Laserfiche WebLink
I <br /> I <br /> 1 The conductors from the generator transfer switch enclosure to the rack mounted <br /> I <br /> 2 automatic transfer switch shall be enclosed in nylon mesh sleeve. <br /> 3 <br /> 4 The enclosure door shall be labeled with the letters "GTS". <br /> 5 <br /> I6 UPS Internal Components <br /> 7 The following equipment shall be furnished and mounted to the EIA rack in the UPS <br /> 8 cabinet. <br /> I9 <br /> 10 1. Controller Power Module <br /> 11 The 1100W/VA UPS module power module shall be designed to operate in <br /> I 12 extreme environments (-40 to 74 degrees C) while ensuring loads remain <br /> 13 protected and running during power outages and other power disturbances. <br /> 14 The UPS module shall provide wide range Automatic Voltage Regulation <br /> 15 (AVR) to lengthen battery life by providing protection without transferring to <br /> 16 backup mode during voltage surge or sag. The module shall have <br /> 17 programmable control and report dry contacts to allow monitoring and <br /> I 18 controlling of key functions. The unit's temperature compensated battery <br /> 19 charging shall protect batteries from overcharging or undercharging. Local <br /> 20 and remote monitoring and control shall be via RS232 port and Ethernet <br /> 21 SNMP interface. The unit shall have one 48 VDC input terminal block and <br /> I22 one 120VAC output terminal block with dual 5-15R receptacle. <br /> 23 <br /> 24 2. Automatic Transfer Switch (UATS) <br /> 25 The 120V/30A universal automatic transfer switch (UATS) shall be a three <br /> 26 stage bypass switch that allows for the UPS to be bypassed and still maintain <br /> 27 the ability to keep batteries fully charged. It shall act as a fail-safe device by <br /> I <br /> 28 switching the critical load to the utility line should a fault occur in the UPS. <br /> 29 This transfer switch shall also include a manual bypass switch which shall <br /> 30 allow servicing the UPS or replacing the batteries without equipment <br /> I <br /> 31 downtime. <br /> 32 <br /> 33 3. Surge Suppressor Assembly, 120/240VAC <br /> I 34 <br /> 35 4. Receptacle Plate Assembly <br /> 36 <br /> 37 The following equipment shall be installed on the battery shelves: <br /> I38 <br /> 39 1. Battery (Four batteries shall be provided) <br /> 40 Batteries shall be BCI group size 31 valve regulated lead acid gel cell <br /> I 41 batteries. Batteries shall provide 220 minutes of run time calculated using <br /> 42 25A DC constant current load. Battery terminals shall be '/" - 20 UNC <br /> 43 threaded. All battery specifications shall meet or exceed controller power <br /> I 44 module manufacturer's requirements. <br /> 45 2. Battery Management System <br /> 46 The battery charge management system shall be for 48V string. It shall monitor <br /> I 47 and protect batteries for runtime optimization and longer battery life by spreading <br /> 48 charge voltage equally across all batteries. The battery management unit shall be <br /> 49 CSA and UL approved and shall come with a battery interface cable. <br /> 50 3. Battery Cable kit <br /> 51 <br /> I 41s`STREET TO WMVD FREIGHT <br /> CORRIDOR IMPROVEMENTS <br /> FED AID#STPUL-9931(012);PW#3472 SP-137 February 10,2016 <br />