My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
2132 ROCKEFELLER AVE 2016-10-12
>
Address Records
>
ROCKEFELLER AVE
>
2132
>
2132 ROCKEFELLER AVE 2016-10-12
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/13/2017 2:09:25 AM
Creation date
10/4/2016 1:58:43 PM
Metadata
Fields
Template:
Address Document
Street Name
ROCKEFELLER AVE
Street Number
2132
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
72
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
9. The existing deck structure may not meet current code requirements, to simply state <br />"Match existing" for the various components does not "...indicate the location nature and <br />extent of the work proposed and show in detail that it will conform to the provisions of <br />this code..." per Section R106.1.1 International Residential Code (IRC). <br />13. A floor or a landing is required on both sides of an entrance/exit. Doors shall not swing <br />over stairs (See #2 above if you should choose to raise the floor level with a framed <br />floor). <br />14. Provide note on drawings indicating that applicant will remove wall coverings (GWB) as <br />needed to allow for inspection of the entire structure. <br />NOTE: Please be advised that no openings are allowed to be created on the north side of <br />the structure, including but not limited to: dryer vent, exhaust fan, range hood, and similar <br />devices. <br />Please prepare a response letter showing where each item in this correction letter is <br />addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />�-��� ��".� -- <br />, � <br />� <br />Jeff eilman <br />Development Technician <br />425-257-8976 <br />Email: ]heilman@ci.everett.wa.us <br />5:\1Common\ClericalUHeilman\CW1212-001 (213Z Rockefeller) 011013.doc <br />
The URL can be used to link to this page
Your browser does not support the video tag.