Laserfiche WebLink
� <br />6. All new fenestration to be U-0.30 or less. <br />L� <br />7. Provide lateral analysis for wind and seismic loading at east wall of front of house <br />(between porch and living). <br />8. Specify window size of all windows. <br />9. All headers that are not 6x are required to be insulated with R-10 ridged insulation in <br />2x6 walls. <br />10. Specify required CFM of all exhaust fans and range hood. Show whole housE� fan size <br />based on table M1507.3.3. <br />11. Provide handrails as required per section R311.7.8 show on plans. <br />12. The site plan general notes show the lot dimensions as 210'x 80', the site plan shows <br />the east property line as 80' and the west property line as 60'. The north and south <br />property lines appear to be incorrect as well. <br />13. Provide minimum 22"x 30" attic access. Show location on plans. <br />14. Where emergency escape and rescue opening are provided they shall have a sill height <br />of not more than 44 inches measured from the finished floor to the bottom of the clear <br />opening. / R310.1 IRC. <br />Please prepare a response letter showing where each item in this c;orrection <br />letter is addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and pl��n review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codE�s. <br />Sincerely, <br />�� <br />�� <br />Jeff Heilman <br />Development Technician <br />425-257-8976 <br />Email: iheilman@ci.everett.wa.us <br />�v <br />5:\1Common\Clerical\JHeilman\CW1504-003 (3602 WETMORE AVE).doc <br />