FOUNDATION, EXCAVATION AND BACKFILL NOTES
<br />1. ALL FINAL GRADED SLOPES SHALL BE A MAXIMUM OF 3 HOPo20NTAL TO 1 VERTICAL.
<br />2. ALL EXCAVATIONS PREPARED FOR PLACEMENT OF CONCREfE SHALL BE OF UNDISTURBED SOILS,
<br />SUBSTANTIALLY HORIZONTAL AND FREE FROM ANY LOOSE, UNSUITABLE MATERIAL OR FROZEN SOILS, AND
<br />WITHOUT THE PRESENCE OF POUNDING WATER. DEWATERING FOR EXCESS GROUNO WATER SHALL BE
<br />PROVIDED WHEN REQUIRED. COMPACTION OF SOILS UNDER CONCREfE PAD FOUNDATIONS SHALL NOT BE IESS
<br />THAN 95% OF THE MODIFIED PROCTOR MN(IMUM DRY DENSIN FOR THE SOIL IN ACCORDANCE WITH ASTM
<br />D1557.
<br />3. CONCRETE FOUNDATIONS SHALL NOT BE PLACED ON ORGANIC OR UNSUITABLE MATERIAL IF INADEQUATE
<br />BEARING CAPACIN IS REACHEO AT THE DESIGNEO EXCAVATION DEPTH, THE UNSATISFACTORY SOIL SHALL BE
<br />EXCAVATED TO ITS FULL DEPTH AND EITHER BE REPLACED WITH MECHANICALLY COMPACTED GRANULAR
<br />MATERIAL OR THE EXCAVATION SHALI BE FlLLED WITH CONCRETE OF THE SAME IYPE SPECIFlED FOR THE
<br />FOUNDATION. CRUSHED STONE MAY BE USED TO STABILIZE THE BOTTOM OF THE EXCAVATION. ANY STONE
<br />SUB BASE MATERIAL, IP USED, SHALL NOT SUBSTITUTE FOR REQUIRED THICKNE55 OF CONCRETE.
<br />4. ALL EXCAVATIONS SHALL BE CLEAN OF UNSUITABLE MATERIAL SUCH AS VEGETATION, TRASH, DEBRIS, AND SO
<br />FORTH PRIOR TO BACK FILLING. BACK FILL SHALL CONSIST OF APPROVED MATERIALS SUCH AS EARTH, LOAM
<br />SANDY CLAY, SAND AND CRAVEL, OR SOfT SHALE, FREE FROM CLODS OR LARGE STONES OVER 2 1/2" MAX
<br />DIMENSIONS. ALL BACK FILL SHALL BE PLACED IN COMPACTED LAYERS.
<br />5. ALL FILL MATERIALS AND FOUNDATION BACK FlLL SHALL BE PLACE� MAXIMUM 6" THICK LIFTS BEFORE
<br />COMPACTION. EACH LIFT SHALL BE WETTED IF REQUIRED AND COMPACTED TO NOT LESS THAN 95Y, OF THE
<br />MODIRED PROCTOR MAXIMUM DRY DENSITY FOR SOIL IN ACCORDANCE WITH ASTM D1557.
<br />6. NEWLY PLACED CONCRETE FOUNDATIONS SHALL CURE A MINIMUM OF 72 HRS PRIOR TO BACK FILLING.
<br />7. FINISHEO GRADING SHALL BE SLOPED TO PROVIDE POSITIVE DRAINAGE AND PREVENT STANDING WATER. THE
<br />FINAL (FINISH) ELEVATION OF SLAB FOUNDATIONS SHALL SLOPE AWAY IN ALL DIRECTIONS FROM THE CENTER.
<br />FINISH GRADE OF CONCREfE PADS SHALL BE A MN(IMUM OF 4 INCHES ABOVE FINAL FINISH GRADE
<br />ELEVATIONS. PROVIDE SURFACE FILL GRAVEL TO ESTABLISH SPECIFlED ELEVATIONS WHERE REQUIREO.
<br />8. NEWLY GRADED SURFACE AREAS TO RECENE GRAVEL SHALL BE COVERED WITH GEOTEXTILE FABRIC TYPE:
<br />iYPAR-3401 AS MANUFACTURED BY "CONSTRUCTION MATERIAL 1-800-239-3841" OR AN APPROVED
<br />EQUIVALENT, SHOWN ON PLANS. THE GEOTEXTILE FABRIC SHALL BE BL4CK IN COLOR TO CONTROL THE
<br />RECURRENCE OP VEGEfATIVE GROWTH AND EXTEND TO WITHIN 1 FOOT OUTSIDE THE SITE FENCING OR
<br />ELECTRICAL GROUNDING SYSTEM PERIMETER WHICH EVER IS GREATER. ALL FABRIC SHALL BE COVERED WITH
<br />A MINIMUM OF 4" DEEP COMPACTED STONE OR GRAVEL AS SPECIFlED. LE FDOT NPE No. 57 FOR FENCED
<br />COMPOUND; FDOT NPE No. 67 POR ACCESS DRIVE AREA.
<br />9. IN ALL AREAS TO RECENE FILL, REMOVE ALL VEGEfATION, TOPSOIL, DEBRIS, WET AND UNSATISFACTORY SOIL
<br />MATERIALS, OBSTRUCTIONS, AND DELETERIOUS MATERIALS FROM GROUND SURFACE. PLOW STRIP OR BREAK
<br />UP SLOPED SURFACES STEEPER THAN 1 VERTICAL TO 4 HORIZONTAL SUCH THAT FILL MATERIAL WILL BIND
<br />WITH EXISTING/PREPARE� SOIL SURFACE.
<br />10. WHEN SUB GRADE OR PREPARED GROUND SURFACE HAS A DENSITY LESS THAN THAT REQUIRED FOR THE
<br />FlLL MATERIAL, SCARIFY THE GROUND SURFACE TO DEPTH REQUIRED, PULVERIZE, MOISTURE-CONDITION
<br />AND/OR AERATE THE SOILS AND RE-COMPACT TO THE REOUIRED DENSIN PRIOR TO PLACEMENT OF FILLS.
<br />11. IN AREAS WHICH EXISTING GRAVEL SURFACING IS REMOVED OR DISTURBED DURWG CONSTRUCTION
<br />OPERATIONS, REPLACE GRAVEL SURFACING TO MATCH ADJACENT GRAVEL SURFACING AND RESTORED TO THE
<br />SAME THICKNESS AND COMPACTION AS SPECIFIED. ALL RESTORED GRAVEL SURFACING SHALL BE FREE FROM
<br />CORRUGATIONS AND WAVES.
<br />12 EXISTING GRAVEL SURFACING MAY BE EXCAVATED SEPARATELY AND REUSED WITH THE CONDIT�ON THAT ANY
<br />UNFAVORABLE AMOUNTS OF ORGANIC MATfER, OR OTHER DELEfERIOUS MATERIALS ARE REMOVED PRIOR TO
<br />REUSE. FURNISH ANY ADDITIONAL GRAVEL RESURFACING MATERIAL AS NEEDED TO PROVIDE A FULL DEPTH
<br />COMPACTED SURFACE THROUGHOUT SITE.
<br />13. GRAVE� SUB SURFACE SHALL BE PREPARED TO REQUIRED COMPACTION AND SUB GRADE ELEVATIONS BEFORE
<br />GRAVE� SURFACING IS PLACED AND/OR RESTORED. ANY LOOSE OR DISTURBED MATERIALS SHALL BE
<br />THOROUGHLY COMPACTED AND ANY DEPRESSIONS IN TNE SUB GRADE SHALL BE FILLED AND COMPACTED
<br />WITH APPROVED SELECTED MATERIAL GRAVEL SURFACING MATERIAL SHALL NOT BE USED FOR FlLLING
<br />DEPRESSIONS IN THE SUB GR4DE.
<br />14. PROTECT EXISTING GRAVEL SURFACING AND SUB GRADE IN AREAS WHERE EOUIPMENT LOADS WILL OPERATE. .
<br />15. DAMAGE TO EXISTING STRUCTURES AN�/OR UTILITIES RESULTING FROM CONTRACTORS NEGLIGENCE SHALL BE
<br />REPNRED AND/OR REPL4CED TO THE OWNERS SATISFACTION AT NO ADDITIONAL COST TO THE CONTRACT.
<br />16. ALL SUITABLE BORROW MATERIAL FOR &4CK FILL OF THE SITE SHALL BE INCLUDED IN THE BID. EXCESS
<br />TOPSOIL AND UNSUITABLE MATERIAL SHALL BE DISPOSED OF OFF SITE AT LOCATIONS APPROVED BY
<br />GOVERNING AGENCIES AT NO ADDITIONAL COST TO THE CONTRACT.
<br />ENVIRONMENTAL NOTES
<br />1. ALL WORK PERFORMED SHALL BE DONE IN ACCORDANCE WITH ISSUED PERMITS. THE CONTRACTOR SHALL 8E
<br />RESPONSIBLE FOR PAYMENT OF FINES AND PROPER CLEAN UP FOR AREAS IN VIOLATION.
<br />2 CONTRACTOR AND/OR DEVELOPER SHALL BE RESPONSIBLE FOR CONSTRUCTION AND MAIMENANCE OF EROSION
<br />AND SEDIMENTATION CONTROLS DURING CONSTRUCTION FOR PROTECTION OF A�JACENT PROPERTIES, ROADWAYS
<br />AND WATERWAYS AND SHALL BE MAINTAINED IN PLACE THROUGH FINAL JURISDICTIONAL INSPECTION & RELEASE
<br />OF SITE.
<br />3. CONTRACTOR SHALL INSTALL/CONSTRUCT ALL NECESSARY SEDIMENT/SILT CONTROL FENCWG AN� PROTECTIVE
<br />MEASURES WITHIN THE IIMITS OP SITE DISTURBANCE PRIOR TO CONSTRUCTION.
<br />4. NO SEDIMENT SHALL BE ALLOWED TO EXIT THE PROPERTY. THE CONTRACTOR IS REPSONIBLE FOR TAKING
<br />ADEQUATE MEPSURES FOR CONTROLLING EROSION. ADDITIONAL SEDIMENT CONTROL FENCING MAY BE REQUIRED
<br />IN ANY AREAS SUBJECT TO EROSION.
<br />5. THE CONTR4CTOR IS RESPONSIBLE FOR MAWTAINING POSITNE DRAINAGE ON THE SITE AT ALL TIMES WITH SILT
<br />AND EROSION CONTROL MEASURES MAINTAINED ON THE DOWNSTREAM SIDE OF SITE DRAINAGE. ANY DAMAGE TO
<br />ADJACENT PROPERTY AS A RESULT OF EROSION WILL 8E CORRECTED AT THE CONTRACTORS EXPENSE.
<br />6. CONTRACTOR SHALL BE RESPONSIBLE FOR DAILY INSPECTIONS AND ANY REPAIRS OF ALL SEDIMENT CONTROL
<br />MEASURES INCLUDING SEDIMENT REMOVAL AS NECESSARY.
<br />7. CLEARING OF VEGEfATION AND TREE REMOVAL SHALL 8E ONLY AS PERMITTED AND BE HELD TO A MINIMUM.
<br />ONLY TREES NECESSARY FOR CONSTRUCTION OF THE FACILITIES SHALL BE REMOVED.
<br />8. SEEDING SAND MULCHING AND/OR SODDING OF THE SITE WILL BE ACCOMPLISHED AS SOON AS POSSIBLE
<br />AFTER COMPLETION OF THE PROJECT FACILITIES AFFECTING LAND DISTURBANCE.
<br />9. CONTRACTOR SHALL PROVIDE ALL EROSION AND SEDIMENTATION CONTROL MEASURES AS REQUIRED 8Y LOCAL,
<br />COUNN AND STATE CODES AND ORDINANCES TO PROTECT EMBANKMENTS FROM SOIL LOSS AND TO PREVENT
<br />ACCUMULATION OF SOIL AND SILT IN STREAMS AND DRAINAGE PATHS LEAVING THE CONSTRUCTION AREA. THIS
<br />MAY INCLUDE SUCH MEASURES AS SILT FENCES, STRAW BALE SE�IMENT BARRIERS, AND CHECK DAMS.
<br />10. RIP RAP OF SIZES INDICATED SHALL CONSIST OF CLEAN, HARD, SOUND, DURABLE, UNIFORM IN QUALIN STONE
<br />FREE OF ANY DEfRIMENTAL QUANTIN OF SOFT, FRIABLE, THIN, ELONGATED OR LAMINATED PIECES,
<br />DISINTEGRATED MATERIAL, ORGANIC MATTER, OIL, ALKALI, OR OTHER DELETERIOUS SUBSTANCES.
<br />STRUCTURAL STEEL NOTES
<br />1. ALL STEEL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC MANUAL OF STEEL
<br />CONSTRUCTION. STEEL SECTIONS SHALL BE IN ACCORDANCE WITH ASTM AS INDICATED BELOW:
<br />W-SHAPES: ASTM A992, 50 KSI
<br />ANGLES, BARS CHANNELS: ASTM A36, 36 KSI
<br />HSS SECTIONS' ASTM 500, 46 KSI
<br />PIPE SECTIONS: ASTM A53-E, 35 KSI
<br />2 ALL EXTERIOR EXPOSED STEEL AND HARDWARE SHALL BE HOT DIPPED GALVANIZED.
<br />3. ALL WELDING SHALL BE PERFORMED USING E70XX ELECTRODES AND WELDING SHALL CONFORM TO
<br />AISC. WHERE FILLET WEID SIZES ARE NOT SHOWN, PROVIDE THE MINIMUM SIZE PER TABLE J2.4 IN
<br />THE AISC "MANUAL OF STEEL CONSTRUCTION". PNNTED SURFACES SHALL BE TOUCHED UP.
<br />4. NON-STURCUTRAL CONNECTIONS FOR STEEL GRATING MAY USE 5/8"0 ASTM A 307 BOLTS UNLESS
<br />NOTED OTHERWISE..
<br />5. FIELD MODIFICATIONS ARE TO BE COATED WITH ZINC ENRICHED PAINT.
<br />ONCRETE MASONRY NOTES
<br />1. CONCRETE MASONRY UNITS SHALL BE MEDIUM WEIGHT UNITS CONFORMING TO ASTM C90, GW\DE N-i,
<br />(F'M=1,500 PS). MEDIUM WEIGHT (115 PCF).
<br />2. MORTAR SHALL BE TYPE "S" (MINIMUM 1,800 PSI AT 28 DAYS).
<br />3. GROUT SHALL HAVE A MINIMUM COMPRESSNE STRNGTH OF 3,000 PSI AT 28 DAYS.
<br />4. ALL CELLS CONTAINING REWFORCING STEEL OR EMBE�DED ITEMS AND ALL CELLS IN RETAINING WALLS
<br />AND WALLS BELOW GRADE SHALL BE SOLID GROUTED.
<br />5. A�L HOR�ZONTAL REWFORCEMENT SHALL BE PLACED IN BOND BEAM OR LINTEL BEAM UNITS.
<br />6. WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL CONSTRUCTION JOINTS SHAL�
<br />BE FORMED BY STOPPING THE GROUT POUR 1-t/2" BELOW TOP OF THE UPPERMOST UNIT.
<br />7. ALL BOND BEAM BLOCK SHALL BE "DEEP CUT" UNITS.
<br />B. PROVIDE WSPECTION AND CLEAN-OUT HOLES AT BASE OF VERTICAL CELLS HAVING GROUT LIFTS IN
<br />EXCESS OF 4'-0" OF HEIGHT.
<br />9. ALL GROUT SHALL BE CONSOLIDATED WITH A MECHANICAL VIBRATOR.
<br />10. CEMENT SHALL BE AS SPECIFIED FOR CONCRETE.
<br />11. REWFORCING BARS - SEE NOTES UNDER "STRUCTURAL CONCRETE NOTES" FOR REQUIREMENTS.
<br />12. PROVIDE ONE BAR DIAMETER (A MINIMUM OF 1/2') GROUT BER4EEN MAIN REWFORCING AND MASONRY
<br />UNITS.
<br />13. LOW LIfT CONSTRUCTION, MAXIMUM GROUT POUR HEIGHT IS 4 FEEf.
<br />14. HIGH UfT GROUTED CONSTRUCTION MAY BE USED IN CONFORMANCE W�TH PROJECT SPECIFICATIONS
<br />AND SECTION 2104.6.1 OF U.B.C.
<br />15. ALL CELLS IN CONCREfE BLOCKS SHA�L BE FILLED SOLID WITH GROUT, E%CEPT AS NOTEED IN THE
<br />DRAWINGS OR SPECIFICATIONS.
<br />16. CELLS SHALL BE IN VERTICAL ALIGNMENT, DOWELS IN FOOTINGS SHALL BE SET TO ALIGN WITH CORES
<br />CONTAINING REINFORCING STEEI.
<br />17. REFER TO ARCHITECTURAL DRAWINGS FOR SURFACE AND HEIGHT OF UNITS, LAYING PATTER AND JOINT
<br />NPE.
<br />18. SAND SHALL BE CLEAN, SHARP AND WELL GR4DED, FREE FROM INJURIOUS AMOUNTS OF DUST, WMPS,
<br />SHALE, ALKAU OR ORGANIC MATERIAL.
<br />19. BRICK SHALL CONFORM TO ASTM C-62 AND SHALL BE GRADE MW OR BETTER.
<br />STRUCTURAL CONCRETE NOTES
<br />1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACi 301-05, ACI 318-05 AND THE
<br />SPECIFICATION FOR CAST-IN-PIACE CONCREfE.
<br />2. ALL CONCREfE SHALL HAVE A MINIMUM COMPRESSNE STRENGTH fc'=3,000 PSI AT 28 DAYS UNLESS
<br />NOTED OTHERWISE.
<br />3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60, DEFORMED UNLESS NOTED
<br />OTHERWISE. WEIDED WIRE FABRIC SHALL CONFORM TO ASTM A 185 WELDED STEEL WIRE FABRIC
<br />UNLESS NOTED OTHERWISE SPLICES CLASS "B" AND ALL HOOKS SHALL BE STANDARD UNLESS NOTED
<br />OTHERWISE.
<br />4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCING STEEL UNLESS
<br />SHOWN OTHERWISE ON DRAWINCS:
<br />CONCRETE CAST AGAWSi EARTH ...............3 IN.
<br />CONCRETE EXPOSED TO EARTH OR WEATHER:
<br />�'6 AND LARGER ...............2 IN.
<br />�5 AND SMALLER & WWF ...............t 1/2 IN.
<br />CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT CAST AGNNST THE GROUND:
<br />SLAB AND WALL ...............3/4 IN.
<br />BEAMS AND COWMNS ...............1 1/2 IN.
<br />5. A 3/4" CHAMFER SHALL BE PROVIDED AT ALL EXPOSED EDGES OF CONCRETE U.N.O.IN ACCORDANCE
<br />WITH ACI 301 SECTIDN 42.4
<br />6. HOLES TO RECEIVE EXPANSION/WEOGE ANCHORS SHALL BE 1/8" LARGER IN DIAMEfER THAN THE
<br />ANCHOR BOLT, DOWEL OR ROD AND SHALL CONFORM TO MANUFACTURER'S RECOMMENDATION FOR
<br />EMBEDMENT DEPTH OR AS SHOWN ON THE DRAWINGS. LOCATE AND AVOID CUTfING EXISTING REBAR
<br />WHEN DRILLING HOLES W ELEVA7ED CONCRETE SLABS.
<br />7. USE AND WSTALLATION OF CONCRETE EXPANSION/WEDGE ANCHOR, SHALL BE PER ICBO &
<br />MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURES.
<br />THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO CARPoER SERVICES IS STRICTLY PROHIBITEO.
<br />WEATHERPROOFING NOTES
<br />STANDARD CONSTRUCTION SPECIFICATIONS FOR WIRELESS SITES
<br />3.6 WEATHERPROOFING CONNECTORS AND GROUND KITS:
<br />w ALL CONNECTORS AND GROUND KITS SHALL BE WEATHERPROOFED USING BUNL RUBBER
<br />WEATHERPROOFING AND TAPE. THIS INSTALLATION MUST BE DONE IN ACCORDANCE WITH THE
<br />MANUFACTURER'S RECOMMENDATION OR AS SHOWN ON THE CONSTRUCTION DRAWINGS (WHICHEVER IS
<br />GREATER). IF NO DIRECTION IS PROVIDED, WEATHERPROOFING MUST BE �ONE PER THE FOLLOWING
<br />INSTRUCTIONS.
<br />1. THE COAXIAL CABLE CONNECTION OR GROUND KIT CAN BE ENCOMPASSED INTO COLD SHRINK AND
<br />COMPLETEIY WRAPPED WITH 2 INCH WIDE ELECTRICAL TAPE OVERLAPPING EACH ROW BY
<br />APPROXIMATELY �" AND EXTENDING PAST THE CONNECTION BY PNO INCHES AS DISCUSSED BELOW; OR
<br />2. THE CON(IAL CABLE CONNECTION OR GROUND KR CAN BE WRAPPED WITH LAYERS OF
<br />ELECTRICAL/BUiYL RUBBER/ELECTRICAL TAPE AS DISCUSSED BELOW; OR
<br />3. THE COAXIAL CABLE CONNECTION OR GROUND KIT CAN BE WRAPPED WITH iW0 LAYERS OF 1.5 INCH
<br />WIDE SELF-AMALGAMATWG TAPE COVERED WITH TNO LAYERS OF ELECTRICAL TAPE AS DISCUSSED
<br />BELOW.
<br />e. COLD SHRINK INSTALLATION PROCEDURE:
<br />1. REQUIRED MATERIAL: COLD SHRINK TUBE, SPACERS AS NEEDED, BLACK ELECTRICAL TAPE-2 INCHES
<br />WIDE
<br />2. REQUIRED TOOLS: KNIFE AND TAPE MEASURE
<br />STEP 1: THOROUGHLY CLEAN AND DRY THE SURFACE OF COAXIAL CABLE AND CONNECTOR TO REMOVE
<br />ALL GREASE AND DIRT. MARK THE MNN FEED (LARGER DIAMEfER) COAXIAL CABLE AT LEAST TWO
<br />INCHES ABOVE THE CONNECTION AS THE SPECIFIED START DIMENSION FOR THE COLD SHRINK.
<br />STEP 2: SLIDE THE COLD SHRINK TUBE OVER THE PRE-CONNECTORIZED END OF THE LARGER
<br />DIAMETER COAXIAL CABLE PRIOR TO MATING CONNECTOR WTERFACES. MAKE THE CONNECTION.
<br />STEP 3: REMOVE WAX PAPER FROM A SPACER HALF AND PRESS ONTO CON(IAL CABLE DIRECTLY
<br />BEHIND THE CONNECTOR. REMOVE THE WAX PAPER FROM THE OTHER SPACER HALF AND ALIGN THE
<br />TWO SPACER HALVES WITH ADHESIVE PORTIONS FACING EACH OTHER. PRESS THE SPACER HALVES
<br />TOGEfHER. THE SPACER WILL BE PLACED NEXT TO THE CONNECTOR ON THE SMALLER DIAMEfER
<br />COA%IAL CABLE SIDE.
<br />STEP 4: SLIDE THE COLD SHRINK TUBE OVER THE CONNECTION TO THE SPECIFIED START DIMENSION
<br />MARK. HOLD THE COLD SHRWK TUBE AND COAXIAL CABLE IN ONE HAND 50 THAT THE EDGE OF COLD
<br />SHRINK TUBE IS IN LINE WITH THE MARK.
<br />STEP 5: WITH YOUR FREE HAND, BEGIN REMOVWG COLD SHRINK TUBE CORE. THE CORE WILL BE
<br />REMOVED BY UNWINDING IN A COUNTERCLOCKW6E DIRECTION WHILE LIGHTLY PULLING THE ATTACHED
<br />CORD AWAY FROM THE TUBE.
<br />STEP 6: USE BOTH HANDS TO CONTINUE THE UNWINDING PROCESS AS THE COLD SHRINK TUBE BEGINS
<br />TO COLlAPSE INTO POSITION. CONTINUE THE UNWINDING PROCE55 UNTIL THE CORE IS COMPLETELY
<br />REMOVED AND THE COLD SHRINK TUBE IS INSTALLED.
<br />STEP 7: EXCESS COLD SHRINK TUBE EXTENDING TWO INCHES BEYOND THE SPACER HALVES CAN BE
<br />REMOVED OR LEFT IN PLACE. EXCESS COLD SHRINK TUBE CAN BE CAREFULLY CUT OFF WITH A KNIFE.
<br />STEP 8: WRAP OVER THE COLD SHRINK TUBE WITH ONE LAYER OF BLACK ELECTRICAL TAPE 2 INCH
<br />WIDTH OVERIAPPING EACH ROW BY 1/2 INCH. THIS TOP LAYER MUST BE WRAPPED USING A SHINGLED
<br />EFFECT. THE LAYER SHALL BE WRAPPED SO THAT THE ENDS ARE IN THE UPWARD DIRECTION CREATING
<br />A SHINGLEO EFFECT WffH THE TAPE SO WATER WILL BE REPELLED AND NOT ALLOWED TO COLLECT AND
<br />POOL THIS TOP LAYER OF ELECTRICAL iAPE MUST EXTEND iW0 INCHES (THE TAPE WIDTH) PAST THE
<br />COLD SHRINK TUBE ONTO THE UNDERLYING CABLE. TAPE SHALL BE WRAPPED SO THAT NO VOIDS OR
<br />AIR PACKETS ARE PRESENL TAPE SHALL BE CUT WITH A SHARP KNIfE.
<br />C. BUNL RUBBER TAPE INSTALLATION PROCEDURE:
<br />1. REQUIRED MATERIAL BLACK ELECTRICAL TAPE-2 INCH WIDE AND BUNL RUBBER TAPE 2 TO 3 INCHES
<br />WIDE.
<br />2. REQl11RE0 TOOLS: KNIFE OR SCISSORS.
<br />STEP 1: THOROUGHLY CLEAN AND DRY THE SURFACE OF COAXIAL CABLE AND CONNECTOR TO REMOVE
<br />ALL GREASE AND DIRT. WRAP CONNECTOR/GROUND KIT WITH iW0 LAYERS OF BLACK ELECTRICAL
<br />TAPE-2 INCH WIDTH OVERLAPPING EACH ROW BY APPROXIMATELY 1/2 INCH. THESE LAYERS OF TAPE
<br />MUST 8E WRAPPED TIGHT ENOUGH SO THAT NO VOIDS OR NR PACKEfS ARE PRESENT AND MUST
<br />EXTEND ONE WCH PAST THE CONNECTOR/GROUN� KIT ON EACH SIDE.'(WO ROWS SHALL BE APPLIED,
<br />ONE IN EACH DIRECTION, WITH THE TOP ROW SHINGLED TO PROMOTE WATER RUNOFF.
<br />STEP 2: WRAP CONNECTOR/GROUND KIT WITH ONE LAYER OF BUNL RUBBER TAPE (2 TO 3 INCHES
<br />WIDTH) OVER THE BLACK ELECTRICAL TAPE OVERLAPPING EACH ROW BY APPROXIMATELY 1/2 INCH. THE
<br />BUNL R1188ER TAPE MUST EXTEND 2 TO 3 INCHES (THE TAPE WIDTH) PAST THE ELECTRICAL TAPE
<br />AND COME IN GOOD CONTACT WIiH THE UNDERLYING CABLE ON CONNECTORS, WHEN
<br />WEATHERPROOFING FROM THE MAtN LWE TO THE JUMPER, BUILD UP THIS AREA WITH EXTRA BUTYL
<br />RUBBER TAPE TO INSURE A SMOOTH TRANSITION FREE OF VOIDS AND AIR PACKETS DOWN TO THE
<br />SMALLER �IAMEfER CABLE.
<br />STEP 3: WRAP CONNECTOR�GROUND KIT WITH iW0 LAYERS OF BLACK ELECTRICAL TAPE 2 INCH WIDTH
<br />OVERLAPPING EACH ROW BY 1 INCH. THESE LAST 1W0 LAYERS MUST BE WRAPPED USING A SHING�EO
<br />EFFECT. THE TOP LAYER SHALL BE WR4PPED SO THAT THE ENDS ARE IN THE UPWARD DIRECTION
<br />CREATING A SHINGLED EFFECT WITH THE TAPE SO WATER WILL BE REPELLED AND NOT ALLOWED TO
<br />COLLECT AND POOL THESE TOP LAYERS OF ELECTRICAL TAPE MUST EXTEND TWO INCHES (THE TAPE
<br />WIDTH) PAST THE BUNL RUBBER TAPE ONTO THE UNDERLYING CABLE.
<br />ALL LAYERS OF TAPE SHALL BE WRAPPEO 50 THAT NO VOIDS OR AIR PACKEiS ARE PRESENT. THE
<br />LAST WR4P OF TAPE SHALL NOT BE PULLED OR STREfCHED. ALL TAPE SHALL BE CUT WITH A SHARP
<br />KNIFE OR SCISSORS.
<br />0. SELF-AMALGAMATING TAPE INSTALLATION PROCEDURE:
<br />1. REQUIREO MATERIAIL SELF-AMALGAMATING TAPE -1.5 INCHES WIDE AND BLACK ELECTRICAL TAPE - 2
<br />INCHES WIDE.
<br />2. REQUIRED TOOLS: KNIFE OR SCISSORS.
<br />STEP 1: THOROUGHLY CLEAN AND DRY THE SURFACE OF COAXIAL CABLE AND CONNECTOR TO REMOVE
<br />ALL GREASE AND DIRT.
<br />STEP 2: START WRAPPING SELF-AMALGAMATMG TAPE ON THE CABLE AT LEAST 2 WCHES FROM THE
<br />CONNECTOR/GROUND KIT. MAKE SURE TAPE IS STRETCHED TIGHT DURING THIS APPLICATION.
<br />STEP 3: WHILE STRETCHING TAPE, MAKE ONE WRAP OF THE TAPE AROUND THE CABLE, MAKING SURE
<br />THE TAPE IS WRAPPED ONTO ITSELF. THE TAPE WILL ONLY ADHERE TO ITSELF.
<br />STEP 4: CONTINUE WRAPPING THE CABLE AND CONNECTOR/GROUND KIT USING HALF OVERL4P (0.75
<br />INCH WIDE) LAYERS.
<br />STEP 5: WRAP OVER AND PAST THE CONNECTOR/GROUND KIT AT LEAST 2 INCHES.
<br />STEP 6: TO TERMINATE THE SELF-AMALGAMATING TAPE, WRAP THE TAPE AT LEAST ONE FULL ROUND
<br />OVER THE CABLE STREfCHING THE TAPE TIGHT. CUT THE TAPE USING KNIFE OR SCISSORS AND APPLY
<br />THE LOOSE END TO THE UNDERLYING SELF-AMALGAMATING TAPE USING THUMB PRESSURE.
<br />STEP 7: TWO ROWS OF SELF-AMALGAMATING TAPE SHALI BE APPLIED IN THIS MANNER, IN A�TERNATMG
<br />DIRECTIONS. THE TOP LAYER SHALL 8E WRAPPED SO THAT THE ENDS ARE IN AN UPWARD DIRECTION
<br />CREATING A SHINGLED EFFECT WITH THE TAPE SO WATER WILL BE REPELLED.
<br />STEP 8: WRAP OVER SELF-AMALGAMATWG TAPE WITH TWO LAYERS OF BLACK ELECTRICAL TAPE- 2
<br />INCH WIDTH OVERLAPPING EACH ROW BY 1 INCH. THESE TOP TWO LAYERS MUST ALSO BE WR4PPED
<br />USING A SHINGLED EFFECT. THE LAYERS SHALL BE WRAPPED 50 THAT THE ENDS ARE IN THE UPWARD
<br />DIRECTION CREATING A SHINGLED EFFECT WITH THE TAPE SO WATER WILL BE REPELLED AND NOT
<br />ALLOWED TO COLLECT AND POOL THESE TOP L4YER5 OF ELECTRICAL TAPE MUST EXTEND 'IWO WCHES
<br />(THE TAPE WIDTH) PAST THE SELF-AMALGAMATING TAPE ONTO THE UNDERLYING CABLE. ALL LAYERS OF
<br />TAPE SHALL BE WRAPPEO SO THAT NO VOIDS OR AIR PACKEfS ARE PRESENT. THE LAST WRAP OF
<br />TAPE SHALL NOT BE PULLED OR STREfCHED. ALL TAPE SHALL BE CUT WITH A SHARP KNIFE OR
<br />SCISSORS.
<br />Sprint'
<br />GENERAL DYNAMICS
<br />WIRELESS SERVICES
<br />:^;,: , KDC
<br />ti� `i y' � ARCHRECfS•ENGINEERS, P.C.
<br />1770200IHSIIIEETSW SUffE200
<br />�� �`'�� i INOIE: �t5 �1
<br />��� �� �� � FAX: �35.712.06�6
<br />PROJFCf INFOR��iK( ION:
<br />NEiN'ORK VISION MM[tS LAUVCI I
<br />EVERGREEN WAY
<br />SE54XC102
<br />6515 MORGAN ROAD
<br />EVEREfT, WA. 98203
<br />SNOHOMISH COUNTY
<br />I_uUEl��l�t � �-�8- � 2
<br />i�uE°F°R:CONSTRUCTION DWGS
<br />REVISIONS
<br />REV. DATE DESCRiPT10N INITIALS
<br />A 07/OS/12 ISSUED FOR CONSTRUCTABILIiY REVIEW yyAS
<br />B 08/08/12 ISSUED FOR 90% CD REVIEW WAS
<br />C 08/31/12 ISSUED FOR 1009 CD REVIEW WAS
<br />D 10/26/12155UED FOR PRELIM.1007 CD REVIEW ET
<br />E 17/08/121SSUED FOR PINAL 100% CD ET
<br />NOT FOR CONSTRUCTION UNLESS
<br />LABELED AS CONSTRUCTION SET
<br />i.icEvsuK[_
<br />5773
<br />REGISTERED
<br />AR ITEC
<br />KENN TH .CAMP
<br />STATE OF WASHINGTON
<br />si �EEr nr�e
<br />GENERA� NOTES
<br />Sl{EET NUMRER: REVISION:
<br />N-2 E
<br />122168
<br />
|