONE IN EACH DIRECTION, WITH THE TOP ROW SHINGLED TO PROMOTE WATER RUNOFF. <br />STEP 2: WRAP CONNECTOR/GROUND KIT WITH ONE LAYER OF BUNL RUBBER TAPE (2 TO 3 INCHES <br />WIDTH) OVER THE BLACK ELECTRICAL TAPE OVERLAPPING EACH ROW BY APPROXIMATELY 1/2 INCH. THE <br />BUNL R1188ER TAPE MUST EXTEND 2 TO 3 INCHES (THE TAPE WIDTH) PAST THE ELECTRICAL TAPE <br />AND COME IN GOOD CONTACT WIiH THE UNDERLYING CABLE ON CONNECTORS, WHEN <br />WEATHERPROOFING FROM THE MAtN LWE TO THE JUMPER, BUILD UP THIS AREA WITH EXTRA BUTYL <br />RUBBER TAPE TO INSURE A SMOOTH TRANSITION FREE OF VOIDS AND AIR PACKETS DOWN TO THE <br />SMALLER �IAMEfER CABLE. <br />STEP 3: WRAP CONNECTOR�GROUND KIT WITH iW0 LAYERS OF BLACK ELECTRICAL TAPE 2 INCH WIDTH <br />OVERLAPPING EACH ROW BY 1 INCH. THESE LAST 1W0 LAYERS MUST BE WRAPPED USING A SHING�EO <br />EFFECT. THE TOP LAYER SHALL BE WR4PPED SO THAT THE ENDS ARE IN THE UPWARD DIRECTION <br />CREATING A SHINGLED EFFECT WITH THE TAPE SO WATER WILL BE REPELLED AND NOT ALLOWED TO <br />COLLECT AND POOL THESE TOP LAYERS OF ELECTRICAL TAPE MUST EXTEND TWO INCHES (THE TAPE <br />WIDTH) PAST THE BUNL RUBBER TAPE ONTO THE UNDERLYING CABLE. <br />ALL LAYERS OF TAPE SHALL BE WRAPPEO 50 THAT NO VOIDS OR AIR PACKEiS ARE PRESENT. THE <br />LAST WR4P OF TAPE SHALL NOT BE PULLED OR STREfCHED. ALL TAPE SHALL BE CUT WITH A SHARP <br />KNIFE OR SCISSORS. <br />0. SELF-AMALGAMATING TAPE INSTALLATION PROCEDURE: <br />1. REQUIREO MATERIAIL SELF-AMALGAMATING TAPE -1.5 INCHES WIDE AND BLACK ELECTRICAL TAPE - 2 <br />INCHES WIDE. <br />2. REQUIRED TOOLS: KNIFE OR SCISSORS. <br />STEP 1: THOROUGHLY CLEAN AND DRY THE SURFACE OF COAXIAL CABLE AND CONNECTOR TO REMOVE <br />ALL GREASE AND DIRT. <br />STEP 2: START WRAPPING SELF-AMALGAMATMG TAPE ON THE CABLE AT LEAST 2 WCHES FROM THE <br />CONNECTOR/GROUND KIT. MAKE SURE TAPE IS STRETCHED TIGHT DURING THIS APPLICATION. <br />STEP 3: WHILE STRETCHING TAPE, MAKE ONE WRAP OF THE TAPE AROUND THE CABLE, MAKING SURE <br />THE TAPE IS WRAPPED ONTO ITSELF. THE TAPE WILL ONLY ADHERE TO ITSELF. <br />STEP 4: CONTINUE WRAPPING THE CABLE AND CONNECTOR/GROUND KIT USING HALF OVERL4P (0.75 <br />INCH WIDE) LAYERS. <br />STEP 5: WRAP OVER AND PAST THE CONNECTOR/GROUND KIT AT LEAST 2 INCHES. <br />STEP 6: TO TERMINATE THE SELF-AMALGAMATING TAPE, WRAP THE TAPE AT LEAST ONE FULL ROUND <br />OVER THE CABLE STREfCHING THE TAPE TIGHT. CUT THE TAPE USING KNIFE OR SCISSORS AND APPLY <br />THE LOOSE END TO THE UNDERLYING SELF-AMALGAMATING TAPE USING THUMB PRESSURE. <br />STEP 7: TWO ROWS OF SELF-AMALGAMATING TAPE SHALI BE APPLIED IN THIS MANNER, IN A�TERNATMG <br />DIRECTIONS. THE TOP LAYER SHALL 8E WRAPPED SO THAT THE ENDS ARE IN AN UPWARD DIRECTION <br />CREATING A SHINGLED EFFECT WITH THE TAPE SO WATER WILL BE REPELLED. <br />STEP 8: WRAP OVER SELF-AMALGAMATWG TAPE WITH TWO LAYERS OF BLACK ELECTRICAL TAPE- 2 <br />INCH WIDTH OVERLAPPING EACH ROW BY 1 INCH. THESE TOP TWO LAYERS MUST ALSO BE WR4PPED <br />USING A SHINGLED EFFECT. THE LAYERS SHALL BE WRAPPED 50 THAT THE ENDS ARE IN THE UPWARD <br />DIRECTION CREATING A SHINGLED EFFECT WITH THE TAPE SO WATER WILL BE REPELLED AND NOT <br />ALLOWED TO COLLECT AND POOL THESE TOP L4YER5 OF ELECTRICAL TAPE MUST EXTEND 'IWO WCHES <br />(THE TAPE WIDTH) PAST THE SELF-AMALGAMATING TAPE ONTO THE UNDERLYING CABLE. ALL LAYERS OF <br />TAPE SHALL BE WRAPPEO SO THAT NO VOIDS OR AIR PACKEfS ARE PRESENT. THE LAST WRAP OF <br />TAPE SHALL NOT BE PULLED OR STREfCHED. ALL TAPE SHALL BE CUT WITH A SHARP KNIFE OR <br />SCISSORS. <br />Sprint' <br />GENERAL DYNAMICS <br />WIRELESS SERVICES <br />:^;,: , KDC <br />ti� `i y' � ARCHRECfS•ENGINEERS, P.C. <br />1770200IHSIIIEETSW SUffE200 <br />�� �`'�� i INOIE: �t5 �1 <br />��� �� �� � FAX: �35.712.06�6 <br />PROJFCf INFOR��iK( ION: <br />NEiN'ORK VISION MM[tS LAUVCI I <br />EVERGREEN WAY <br />SE54XC102 <br />6515 MORGAN ROAD <br />EVEREfT, WA. 98203 <br />SNOHOMISH COUNTY <br />I_uUEl��l�t � �-�8- � 2 <br />i�uE°F°R:CONSTRUCTION DWGS <br />REVISIONS <br />REV. DATE DESCRiPT10N INITIALS <br />A 07/OS/12 ISSUED FOR CONSTRUCTABILIiY REVIEW yyAS <br />B 08/08/12 ISSUED FOR 90% CD REVIEW WAS <br />C 08/31/12 ISSUED FOR 1009 CD REVIEW WAS <br />D 10/26/12155UED FOR PRELIM.1007 CD REVIEW ET <br />E 17/08/121SSUED FOR PINAL 100% CD ET <br />NOT FOR CONSTRUCTION UNLESS <br />LABELED AS CONSTRUCTION SET <br />i.icEvsuK[_ <br />5773 <br />REGISTERED <br />AR ITEC <br />KENN TH .CAMP <br />STATE OF WASHINGTON <br />si �EEr nr�e <br />GENERA� NOTES <br />Sl{EET NUMRER: REVISION: <br />N-2 E <br />122168 <br />