Laserfiche WebLink
� • � � <br />Mr. Jeff Heilman <br />City of Everett Letter May 6, 2015 <br />� <br />7. Provide lateral analysis for wind and seismic loading at east wall of front of house i;between <br />porch and living). <br />Response: Please see Structural response, and change to A-2.0. <br />8. Specify Window size of all windows. <br />Response: Please see added notes on all windows on Sheets A-2.0 and A-2.1 <br />9. All headers that are note 6x are required to be insulated with r-10 ridged insulation in 2x6 walls. <br />Response: Please see added not on A-2.0. <br />10. Specify required CFM on all Exhaust fans and range hood. Show whole house fai� size based <br />on table M1507.3.3. <br />Response: Please see added notes at each fan as well as reference to M1507.3.3 on whole <br />house fan at laundry room. <br />11. Provide handrails as required per R311.7.8 show on plans. <br />Response: Please see added not on sheet A-2.1 <br />12. The site plan general notes show the lot dimension as 210'x80', the site plan shovvs the east <br />property line as 80' and the west property lint as 60'. The north and south property lin�= appear to <br />be incorrect as well. <br />Response: dimensions were incorrect. The correct size is noted on the notes and the� plan as 125'- <br />0" x 60'-0" <br />13. Provide minimum 22"x30" attic access. Show on plans. <br />Response: Please note location in bedroom on sheet A-2.0 <br />14: where emergency escape and rescue opening are provided they shall have a sill height of not <br />more than 44" measured from the finished floor to the bottom of the clear opening. / R:310.1 IRC <br />Response: Please see note 13 on sheet A-2.0 and sill height called out on plan. <br />Sincerely, <br />� <br />Tim Go an <br />Z�.� <br />