Laserfiche WebLink
11. Supports for solar modules are installed to spread the dead load across as many roof- <br /> framing members as needed to ensure that no point load exceeds fifty(50)pounds, } ❑ <br /> [IRC M2302,2.1(5)] <br /> 12. The photovoltaic modules and supporting structure shall be constructed of <br /> noncombustible materials or fire-retardant treated wood equivalent to that required for ❑ <br /> the roof construction. [IRC M2302.2.1] <br /> 13, Roof and wall penetrations shall be flashed and sealed to prevent entry of water, 4 ❑ <br /> rodents,and insects. [IRC M2302.2.2] <br /> 14. PV modules are listed and labeled with a fire classification in accordance with UL 1703. El <br /> M2302,2.3] <br /> Comments: <br /> ={ If you answered yes to all of the above questions,the project qualifies for the over-the- <br /> counter permitting process. <br /> Determine if your project qualifies for an Over-the-Counter electrical permit <br /> Yes No N/A <br /> 1. PV modules,inverters, and combiner boxes are identified for use in PV systems. ❑ <br /> 2. The inverters are listed and labeled in accordance with UL 1741 and are listed for ❑ <br /> utility interaction. [IRC M2302.41 <br /> 3. The AC interconnection point is on the load side of service disconnect. [NEC 690.64(6)] <br /> 4. The system meets all current NEC,City and Washington Cities Electrical Code ( ❑ <br /> requirements. <br /> 5. For Split-Buss modules the AC interconnection must be one of the six service El <br /> disconnects. <br /> 6. Maximum load added to the panelboard is based on the rating of the panelboards bus/main OCPD <br /> combination in accordance with NEC 705.12(D)(2)(3)(b),and is limited to(check combination that <br /> applies): <br /> ❑225 amp bus/200 amp main OCPD-13,440 AC watts,maximum 70 amp inverter OCPD. <br /> ❑225 amp bus/225 amp main OCPD- 8,640 AC watts,maximum 45 amp inverter OCPD. <br /> ^51 <br /> 400 amp bus/200 amp main OCPD- 7,860 AC watts,maximum 40 amp inverter OCPD. <br /> ❑150 amp bus/150 amp main CCPD- 5,760 AC watts,maximum 30 amp inverter OCPD. <br /> ❑125 amp bus/125 amp main OCPD- 4,800 AC watts,maximum 25 amp inverter CCPD. <br /> ❑125 amp bus/100 amp main OCPD- 9,600 AC watts,maximum 50 amp inverter CCPD. <br /> v <br />